Sensor Assembly — Install the sensor assembly in the loca- tion shown in Fig. 26.
Motor Mount — To ensure proper fan height, replace the existing motor mount with the new motor mount provided with accessory.
Transformer
Motormaster® I Control — Recommended mounting location is on the inside of the panel to the left of the control box. The control should be mounted on the inside of the panel, verti- cally, with leads protruding from bottom of extrusion.
B. Motormaster III Control Installation (581A240)
Install
Wind baffles must be
CAUTION: To avoid damage to the refrigerant coils and electrical components, use recommended screw sizes only. Use care when drilling holes.
MOTORMASTER
SENSOR
LOCATION
HAIRPIN END
NOTES:
1.All sensors are located on the eighth hairpin up from the bottom.
2.Field installed tubing insulation is required to be installed over the TXV (thermostatic expansion valve) bulb and capillary tube for proper operation at low ambients. Tubing insulation is only required on the portion of suction line located between indoor and outdoor section.
Fig. 26 — Motormaster I and Motormaster III Sensor
Locations
Replace Outdoor Motor
Replace
Install Motormaster III Controls
Only one Motormaster III control is required per unit.
Sensor — Install the sensor for thermistor input control in the location shown in Fig. 26. Connect sensor leads to the purple and grey control signal leads on the Motormaster III control.
Signal Selection Switch — Remove the cover of the Motor- master III control. Set the switch to accept the thermistor sensor input signal. Set the frequency to match the unit power supply (60 Hz).
Motormaster III Control — Recommended mounting location is beneath the control box, mounted to the partition that sep- arates the control box section from the indoor section.
NOTE: If unit power is supplied through the roof curb and basepan of the unit, mount the Motormaster III control on the corner post adjacent to the conduit running from the basepan to the bottom of the control box.
START-UP
Use the following information and
I. UNIT PREPARATION
Check that unit has been installed in accordance with these installation instructions and all applicable codes.
II. SERVICE VALVES
Ensure that the liquid line service valve is open. Damage to the compressor could result if it is left closed.
III. COMPRESSOR MOUNTING
Compressors are internally spring mounted. Do not loosen or remove compressor holddown bolts.
IV. REFRIGERANT SERVICE PORTS
Each refrigerant system has a total of 3
V. COMPRESSOR ROTATION
It is important to be certain the compressors are rotating in the proper direction. To determine whether or not compres- sors are rotating in the proper direction:
1.Connect service gages to suction and discharge pres- sure fittings.
2.Energize the compressor.
3.The suction pressure should drop and the discharge pressure should rise, as is normal on any
If the suction pressure does not drop and the discharge pres- sure does not rise to normal levels:
1.Note that the evaporator fan is probably also rotating in the wrong direction.
2.Turn off power to the unit.
3.Reverse any two of the incoming power leads.
4.Turn on power to the compressor.
The suction and discharge pressure levels should now move to their normal