Table 9 — Fan Performance — 581A180360 (High Heat Units)

 

 

 

 

 

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

CFM

 

0.2

 

 

04

 

 

0.6

 

 

0.8

 

 

1.0

 

 

Rpm

Watts

Bhp

Rpm

Watts

Bhp

Rpm

Watts

Bhp

Rpm

Watts

Bhp

Rpm

Watts

Bhp

4500

753

1307

1.53

786

1404

1.65

861

1644

1.93

932

1893

2.22

997

2150

2.52

4800

747

1384

1.62

818

1603

1.88

890

1852

2.17

958

2108

2.47

1022

2373

2.78

5100

775

1571

1.84

850

1822

2.14

920

2079

2.44

986

2344

2.75

1048

2616

3.07

5700

849

2054

2.41

918

2323

2.73

982

2598

3.05

1044

2879

3.38

1102

3166

3.71

6000

886

2329

2.73

952

2607

3.06

1015

2891

3.39

1074

3180

3.73

1130

3474

4.08

6300

924

2628

3.08

987

2915

3.42

1047

3207

3.76

1105

3504

4.11

1160

3807

4.46

6600

962

2951

3.46

1023

3246

3.81

1081

3547

4.16

1136

3853

4.52

1190

4163

4.88

6900

1000

3298

3.87

1059

3603

4.23

1115

3912

4.59

1168

4225

4.96

1220

4543

5.33

7200

1038

3672

4.31

1095

3986

4.67

1149

4303

5.05

1201

4625

5.42

1251

4950

5.81

7500

1077

4072

4.78

1131

4394

5.15

1184

4720

5.54

1234

5050

5.92

 

 

 

 

 

 

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

 

CFM

 

1.2

 

 

 

1.4

 

 

 

1.6

 

 

 

1.8

 

 

2.0

 

 

 

Rpm

Watts

Bhp

Rpm

 

Watts

Bhp

Rpm

 

Watts

Bhp

Rpm

Watts

Bhp

Rpm

Watts

 

Bhp

4500

1060

2414

2.83

1119

 

2685

3.15

1175

 

2964

3.48

 

1230

3250

3.81

1282

3542

 

4.15

4800

1082

2644

3.10

1140

 

2922

3.43

1195

 

3207

3.76

 

1248

3498

4.10

1299

3795

 

4.45

5100

1106

2894

3.39

1163

 

3178

3.73

1216

 

3470

4.07

 

1268

3767

4.42

1319

4071

 

4.77

5700

1157

3459

4.06

1211

 

3757

4.41

1262

 

4061

4.76

 

1312

4371

5.13

1360

4686

 

5.50

6000

1184

3774

4.43

1236

 

4080

4.79

1287

 

4391

5.15

 

1335

4707

5.52

1382

5029

 

5.90

6300

1212

4114

4.83

1263

 

4427

5.19

1312

 

4745

5.57

 

1359

5067

5.94

 

6600

1241

4478

5.25

1290

 

4798

5.63

1338

 

5122

6.01

 

 

6900

1270

4866

5.71

 

 

 

 

 

 

 

 

7200

 

 

 

 

7500

 

 

 

 

 

 

 

 

 

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

 

CFM

 

2.2

 

 

2.4

 

 

 

 

2.6

 

 

2.8

 

 

3.0

 

 

 

Rpm

Watts

Bhp

Rpm

Watts

 

Bhp

Rpm

 

Watts

Bhp

Rpm

Watts

Bhp

Rpm

Watts

 

Bhp

4500

1332

3841

4.50

1381

4145

 

4.86

1428

 

4456

5.23

1473

4772

5.60

1518

5095

 

5.98

4800

1349

4100

4.81

1397

4409

 

5.17

1443

 

4725

5.54

1488

5046

5.92

 

5100

1367

4380

5.14

1414

4695

 

5.51

1460

 

5016

5.88

 

5700

1407

5007

5.87

 

 

 

6000

 

 

 

6300

 

 

 

6600

 

 

 

6900

 

 

 

7200

 

 

 

7500

 

 

 

 

 

LEGEND

Bhp

Brake Horsepower

FIOP

Factory-Installed Option

Watts —

Input Watts to Motor

*Standard low-medium static drive range is 873 to 1021 rpm. Alternate high-static drive range is 1025 to 1200. Other rpms require a field- supplied drive.

NOTES:

1.Maximum continuous bhp for the standard motor is 6.13. The maxi- mum continuous watts is 5180. Do not adjust motor rpm such that motor maximum bhp and/or watts is exceeded at the maximum operating cfm.

2.Static pressure losses (i.e., economizer) must be added to external static pressure before entering Fan Performance table.

3.Interpolation is permissible. Do not extrapolate.

4.Fan performance is based on wet coils, clean filters, and casing losses. See Table 13 for accessory/FIOP static pressure information.

5.Extensive motor and drive testing on these units ensures that the full bhp and watts range of the motor can be utilized with confidence. Using your fan motors up to the watts or bhp rating shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected.

6.Use of a field-supplied motor may affect wiring size. Contact your Bryant representative for details.