Table 10 — Fan Performance — 581A240360 (High Heat Units)
|
|
|
|
| AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) |
|
|
|
| ||||||
CFM |
| 0.2 |
|
| 0.4 |
|
| 0.6 |
|
| 0.8 |
|
| 1.0 |
|
| Rpm | Watts | Bhp | Rpm | Watts | Bhp | Rpm | Watts | Bhp | Rpm | Watts | Bhp | Rpm | Watts | Bhp |
6,000 | 868 | 2752 | 3.26 | 934 | 2987 | 3.54 | 997 | 3227 | 3.83 | 1058 | 3470 | 4.12 | 1115 | 3716 | 4.41 |
6,500 | 929 | 3201 | 3.80 | 991 | 3436 | 4.08 | 1051 | 3675 | 4.36 | 1108 | 3917 | 4.65 | 1162 | 4163 | 4.94 |
7,000 | 991 | 3687 | 4.37 | 1049 | 3923 | 4.65 | 1105 | 4161 | 4.94 | 1159 | 4403 | 5.22 | 1211 | 4647 | 5.51 |
7,500 | 1054 | 4211 | 5.00 | 1109 | 4447 | 5.28 | 1161 | 4686 | 5.56 | 1213 | 4926 | 5.84 | 1262 | 5170 | 6.13 |
8,000 | 1117 | 4773 | 5.66 | 1168 | 5009 | 5.94 | 1218 | 5247 | 6.22 | 1267 | 5488 | 6.51 | 1314 | 5731 | 6.80 |
8,500 | 1180 | 5373 | 6.37 | 1229 | 5609 | 6.65 | 1277 | 5847 | 6.94 | 1323 | 6088 | 7.22 | 1368 | 6331 | 7.51 |
9,000 | 1244 | 6011 | 7.13 | 1290 | 6247 | 7.41 | 1335 | 6485 | 7.69 | 1380 | 6726 | 7.98 | 1423 | 6968 | 8.27 |
9,500 | 1308 | 6687 | 7.93 | 1352 | 6924 | 8.21 | 1395 | 7162 | 8.50 | 1437 | 7402 | 8.78 | 1479 | 7644 | 9.07 |
10,000 | 1372 | 7401 | 8.78 | 1414 | 7638 | 9.06 | 1455 | 7876 | 9.34 | 1496 | 8117 | 9.63 | 1535 | 8358 | 9.92 |
|
|
|
|
| AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) |
|
|
|
|
| ||||||||
CFM |
| 1.2 |
|
| 1.4 |
|
|
|
| 1.6 |
|
| 1.8 |
|
| 2.0 |
|
|
| Rpm | Watts | Bhp | Rpm | Watts |
| Bhp | Rpm |
| Watts | Bhp | Rpm | Watts | Bhp | Rpm | Watts |
| Bhp |
6,000 | 1171 | 3965 | 4.70 | 1224 | 4216 |
| 5.00 | 1276 |
| 4469 | 5.30 | 1326 | 4726 | 5.61 | 1374 | 4983 |
| 5.91 |
6,500 | 1215 | 4410 | 5.23 | 1266 | 4659 |
| 5.53 | 1316 |
| 4911 | 5.83 | 1364 | 5165 | 6.13 | 1411 | 5421 |
| 6.43 |
7,000 | 1262 | 4894 | 5.81 | 1311 | 5142 |
| 6.10 | 1358 |
| 5392 | 6.40 | 1404 | 5645 | 6.70 | 1449 | 5899 |
| 7.00 |
7,500 | 1310 | 5415 | 6.42 | 1357 | 5663 |
| 6.72 | 1403 |
| 5912 | 7.01 | 1447 | 6164 | 7.31 | 1490 | 6416 |
| 7.61 |
8,000 | 1360 | 5976 | 7.09 | 1405 | 6222 |
| 7.38 | 1449 |
| 6471 | 7.68 | 1492 | 6721 | 7.97 | 1533 | 6973 |
| 8.27 |
8,500 | 1412 | 6575 | 7.80 | 1455 | 6821 |
| 8.09 | 1497 |
| 7068 | 8.39 | 1538 | 7318 | 8.68 | — | — |
| — |
9,000 | 1465 | 7212 | 8.56 | 1506 | 7457 |
| 8.85 | 1547 |
| 7705 | 9.14 | — | — | — | — | — | — |
|
9,500 | 1519 | 7888 | 9.36 | — | — |
| — | — | — | — | — | — | — | — | — | — |
|
|
10,000 | — | — | — | — | — | — | — | — |
| — | — | — | — | — | — | — |
|
|
|
|
|
|
| AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) |
|
|
|
|
|
| ||||||||
CFM |
| 2.2 |
|
| 2.4 |
|
|
|
| 2.6 |
|
| 2.8 |
|
|
| 3.0 |
|
|
| Rpm | Watts | Bhp | Rpm | Watts |
| Bhp | Rpm |
| Watts | Bhp | Rpm | Watts |
| Bhp | Rpm | Watts |
| Bhp |
6,000 | 1422 | 5243 | 6.22 | 1468 | 5505 |
| 6.53 | 1513 |
| 5768 | 6.84 | — | — |
| — | — | — | — |
|
6,500 | 1456 | 5679 | 6.74 | 1501 | 5938 |
| 7.04 | 1544 |
| 6199 | 7.35 | — | — |
| — | — | — | — |
|
7,000 | 1493 | 6155 | 7.30 | 1536 | 6412 |
| 7.61 | — |
| — | — | — | — | — | — | — | — |
|
|
7,500 | 1533 | 6670 | 7.91 | — | — |
| — | — | — | — | — | — | — |
| — | — | — |
|
|
8,000 | — | — | — | — | — | — | — | — |
| — | — | — | — |
| — | — | — |
|
|
8,500 | — | — | — | — | — | — | — | — |
| — | — | — | — |
| — | — | — |
|
|
9,000 | — | — | — | — | — | — | — | — |
| — | — | — | — |
| — | — | — |
|
|
9,500 | — | — | — | — | — | — | — | — |
| — | — | — | — |
| — | — | — |
|
|
10,000 | — | — | — | — | — | — | — | — |
| — | — | — | — |
| — | — | — |
|
|
|
| LEGEND |
Bhp | — | Brake Horsepower |
FIOP | — | |
Watts — | Input Watts to Motor |
*Standard
NOTES:
1.Maximum continuous bhp for the standard motor is 9.47 (for
2.Static pressure losses (i.e., economizer) must be added to external static pressure before entering Fan Performance table.
3.Interpolation is permissible. Do not extrapolate.4
4.Fan performance is based on wet coils, clean filters, and casing losses. See Table 13 for accessory/FIOP static pressure information.
5.Extensive motor and drive testing on these units ensures that the full bhp and watts range of the motor can be utilized with confidence. Using your fan motors up to the watts or bhp rating shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected.
6.Use of a