![Fig. 21 — Seal Strip Location](/images/new-backgrounds/33375/3337523x1.webp)
3.Secure lower filter retainer and long section of filter support bracket to unit. See Fig. 22. Leave screws loose on 180 and 240 units.
4.Slide baffle (sizes 180 and 240) behind lower filter retainer and tighten screws.
5.Loosen sheet metal screws for top panel of base unit- located above
6.Match notches in hood top panel with unit top panel screws. Insert hood flange between top panel flange and unit. Tighten screws.
7.Hold hood side panel flanges flat against unit, and install screws removed in Step 5.
Fig. 21 — Seal Strip Location
BAFFLE (180 AND 240 SIZES ONLY)
LOWER FILTER
RETAINER
FILTER SUPPORT
BRACKET
HOOD SIDE
PANELS (2)
HOOD TOP PANEL
BAFFLE
(180 AND
240
ONLY)
LOWER
FILTER
RETAINER
FILTER SUPPORT
BRACKET
HOOD DRAIN PAN
UPPER FILTER RETAINER
NOTE: The outdoor air hood comes with a baffle which is used on sizes 180 and 240 only. Discard baffle for size 155 units.
Fig. 22 — Outdoor-Air Hood Details
8.Insert
9.Attach remaining short section of filter support bracket.
A.Enthalpy Control Installation
NOTE: The accessory
1.Remove and discard the
economizer control module (between terminals SR and +). See Fig. 18.
2.Remove black wire assembly containing the
minal SO and the
between economizer control module terminals SR and +, replacing the jumper removed in Step 1. See Fig. 18.
3.Disconnect the blue wire from the OAT.
4.Remove OAT from the outside of the economizer. See Fig. 17.
5.Mount the enthalpy sensor (Fig. 23) to the econo- mizer on the outside of the unit (in the same location from which the OAT was removed) using the 2 screws provided. See Fig. 17.
6.Reconnect the blue wire removed in Step 3 to the enthalpy sensor terminal +.
7.Cut the violet wire provided to desired length and terminate with
8.Set changeover set point to the desired location. See Fig. 24.
NOTE: For maximum benefit of outdoor air, set the enthalpy control to the “A” setting. At this setting, when the relative humidity is 50% and the outdoor air is below 74 F, the relay contacts on the sensor will be closed.
9. Reinstall economizer hoods if removed.
IMPORTANT: Be sure all seal strips and RTV sealant are intact. A watertight seal to inside of unit must be maintained.