installation, start-up and service instructions
581A
SizesSINGLE PACKAGE ROOFTOP
ELECTRIC COOLING/GAS HEATING UNITS
CONTENTS
Page
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . 1
INSTALLATION | ||
I. Step 1 — Provide Unit Support | . . . 1 | |
II. Step 2 — Rig and Place Unit | . . . 3 | |
III. Step 3 — Field Fabricate Ductwork | . . . 7 | |
IV. Step 4 — Make Unit Duct Connections . . . . | . . . 7 | |
V. Step 5 — Install Flue Hood and Wind |
| |
Baffle | . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . | . . . 7 |
VI. Step 6 — Trap Condensate Drain | . . . 8 | |
VII. Step 7 | — Install Gas Piping | . . . 8 |
VIII. Step 8 | — Make Electrical Connections . . . . | . . . 8 |
IX. Step 9 | — Make |
|
Adjustments | . . . 9 | |
X. Step 10 — Install | . . 11 | |
XI. Step 11 — Install All Accessories | . . 13 |
SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . .
SAFETY CONSIDERATIONS
Installation and servicing of
Untrained personnel can perform the basic maintenance functions of cleaning coils and filters and replacing filters. All other operations should be performed by trained service personnel. When working on
Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloth for unbrazing operations. Have fire extinguishers available for all brazing operations.
WARNING: Before performing service or mainte- nance operations on unit, turn off mail power switch to unit. electrical shock could cause personal injury.
Cancels: II | II |
| 6/15/99 |
WARNING:
1.Improper installation, adjustment, alteration, service, or maintenance can cause property damage, personal injury, or loss of life. Refer to the User’s Information Manual provided with this unit for more details.
2.Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
What to do if you smell gas:1.DO NOT try to light any appliance.
2.DO NOT touch any electrical switch, or use any phone in your building.
3.IMMEDIATELY call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
4.If you cannot reach your gas supplier, call the fire department.
WARNING: Disconnect gas piping from unit when pressure testing at pressure greater than 0.5 psig. Pressures greater than 0.5 psig will cause gas valve damage resulting in hazardous condition. If gas valve is subjected to pressure greater than 0.5 psig, it must be replaced before use. When pressure testing field- supplied gas piping at pressures of 0.5 psig or less, a unit connected to such piping must be isolated by clos- ing the manual gas valve(s).
IMPORTANT: Units have high ambient operating limits. If limits are exceeded, the units will automatically lock the compressor out of operation. Manual reset will be required to restart the compressor.
INSTALLATION
I. STEP 1 — PROVIDE UNIT SUPPORT
A. Roof Curb
Assemble or install accessory roof curb or horizontal supply roof curb in accordance with instructions shipped with this accessory. See Fig. 1 and 2. Install insulation, cant strips, roofing, and counter flashing as shown. Ductwork can be installed to roof curb or horizontal supply roof curb before unit is set in place.