ALIGNMENT

HOLE

(IN BASE RAIL)

EDGE FLANGE

ALIGNMENT

HOLE SHOULD LINE UP WITH ROOF CURB EDGE FLANGE

WARNING: For vertical supply and return units, tools or parts could drop into ductwork and cause an injury. Install a 90-degree turn in the return ductwork between the unit and the conditioned space. If a 90-degree elbow cannot be installed, then a grille of sufficient strength and density should be installed to prevent objects from falling into the conditioned space.

Fig. 5 — Alignment Hole Details

 

RETURN

SUPPLY

 

OPENING

OPENING

 

CURB

CURB

 

RETURN

SUPPLY

ALIGNMENT

OPENING

OPENING

 

 

HOLES FOR

 

 

CURB-BOTH

 

 

SIDES

ROOF CURB

Fig. 6 — Alignment Hole Location

IV. STEP 4 — FIELD FABRICATE DUCTWORK

On vertical units, secure all ducts to roof curb and building structure. Do not connect ductwork to unit. For horizontal applications, field-supplied flanges should be attached to horizontal discharge openings and all ductwork secured to the flanges. Insulate and weatherproof all external duct- work, joints, and roof openings with counter flashing and mastic in accordance with applicable codes.

Ducts passing through an unconditioned space must be insulated and covered with a vapor barrier.

If a plenum return is used on a vertical unit, the return should be ducted through the roof deck to comply with appli- cable fire codes.

A minimum clearance is not required around ductwork. Cab- inet return-air static pressure (a negative condition) shall not exceed 0.35 in. wg with economizer or 0.45 in. wg with- out economizer.

These units are designed for a minimum continuous return- air temperature in heating of 50 F (dry bulb), or an intermit- tent operation down to 45 F (dry bulb), such as when used with a night set-back thermostat.

To operate at lower return-air temperatures, a field-supplied outdoor-air temperature control must be used to initiate both stages of heat when the temperature is below 45 F. Indoor comfort may be compromised when these lower air tempera- tures are used with insufficient heating temperature rise.

V. STEP 5 — MAKE UNIT DUCT CONNECTIONS

A. Vertical Configuration

Unit is shipped for vertical supply and return duct connec- tions. Ductwork openings are shown in Fig. 1 and 4. Duct connections for vertical configuration are shown in Fig. 7. Field-fabricated concentric ductwork may be connected as shown in Fig. 8 and 9. The unit is designed to attach the ductwork to the roof curb. Do not attach duct directly to the unit.

B. Horizontal Applications

Horizontal units are shipped with outer panels that allow for side by side horizontal duct connections. If specified during ordering, the unit will be shipped with the vertical duct openings blocked off from the factory, ready for side supply installation. If the horizontal supply/return option was not specified at time of ordering the unit, a field-installed acces- sory kit is required to convert the vertical unit into a hori- zontal supply configuration.

Installation of the duct block-off covers should be completed prior to placing the unit unless sufficient side clearance is available. A minimum of 66 in. is required between the unit and any obstruction to install the duct block-off covers. Side supply duct dimensions and locations are shown on Fig. 4. Install ductwork to horizontal duct flange connections on side of unit.

ECONOMIZER

SEE

SEE

HEAT

EXCHANGER

NOTE

NOTE

 

AIR

 

AIR

IN

 

OUT

NOTE: Do not drill in this area; damage to basepan may result in water leak.

Fig. 7 — Air Distribution — Vertical Supply/Return

ECONOMIZER

SEE

 

SEE

HEAT

 

EXCHANGER

NOTE

 

NOTE

 

AIR OUT

AIR IN

AIR OUT

 

NOTE: Do not drill in this area; damage to basepan may result in water leak.

Fig. 8 — Air Distribution — Concentric Duct

9

Page 9
Image 9
Bryant 581A IV. Field Fabricate Ductwork, Make Unit Duct Connections, Vertical Configuration, Horizontal Applications

581A specifications

The Bryant 581A is a pivotal model in the realm of heating, ventilation, and air conditioning (HVAC) systems, known for its robust performance and energy efficiency. As part of the Bryant product lineup, the 581A offers a blend of innovative technologies combined with reliable engineering, making it a suitable choice for both residential and light commercial applications.

One of the standout features of the Bryant 581A is its outstanding energy efficiency. With a Seasonal Energy Efficiency Ratio (SEER) rating of up to 16, this model meets Energy Star qualifications, ensuring that homeowners can enjoy lower utility bills while helping to reduce their environmental footprint. The efficiency is further enhanced by the unit’s environmentally friendly refrigerant, which not only improves performance but also aligns with modern sustainability standards.

Another key characteristic of the Bryant 581A is its durable construction. Designed to withstand various weather conditions, the unit features a robust cabinet that protects internal components. This durability not only prolongs the lifespan of the system but also minimizes the need for frequent maintenance or repairs. The coil design is optimized for heat transfer efficiency, enhancing the unit's overall performance in both cooling and heating modes.

In terms of technology, the Bryant 581A incorporates advanced control systems that enable precise temperature regulation. The multi-stage cooling capabilities ensure that the system can adapt to varying temperature demands, providing comfort in all seasons. Additionally, the model is compatible with smart thermostats, allowing homeowners to control their HVAC system remotely via smartphone or other connected devices.

Noise reduction is another aspect where the Bryant 581A excels. Equipped with a variable-speed compressor and sound-dampening features, this model operates quietly, minimizing disruption in residential or office environments. This focus on acoustic comfort makes it an ideal choice for those who value a peaceful living or working space.

Overall, the Bryant 581A represents an excellent balance of efficiency, durability, and modern technology. With features aimed at enhancing user comfort and reducing operational costs, it stands out as a reliable solution in the competitive HVAC market. Whether for new installations or replacements, the Bryant 581A is a testament to the brand’s commitment to quality and innovation in home climate control.