G.EconoMi$er IV Troubleshooting Completion

4.Remove the jumper across T and T1. The actuator should drive fully closed.

5.Return EconoMi$er IV settings and wiring to normal after completing troubleshooting.

G.EconoMi$er IV Troubleshooting Completion

This procedure is used to return the EconoMi$er IV to opera- tion. No troubleshooting or testing is done by performing the following procedure.

1.Disconnect power at TR and TR1.

2.Set enthalpy potentiometer to previous setting.

3.Set DCV maximum position potentiometer to previ- ous setting.

4.Set minimum position, DCV set point, and exhaust potentiometers to previous settings.

5.Remove 620-ohm resistor from terminals SR and +.

6.Remove 1.2 kilo-ohm checkout resistor from termi- nals SO and +. If used, reconnect sensor from termi- nals SO and +.

7.Remove jumper from TR to N.

8.Remove jumper from TR to 1.

9.Remove 5.6 kilo-ohm resistor from T and T1. Recon- nect wires at T and T1.

10.Remove jumper from P to P1. Reconnect device at P and P1.

11.Apply power (24 vac) to terminals TR and TR1.

Table 37 — EconoMi$er IV Input/Output Logic

 

INPUTS

 

 

 

 

 

OUTPUTS

 

Demand Control

Enthalpy*

 

 

 

Compressor

N Terminal†

 

 

Y1

Y2

Stage

Stage

Occupied

Unoccupied

Ventilation (DCV)

Outdoor

Return

 

 

1

2

Damper

 

 

 

 

 

Below set

High

Low

On

On

On

On

Minimum position

Closed

(DCV LED Off)

(Free Cooling LED Off)

 

On

Off

On

Off

 

 

 

 

 

 

 

 

 

 

Off

Off

Off

Off

 

 

 

Low

High

On

On

On

Off

Modulating** (between min.

Modulating** (between

 

(Free Cooling LED On)

 

On

Off

Off

Off

position and full-open)

closed and full-open)

 

 

 

 

 

 

 

 

Off

Off

Off

Off

Minimum position

Closed

Above set

High

Low

On

On

On

On

Modulating†† (between min.

Modulating†† (between

(DCV LED On)

(Free Cooling LED Off)

 

On

Off

On

Off

position and DCV maximum)

closed and DCV

 

 

 

 

maximum)

 

 

 

Off

Off

Off

Off

 

 

 

 

 

 

 

Low

High

On

On

On

Off

Modulating***

Modulating†††

 

(Free Cooling LED On)

 

On

Off

Off

Off

 

 

 

 

 

 

 

 

 

 

Off

Off

Off

Off

 

 

*For single enthalpy control, the module compares outdoor enthalpy to the ABCD set point.

†Power at N terminal determines Occupied/Unoccupied setting: 24 vac (Occupied), no power (Unoccupied).

**Modulation is based on the supply-air sensor signal. ††Modulation is based on the DCV signal.

***Modulation is based on the greater of DCV and supply-air sensor signals, between minimum position and either maximum position (DCV) or fully open (supply-air signal).

†††Modulation is based on the greater of DCV and supply-air sensor signals, between closed and either maximum position (DCV) or fully open (supply-air signal).

Fig. 44 — EconoMi$er IV Functional View