V. BELT TENSION ADJUSTMENT

10. Disconnect wiring connections and remove the 4 mounting bolts.

11. Remove the motor.

12. To install the new motor, reverse Steps 1-11.

V. BELT TENSION ADJUSTMENT

To adjust belt tension:

1. Loosen fan motor bolts.

2. Size 155 Units:

Move motor mounting plate up or down for proper belt tension (1/2 in. deflection with one finger).

Size 180 and 240 Units:

Turn motor jacking bolt to move motor mounting plate up or down for proper belt tension (3/8 in. deflec- tion at midspan with one finger [9 lb force]).

3. Tighten nuts.

4. Adjust bolts and nut on mounting plate to secure motor in fixed position.

VI. CONDENSER-FAN ADJUSTMENT

A. 581A155 and 180 Units (Fig. 33)

1.

Shut off unit power supply.

2.

Remove access panel(s) closest to the fan to be

 

adjusted.

3.

Loosen fan hub setscrews.

4.

Adjust fan height on shaft using a straightedge

Fig. 31 — 581A155 Evaporator-Fan Motor Adjustment

placed across the fan orifice.

 

5.

Tighten setscrews and replace panel(s).

6.

Turn on unit power.

B. 581A240 Units (Fig. 34)

1.

Shut off unit power supply.

2.

Remove fan top-grille assembly and loosen fan hub

 

screws.

3.

Adjust fan height on unit, using a straightedge

 

placed across the fan orifice.

NOTE: A 31/2-in. bolt and threaded plate are included in the installer’s packet. They should be added to the motor support channel below the motor mounting plate to aid in raising the motor. The plate part number is 50DP503842. The adjustment bolt is 3/8 - 16 x 13/4-in. LG.

Fig. 32 — 581A180 and 240 Evaporator-Fan Motor Section

6.Remove jacking bolt and tapped jacking bolt plate.

7.Remove the 2 screws that secure the motor mounting plate to the motor support channel.

8.Remove the 3 screws from the end of the motor sup- port channel that interfere with the motor slide path.

9.Slide out the motor and motor mounting plate.

NOTE: Dimension is in inches.

Fig. 33 — Condenser Fan Adjustment, 581A155 and 180

NOTE: Dimension is in inches.

Fig. 34 — Condenser Fan Adjustment, 581A240