Table 16 — Fan Performance — 581A210 High Heat Horizontal Discharge Units*

AIRFLOW

 

 

 

 

 

EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

 

 

0.2

 

 

0.4

 

 

0.6

 

 

0.8

 

 

1.0

 

(Cfm)

 

 

 

 

 

 

 

 

 

 

 

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

3,500

645

1105

1.27

720

1329

1.53

788

1549

1.78

851

1767

2.03

910

1982

2.28

4,000

718

1454

1.67

785

1692

1.95

848

1926

2.22

906

2158

2.48

962

2388

2.75

4,500

792

1866

2.15

853

2117

2.43

911

2364

2.72

965

2609

3.00

1017

2583

2.97

5,000

867

2343

2.69

923

2605

3.00

977

2865

3.30

1027

2845

3.27

1076

3163

3.64

5,500

943

2889

3.32

995

3162

3.64

1044

3158

3.63

1092

3497

4.02

1138

3843

4.42

6,000

1019

3177

3.65

1067

3532

4.06

1113

3892

4.48

1158

4259

4.90

1201

4631

5.33

6,500

1096

3973

4.57

1141

4354

5.01

1184

4742

5.45

1226

5136

5.91

1267

5535

6.37

7,000

1173

4894

5.63

1215

5304

6.10

1256

5719

6.58

1295

6140

7.06

1334

6567

7.55

7,500

1250

5952

6.85

1290

6389

7.35

1328

6832

7.86

1366

7281

8.37

8,000

1328

7153

8.23

1365

7620

8.76

8,500

9,000

9,500

10,000

 

 

 

 

 

 

 

 

 

 

 

 

AIRFLOW

 

 

 

 

 

EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

 

 

1.2

 

 

1.4

 

 

1.6

 

 

1.8

 

 

2.0

 

(Cfm)

 

 

 

 

 

 

 

 

 

 

 

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

3,500

965

2195

2.53

1018

2181

2.51

1068

2442

2.81

1116

2708

3.11

1162

2979

3.43

4,000

1014

2364

2.72

1064

2644

3.04

1112

2930

3.37

1158

3221

3.70

1202

3517

4.05

4,500

1067

2882

3.31

1114

3187

3.67

1160

3498

4.02

1204

3814

4.39

1246

4135

4.76

5,000

1123

3489

4.01

1168

3820

4.39

1211

4156

4.78

1253

4497

5.17

1294

4844

5.57

5,500

1182

4194

4.82

1224

4551

5.23

1266

4913

5.65

1306

5280

6.07

1345

5652

6.50

6,000

1243

5008

5.76

1283

5391

6.20

1323

5779

6.65

1361

6172

7.10

1398

6569

7.56

6,500

1306

5939

6.83

1345

6349

7.30

1382

6763

7.78

7,000

1371

6997

8.05

7,500

8,000

8,500

9,000

9,500

10,000

 

 

LEGEND

Bhp

Brake Horsepower Input to Fan

Watts

Input Watts to Motor

*Motor drive ranges:

Low Range: 896-1227 (208/230 and 460-v), 863-1141 (575-v)

High Range: 1113-1414 (208/230 and 460-v), 1042-1285 (575-v) All other rpms require field-supplied drive.

Refer to page 23 for general Fan Performance Data notes.

NOTE: Maximum continuous bhp is:

Low Range: 4.25 (208/230 and 460-v), 3.45 (575-v)

High Range: 5.75

Table 17 — Fan Performance — 581A240 Low Heat Horizontal Discharge Units*

AIRFLOW

 

 

 

 

 

EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

 

 

0.2

 

 

0.4

 

 

0.6

 

 

0.8

 

 

1.0

 

(Cfm)

 

 

 

 

 

 

 

 

 

 

 

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

3,500

642

1082

1.24

714

1296

1.49

781

1510

1.74

843

1726

1.98

901

1943

2.23

4,000

714

1426

1.64

780

1651

1.90

841

1877

2.16

898

2103

2.42

952

2330

2.68

4,500

787

1831

2.11

847

2067

2.38

904

2303

2.65

957

2540

2.92

1008

2501

2.88

5,000

862

2301

2.65

917

2547

2.93

969

2793

3.21

1019

2755

3.17

1066

3062

3.52

5,500

937

2838

3.26

988

3094

3.56

1036

3067

3.53

1083

3390

3.90

1127

3719

4.28

6,000

1013

3113

3.58

1060

3445

3.96

1105

3783

4.35

1149

4130

4.75

1191

4484

5.16

6,500

1089

3893

4.48

1133

4250

4.89

1175

4615

5.31

1216

4986

5.73

1256

5364

6.17

7,000

1166

4798

5.52

1207

5181

5.96

1247

5570

6.41

1285

5965

6.86

1323

6369

7.32

7,500

1243

5837

6.71

1282

6244

7.18

1319

6658

7.66

1355

7080

8.14

1391

7507

8.63

8,000

1320

7017

8.07

1356

7450

8.57

1392

7890

9.08

8,500

1398

8350

9.60

9,000

9,500

10,000

 

 

 

 

 

 

 

 

 

 

 

 

AIRFLOW

 

 

 

 

 

EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

 

 

1.2

 

 

1.4

 

 

1.6

 

 

1.8

 

 

2.0

 

(Cfm)

 

 

 

 

 

 

 

 

 

 

 

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

3,500

955

2160

2.48

1007

2142

2.46

1056

2409

2.77

1104

2684

3.09

1149

2968

3.41

4,000

1004

2299

2.64

1053

2578

2.96

1100

2865

3.29

1145

3160

3.63

1189

3463

3.98

4,500

1056

2793

3.21

1103

3093

3.56

1147

3402

3.91

1191

3718

4.28

1233

4041

4.65

5,000

1112

3376

3.88

1156

3699

4.25

1199

4029

4.63

1240

4366

5.02

1280

4710

5.42

5,500

1171

4057

4.67

1212

4402

5.06

1253

4754

5.47

1292

5114

5.88

1331

5480

6.30

6,000

1232

4845

5.57

1271

5213

6.00

1310

5588

6.43

1348

5970

6.87

1384

6358

7.31

6,500

1295

5749

6.61

1333

6141

7.06

1369

6538

7.52

7,000

1360

6778

7.80

1396

7193

8.27

7,500

8,000

8,500

9,000

9,500

10,000

 

 

LEGEND

Bhp

Brake Horsepower Input to Fan

Watts

Input Watts to Motor

*Motor drive ranges:

Low Range: 1113-1414

High Range: 1096-1339

All other rpms require field-supplied drive.

Refer to page 23 for general Fan Performance Data notes.

NOTE: Maximum continuous bhp is:

Low Range: 5.75

High Range: 8.63