Table 11 — Air Quantity Limits
UNIT | MINIMUM | MAXIMUM |
581A | CFM | CFM |
155 | 3600 | 6,000 |
180 | 4500 | 7,500 |
240 | 6000 | 10,000 |
Table 12 — Evaporator Fan Motor Specifications
UNIT | NOMINAL | VOLTAGE | MAX | EFF. | MAX | MAX | MAX | |
581A | Hp | WATTS | BHP | BkW | AMPS | |||
|
| |||||||
155 | 2.9 | 208 | 2700 | 85.8% | 3.13 | 2.34 | 9.46 | |
(Standard | 2.9 | 230 | 2700 | 85.8% | 3.13 | 2.34 | 8.6 | |
Motor) | 2.9 | 460 | 2700 | 85.8% | 3.13 | 2.34 | 4.3 | |
155 | 3.7 | 208 | 3775 | 85.8% | 4.38 | 3.27 | 10.5 | |
(Optional | 3.7 | 230 | 3775 | 85.8% | 4.38 | 3.27 | 10.5 | |
Motor) | 3.7 | 460 | 3775 | 85.8% | 4.38 | 3.27 | 4.8 | |
180 | 5 | 208 | 5180 | 87.5% | 6.13 | 4.57 | 15.8 | |
5 | 230 | 5180 | 87.5% | 6.13 | 4.57 | 15.8 | ||
| 5 | 460 | 5180 | 87.5% | 6.13 | 4.57 | 7.9 | |
240 | 7.5 | 208 | 7915 | 88.5% | 9.47 | 7.06 | 22 | |
7.5 | 230 | 8640 | 88.5% | 10.33 | 7.71 | 22 | ||
| 7.5 | 460 | 8640 | 88.5% | 10.33 | 7.71 | 13 |
BHP — Brake Horsepower
Table 13 — Accessory/FIOP Economizer Static Pressure (in. wg)
UNIT | UNIT | CFM | ECONOMIZER | |
581A | VOLTAGE | PRESSURE DROP | ||
| ||||
|
| 3,750 | .03 | |
155, 180 | All | 4,000 | .03 | |
5,000 | .05 | |||
| ||||
|
| 6,000 | .07 | |
|
| 7,500 | .10 | |
|
| 6,000 | .07 | |
240 | All | 7,200 | .09 | |
9,000 | .11 | |||
|
| |||
|
| 10,000 | .12 |
LEGEND
bhp — Brake Horsepower FIOP —
NOTES:
1.The
2.The static pressure must be added to external static pressure. The sum and the evaporator
Table 14 — Fan RPM at Motor Pulley Setting*
581A | 0 | 1/ | 1 | 11/ | 2 | 21/ | 3 | 31/ | 2 | 4 | 41/ | 5 | 51/ | 6 |
|
| 2 |
| 2 |
| 2 |
|
|
| 2 |
| 2 |
| |
155† | †† | †† | †† | †† | 1064 | 1035 | 1006 |
| 978 | 949 | 920 | 891 | 863 | 834 |
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
155** | †† | †† | †† | †† | 1426 | 1393 | 1360 | 1327 | 1294 | 1261 | 1227 | 1194 | 1161 | |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
180† | †† | †† | †† | †† | 1021 | 1002 | 984 |
| 965 | 947 | 928 | 910 | 891 | 873 |
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
180** | †† | †† | †† | †† | 1200 | 1178 | 1156 | 1134 | 1112 | 1091 | 1069 | 1047 | 1025 | |
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
240† | †† | †† | †† | †† | 1151 | 1132 | 1114 | 1095 | 1077 | 1058 | 1040 | 1021 | 1002 | |
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
240** | †† | †† | †† | †† | 1369 | 1347 | 1325 | 1303 | 1281 | 1259 | 1237 | 1215 | 1193 | |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
*Approximate fan rpm shown. †Indicates standard drive package. **Indicates alternate drive package.
††Due to belt and pulley style, pulley cannot be set to this number of turns open.