Table 11 — Fan Performance — 581A300 Low Heat Vertical Discharge Units*

AIRFLOW

 

 

 

 

 

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

 

 

0.2

 

 

0.4

 

 

 

0.6

 

 

 

0.8

 

 

1.0

 

(Cfm)

 

 

 

 

 

 

 

 

 

 

 

 

 

Rpm

Watts

Bhp

Rpm

Watts

 

Bhp

Rpm

Watts

Bhp

Rpm

 

Watts

Bhp

Rpm

Watts

Bhp

6,500

750

2,468

2.84

806

2,767

 

3.18

854

3,031

3.49

898

 

3,298

3.79

943

3,584

4.12

7,000

797

2,942

3.38

853

3,276

 

3.77

899

3,557

4.09

941

 

3,832

4.41

982

4,118

4.74

7,500

845

3,468

3.99

900

3,840

 

4.42

945

4,142

4.76

985

 

4,430

5.09

1024

4,721

5.43

8,000

892

4,045

4.65

948

4,462

 

5.13

991

4,789

5.51

1030

 

5,092

5.86

1067

5,391

6.20

8,500

939

4,677

5.38

995

5,141

 

5.91

1038

5,497

6.32

1076

 

5,818

6.69

1112

6,129

7.05

9,000

986

5,364

6.17

1042

5,882

 

6.76

1085

6,269

7.21

1122

 

6,611

7.60

1157

6,936

7.98

9,500

1033

6,108

7.03

1090

6,684

 

7.69

1132

7,105

8.17

1169

 

7,470

8.59

1203

7,813

8.99

10,000

1079

6,911

7.95

1137

7,550

 

8.68

1180

8,007

9.21

1216

 

8,399

9.66

1249

8,761

10.08

10,500

1126

7,773

8.94

1184

8,480

 

9.75

1227

8,978

10.33

1263

 

9,399

10.81

1296

9,782

11.25

11,000

1172

8,696

10.00

1232

9,475

 

10.90

1274

10,017

11.52

1310

 

10,468

12.04

1342

10,876

12.51

11,500

1219

9,681

11.13

1279

10,539

 

12.12

1322

11,127

12.80

1357

 

11,611

13.35

12,000

1265

10,732

12.34

1326

11,669

 

13.42

 

12,500

1311

11,848

13.63

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AIRFLOW

 

 

 

 

 

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

 

 

1.2

 

 

1.4

 

 

 

1.6

 

 

 

1.8

 

 

2.0

 

(Cfm)

 

 

 

 

 

 

 

 

 

 

 

 

 

Rpm

Watts

Bhp

Rpm

Watts

 

Bhp

Rpm

Watts

Bhp

Rpm

 

Watts

Bhp

Rpm

Watts

Bhp

6,500

988

3,900

4.49

1035

4,250

 

4.89

1082

4,634

5.33

1130

 

5,053

5.81

1177

5,499

6.32

7,000

1024

4,426

5.09

1066

4,760

 

5.48

1109

5,126

5.90

1153

 

5,524

6.35

1197

5,953

6.85

7,500

1063

5,026

5.78

1101

5,351

 

6.15

1141

5,702

6.56

1181

 

6,081

6.99

1222

6,490

7.46

8,000

1104

5,698

6.55

1140

6,020

 

6.92

1176

6,361

7.32

1213

 

6,727

7.74

1251

7,118

8.19

8,500

1146

6,443

7.41

1180

6,765

 

7.78

1214

7,103

8.17

1249

 

7,459

8.58

1283

7,837

9.01

9,000

1190

7,259

8.35

1222

7,586

 

8.73

1255

7,925

9.11

1287

 

8,276

9.52

1319

8,645

9.94

9,500

1235

8,148

9.37

1266

8,483

 

9.76

1296

8,824

10.15

1327

 

9,176

10.55

1357

9,541

10.97

10,000

1280

9,111

10.48

1310

9,456

 

10.88

1340

9,804

11.28

1369

 

10,158

11.68

1398

10,522

12.10

10,500

1326

10,147

11.67

1355

10,505

 

12.08

1384

10,862

12.49

 

11,000

1372

11,259

12.95

 

 

11,500

 

 

12,000

 

 

12,500

 

 

 

 

LEGEND

Bhp

Brake Horsepower Input to Fan

Watts

Input Watts to Motor

*Motor drive ranges: Low Range: 941-1176 High Range: 1014-1297

All other rpms require field-supplied drive.

Refer to page 23 for general Fan Performance Data notes.

