569J

569J 16-25 PIPING RECOMMENDATIONS (SINGLE-CIRCUIT UNIT)

R-410A

 

 

 

 

 

 

Equivalent Length

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Ft

 

 

0-38

 

38-75

 

75-113

 

113-150

150-188

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

m

 

 

0-12

 

12-23

 

23-34

 

34-46

46-57

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Linear Length

 

 

 

 

 

 

 

 

 

 

 

Ft

 

 

0-25

 

25-50

 

50-75

 

75-100

100-125

 

Model

m

 

 

0-8

 

8-15

 

15-23

 

23-30

30-38

 

569J*16

Liquid Line

 

5/8

 

5/8

 

5/8

 

5/8

5/8

 

 

Max Lift

 

25

 

50

 

75

 

100

125

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Suction Line

 

1-1/8

 

1-3/8

 

1-3/8

 

1-3/8

1-3/8

1-5/8

 

Charge (lbs)

 

 

 

 

 

 

 

 

 

 

 

Novation

 

24.3

 

27.5

 

30.6

 

33.7

37.8

 

 

RTPF

 

42.7

 

45.9

 

49.0

 

52.1

56.2

 

 

 

 

 

 

 

 

 

 

 

 

 

569J*25

Liquid Line

 

5/8

 

5/8

 

5/8

 

5/8

5/8

 

 

Max Lift

 

25

 

50

 

71

 

77

63

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Suction Line

 

1-1/8

1-3/8

1-3/8

 

1-3/8

1-5/8

1-5/8

1-5/8

 

 

Charge (lbs)

 

37.8

 

40.8

 

44.6

 

47.8

51.1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Legend:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Equivalent

Equivalent tubing length, including effects of refrigeration specialties devices

 

 

 

Length

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Linear Length

Typical linear tubing length, (50% added to linear to define Equivalent Length for this table)

 

 

 

 

 

 

 

 

 

 

 

 

Liquid Line

Tubing size, inches OD.

 

 

 

 

 

 

 

 

 

 

Max Lift

Maximum liquid lift (indoor unit ABOVE outdoor unit only), at maximum permitted liquid line pressure drop —

 

S

Linear Length Less than 75 ft (23 m): Minimum 2.0° F subcooling entering TXV

 

 

 

S

Linear Length Greater than 75 ft (23m): Minimum 0.5° F subcooling entering TXV

 

 

 

 

 

 

 

 

 

 

 

 

Suction Line

Tube size, inches OD

 

 

 

 

 

 

 

 

 

 

Charge

Charge Quantity, lbs. Calculated for both liquid line sizes (where applicable), but only with larger suction line size

 

(where applicable)

 

 

 

 

 

 

 

 

 

 

 

NOTE:

For applications with equivalent length greater than 188 ft (57 m) and/0r linear length greater than 125 ft (38 m),

 

contact your local Carrier representative.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 