Bryant 581A operation manual Air Quantity Limits, Evaporator Fan Motor Specifications

Models: 581A

1 40
Download 40 pages 46.88 Kb
Page 23
Image 23

Table 11 — Air Quantity Limits

UNIT

MINIMUM

MAXIMUM

581A

CFM

CFM

155

3600

6,000

180

4500

7,500

240

6000

10,000

Table 12 — Evaporator Fan Motor Specifications

UNIT

NOMINAL

VOLTAGE

MAX

EFF.

MAX

MAX

MAX

581A

Hp

WATTS

BHP

BkW

AMPS

 

 

155

2.9

208

2700

85.8%

3.13

2.34

9.46

(Standard

2.9

230

2700

85.8%

3.13

2.34

8.6

Motor)

2.9

460

2700

85.8%

3.13

2.34

4.3

155

3.7

208

3775

85.8%

4.38

3.27

10.5

(Optional

3.7

230

3775

85.8%

4.38

3.27

10.5

Motor)

3.7

460

3775

85.8%

4.38

3.27

4.8

180

5

208

5180

87.5%

6.13

4.57

15.8

5

230

5180

87.5%

6.13

4.57

15.8

 

5

460

5180

87.5%

6.13

4.57

7.9

240

7.5

208

7915

88.5%

9.47

7.06

22

7.5

230

8640

88.5%

10.33

7.71

22

 

7.5

460

8640

88.5%

10.33

7.71

13

BHP — Brake Horsepower

Table 13 — Accessory/FIOP Economizer Static Pressure (in. wg)

UNIT

UNIT

CFM

ECONOMIZER

581A

VOLTAGE

PRESSURE DROP

 

 

 

3,750

.03

155, 180

All

4,000

.03

5,000

.05

 

 

 

6,000

.07

 

 

7,500

.10

 

 

6,000

.07

240

All

7,200

.09

9,000

.11

 

 

 

 

10,000

.12

LEGEND

bhp — Brake Horsepower FIOP — Factory-Installed Option

NOTES:

1.The factory-assembled horizontal adapter substantially improves fan performance. See Fig. 27.

2.The static pressure must be added to external static pressure. The sum and the evaporator entering-air cfm should then be used in con- junction with the Fan Performance table to determine blower rpm, bhp, and watts.

Table 14 — Fan RPM at Motor Pulley Setting*

581A

0

1/

1

11/

2

21/

3

31/

2

4

41/

5

51/

6

 

 

2

 

2

 

2

 

 

 

2

 

2

 

155†

††

††

††

††

1064

1035

1006

 

978

949

920

891

863

834

 

 

 

 

 

 

 

 

 

 

 

 

 

 

155**

††

††

††

††

1426

1393

1360

1327

1294

1261

1227

1194

1161

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

180†

††

††

††

††

1021

1002

984

 

965

947

928

910

891

873

 

 

 

 

 

 

 

 

 

 

 

 

 

 

180**

††

††

††

††

1200

1178

1156

1134

1112

1091

1069

1047

1025

 

 

 

 

 

 

 

 

 

 

 

 

 

 

240†

††

††

††

††

1151

1132

1114

1095

1077

1058

1040

1021

1002

 

 

 

 

 

 

 

 

 

 

 

 

 

 

240**

††

††

††

††

1369

1347

1325

1303

1281

1259

1237

1215

1193

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*Approximate fan rpm shown. †Indicates standard drive package. **Indicates alternate drive package.

††Due to belt and pulley style, pulley cannot be set to this number of turns open.

—23—

Page 23
Image 23