Table 35 — Heating Service Analysis

PROBLEM

CAUSE

REMEDY

Burners Will Not Ignite.

Misaligned spark electrodes.

Check flame ignition and sensor electrode positioning.

 

 

 

Adjust as needed.

 

 

No gas at main burners.

Check gas line for air; purge as necessary. After purging gas line of

 

 

 

air, allow gas to dissipate for at least 5 minutes before attempting to

 

 

 

relight unit.

 

 

 

Check gas valve.

 

 

Water in gas line.

Drain water and install drip leg to trap water.

 

 

No power to furnace.

Check power supply, fuses, wiring, and circuit breaker.

 

 

No 24 v power supply to control circuit.

Check transformer. Transformers with internal overcurrent protection

 

 

 

require a cool-down period before resetting. Check 24-v

 

 

 

circuit breaker; reset if necessary.

 

 

Miswired or loose connections.

Check all wiring and wire nut connections.

 

 

Burned-out heat anticipator in thermostat.

Replace thermostat.

 

 

Broken thermostat wires.

Run continuity check. Replace wires if necessary.

Inadequate Heating.

Dirty air filter.

Clean or replace filter as necessary.

 

 

Gas input to unit too low.

Check gas pressure at manifold. Clock gas meter for input. If too low,

 

 

 

increase manifold pressure or replace with correct orifices.

 

 

Unit undersized for application.

Replace with proper unit or add additional unit.

 

 

Restricted airflow.

Clean filter, replace filter, or remove any restrictions.

 

 

Blower speed too low.

Install alternate motor, if applicable, or adjust pulley to increase fan

 

 

 

speed.

 

 

Limit switch cycles main burners.

Check rotation of blower, thermostat heat anticipator settings, and

 

 

 

temperature rise of unit. Adjust as needed.

 

 

Too much outdoor air.

Adjust minimum position.

 

 

 

Check economizer operation.

Poor Flame Characteristics.

Incomplete combustion (lack of combustion air)

Check all screws around flue outlets and burner compartment.

 

 

results in:

Tighten as necessary.

 

 

Aldehyde odors, CO, sooting flame, or floating flame.

Cracked heat exchanger.

 

 

 

Overfired unit — reduce input, change orifices, or adjust gas line or

 

 

 

manifold pressure.

 

 

 

Check vent for restriction. Clean as necessary.

 

 

 

Check orifice to burner alignment.

Burners Will Not Turn Off.

Unit is locked into Heating mode for a one minute min-

Wait until mandatory one minute time period has elapsed or power to

 

 

imum.

unit.

Table 36 — IGC Board LED Alarm Codes

LED FLASH

DESCRIPTION

ACTION TAKEN BY

RESET METHOD

PROBABLE CAUSE

 

CODE

CONTROL

 

 

 

 

 

On

Normal Operation

 

Off

Hardware Failure

No gas heating.

Loss of power to the IGC. Check 5 amp fuse on IGC, power

 

 

 

 

 

to unit, 24V circuit breaker, transformer, and wiring to the

 

 

 

 

 

IGC.

 

1 Flash

Indoor Fan On/Off Delay

5 seconds subtracted from On

Power reset.

High temperature limit switch opens during heat exchanger

 

 

Modified

delay.

 

warm-up period before fan-on delay expires.

 

 

 

5 seconds added to Off delay

 

High temperature limit switch opens within

 

 

 

(3 min max).

 

10 minutes of heat call (W) Off.

 

 

 

 

 

See Limit Switch Fault.

2

Flashes

Limit Switch Fault

Gas valve and igniter Off.

Limit switch closed, or heat

High temperature limit switch is open. Check the operation

 

 

 

Indoor fan and inducer On.

call (W) Off.

of the indoor (evaporator) fan motor. Ensure that the sup-

 

 

 

 

 

ply-air temperature rise is within the range on the unit

 

 

 

 

 

nameplate. Check wiring and limit switch

 

 

 

 

 

operation.

3

Flashes

Flame Sense Fault

Indoor fan and inducer On.

Flame sense normal.

The IGC sensed a flame when the gas valve should be

 

 

 

 

Power reset for LED reset.

closed. Check wiring, flame sensor, and gas valve opera-

 

 

 

 

 

tion.