NOTE: Maximum continuous bhp is:

Low Range: 8.63

High Range: 11.50

Table 12 — Fan Performance — 581A300 Medium Heat Vertical Discharge Units*

AIRFLOW

 

 

 

 

 

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

 

 

0.2

 

 

0.4

 

 

 

0.6

 

 

 

0.8

 

 

1.0

 

(Cfm)

 

 

 

 

 

 

 

 

 

 

 

 

 

Rpm

Watts

Bhp

Rpm

Watts

 

Bhp

Rpm

Watts

Bhp

Rpm

 

Watts

Bhp

Rpm

Watts

Bhp

6,500

775

2,600

2.99

825

2,872

 

3.30

871

3,130

3.60

915

 

3,400

3.91

959

3,692

4.25

7,000

826

3,115

3.58

875

3,408

 

3.92

918

3,679

4.23

959

 

3,954

4.55

1000

4,245

4.88

7,500

878

3,690

4.24

925

4,006

 

4.61

966

4,292

4.94

1005

 

4,575

5.26

1043

4,868

5.60

8,000

929

4,326

4.98

975

4,667

 

5.37

1015

4,970

5.72

1052

 

5,265

6.06

1088

5,564

6.40

8,500

981

5,029

5.78

1026

5,395

 

6.20

1064

5,717

6.58

1100

 

6,025

6.93

1134

6,332

7.28

9,000

1033

5,799

6.67

1076

6,191

 

7.12

1114

6,533

7.51

1148

 

6,856

7.89

1181

7,173

8.25

9,500

1085

6,640

7.64

1128

7,058

 

8.12

1164

7,421

8.54

1198

 

7,761

8.93

1229

8,091

9.31

10,000

1137

7,553

8.69

1179

8,000

 

9.20

1214

8,385

9.64

1247

 

8,741

10.05

1278

9,086

10.45

10,500

1190

8,542

9.82

1230

9,016

 

10.37

1265

9,424

10.84

1297

 

9,799

11.27

1327

10,158

11.68

11,000

1242

9,609

11.05

1282

10,111

 

11.63

1316

10,542

12.12

1347

 

10,937

12.58

1376

11,311

13.01

11,500

1294

10,756

12.37

1333

11,287

 

12.98

1367

11,741

13.50

 

12,000

1347

11,985

13.78

 

 

12,500

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AIRFLOW

 

 

 

 

 

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

 

 

1.2

 

 

1.4

 

 

 

1.6

 

 

 

1.8

 

 

2.0

 

(Cfm)

 

 

 

 

 

 

 

 

 

 

 

 

 

Rpm

Watts

Bhp

Rpm

Watts

 

Bhp

Rpm

Watts

Bhp

Rpm

 

Watts

Bhp

Rpm

Watts

Bhp

6,500

1004

4,016

4.62

1050

4,374

 

5.03

1098

4,769

5.48

1145

 

5,195

5.97

1192

5646

6.49

7,000

1041

4,559

5.24

1083

4,902

 

5.64

1126

5,277

6.07

1170

 

5,685

6.54

1214

6122

7.04

7,500

1081

5,179

5.96

1120

5,512

 

6.34

1159

5,872

6.75

1199

 

6,261

7.20

1240

6680

7.68

8,000

1124

5,875

6.76

1160

6,203

 

7.13

1196

6,553

7.54

1233

 

6,928

7.97

1270

7329

8.43

8,500

1168

6,647

7.64

1202

6,974

 

8.02

1235

7,318

8.42

1269

 

7,684

8.84

1304

8071

9.28

9,000

1214

7,495

8.62

1245

7,825

 

9.00

1277

8,168

9.39

1309

 

8,527

9.81

1341

8905

10.24

9,500

1260

8,421

9.69

1290

8,756

 

10.07

1320

9,100

10.47

1351

 

9,457

10.88

1381

9830

11.31

10,000

1308

9,425

10.84

1337

9,768

 

11.23

1365

10,116

11.63

1394

 

10,474

12.05

10,500

1356

10,510

12.09

1384

10,862

 

12.49

 

11,000

 

 

11,500

 

 

12,000

 

 

12,500

 

 

 

 

LEGEND

Bhp

Brake Horsepower Input to Fan

Watts

Input Watts to Motor

*Motor drive ranges: Low Range: 941-1176 High Range: 1014-1297

All other rpms require field-supplied drive.

Refer to page 23 for general Fan Performance Data notes.

NOTE: Maximum continuous bhp is:

Low Range: 8.63

High Range: 11.50

22