Bryant operation manual Base Unit Dimensions 581A155 and

Models: 581A

1 40
Download 40 pages 46.88 Kb
Page 4
Image 4
Fig. 4 — Base Unit Dimensions; 581A155 and 180

 

STD UNIT

ECONO-

CORNER

CORNER

CORNER

CORNER

 

 

 

 

 

 

UNIT

MIZER

DIM A

DIM B

DIM C

WEIGHT

 

A

 

B

 

C

 

D

581A

WEIGHT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Lb

Kg

Lb

Kg

Lb

 

Kg

Lb

 

Kg

Lb

 

Kg

Lb

 

Kg

ft-in.

mm

ft-in.

mm

ft-in.

mm

155

1725

782

110

50

427

 

194

390

 

177

438

 

199

470

 

213

3-3

991

3-5

1051

1-10

559

180

1800

816

110

50

417

 

189

399

 

181

481

 

218

503

 

228

3-2

961

3-6

1070

1-10

559

—4—

POWER EXHAUST/ BAROMETRIC RELIEF (ACCESSORY ONLY)

NOTES:

1.

Refer to print for roof curb accessory dimensions.

2.

Dimensions in ( ) are in millimeters.

3.Manual background Center of Gravity.

4.Manual background Direction of airflow.

5.Ductwork to be attached to accessory roof curb only.

6.Minimum clearance:

Rear: 7 ft-0 in. (2134) for coil removal. This dimension can be reduced to 4 ft-0 in. (1219) if conditions permit coil removal from the top.

4 ft-0 in. (1219) to combustible surfaces, all four sides (includes between units).

Left side: 4 ft-0 in.(1219) for proper condenser coil airflow.

Front: 4 ft-0 in. (1219) for control box access.

Right side: 4 ft-0 in. (1219) for proper operation of damper and power exhaust if so equipped.

Top: 6 ft-0 in. (1829) to assure proper condenser fan operation.

Bottom: 14 in. (356) to combustible surfaces (when not using curb).

Control box side: 3 ft-0 in. (914) to ungrounded surfaces, non-combustible.

Control box side: 3 ft-6 in. (1067) to block or concrete walls, or other grounded surfaces.

Local codes or jurisdiction may prevail.

7.With the exception of clearance for the condenser coil and the damper/ power exhaust as stated in Note no. 6, a removable fence or barricade requires no clearance.

8.Dimensions are from outside of corner post. Allow 0 ft-5/16in. (8) on each side for top cover drip edge.

581A180 ONLY

POWER EXHAUST/

BAROMETRIC RELIEF (ACCESSORY ONLY)

FIELD

SUPPLIED

Fig. 4 — Base Unit Dimensions; 581A155 and 180

Page 4
Image 4