4

Flashes

Four Consecutive Limit

No gas heating.

Heat call (W) Off.

4 consecutive limit switch faults within a single call for heat.

 

 

Switch Fault

 

Power reset for LED reset.

See Limit Switch Fault.

5

Flashes

Ignition Fault

No gas heating.

Heat call (W) Off.

Unit unsuccessfully attempted ignition for 15 minutes. Check

 

 

 

 

Power reset for LED reset.

igniter and flame sensor electrode spacing, gaps, etc. Check

 

 

 

 

 

flame sense and igniter wiring. Check gas valve operation

 

 

 

 

 

and gas supply.

6

Flashes

Induced Draft Motor Fault

If heat off: no gas heating.

Inducer sense normal, or

Inducer sense On when heat call Off, or inducer sense Off

 

 

 

If heat on: gas valve Off and

heat call (W) Off.

when heat call On. Check wiring, voltage, and operation of

 

 

 

inducer On.

 

IGC motor. Check speed sensor wiring to IGC.

7

Flashes

Rollout Switch Lockout

Gas valve and igniter Off.

Power reset.

Rollout switch has opened. Check gas valve operation.

 

 

 

Indoor fan and inducer On.

 

Check induced-draft blower wheel is properly secured to

 

 

 

 

 

motor shaft.

8

Flashes

Internal Control Lockout

No gas heating.

Power reset.

IGC has sensed internal hardware or software error. If fault

 

 

 

 

 

is not cleared by resetting 24 v power, replace the IGC.

9

Flashes

Temporary Software Lockout

No gas heating.

1 hour auto reset, or power

Electrical interference is disrupting the IGC software.

 

 

 

 

reset.

 

LEGEND

IGC — Integrated Gas Unit Control LED — Light-Emitting Diode

NOTES:

1.There is a 3-second pause between alarm code displays.

2.If more than one alarm code exists, all applicable alarm codes will be displayed in numerical sequence.

3.Alarm codes on the IGC will be lost if power to the unit is interrupted.

48

Page 48
Image 48
Bryant 581A operation manual Heating Service Analysis, Problem Cause Remedy

581A specifications

The Bryant 581A is a pivotal model in the realm of heating, ventilation, and air conditioning (HVAC) systems, known for its robust performance and energy efficiency. As part of the Bryant product lineup, the 581A offers a blend of innovative technologies combined with reliable engineering, making it a suitable choice for both residential and light commercial applications.

One of the standout features of the Bryant 581A is its outstanding energy efficiency. With a Seasonal Energy Efficiency Ratio (SEER) rating of up to 16, this model meets Energy Star qualifications, ensuring that homeowners can enjoy lower utility bills while helping to reduce their environmental footprint. The efficiency is further enhanced by the unit’s environmentally friendly refrigerant, which not only improves performance but also aligns with modern sustainability standards.

Another key characteristic of the Bryant 581A is its durable construction. Designed to withstand various weather conditions, the unit features a robust cabinet that protects internal components. This durability not only prolongs the lifespan of the system but also minimizes the need for frequent maintenance or repairs. The coil design is optimized for heat transfer efficiency, enhancing the unit's overall performance in both cooling and heating modes.

In terms of technology, the Bryant 581A incorporates advanced control systems that enable precise temperature regulation. The multi-stage cooling capabilities ensure that the system can adapt to varying temperature demands, providing comfort in all seasons. Additionally, the model is compatible with smart thermostats, allowing homeowners to control their HVAC system remotely via smartphone or other connected devices.

Noise reduction is another aspect where the Bryant 581A excels. Equipped with a variable-speed compressor and sound-dampening features, this model operates quietly, minimizing disruption in residential or office environments. This focus on acoustic comfort makes it an ideal choice for those who value a peaceful living or working space.

Overall, the Bryant 581A represents an excellent balance of efficiency, durability, and modern technology. With features aimed at enhancing user comfort and reducing operational costs, it stands out as a reliable solution in the competitive HVAC market. Whether for new installations or replacements, the Bryant 581A is a testament to the brand’s commitment to quality and innovation in home climate control.