B. Heating, Units Without Economizer
NOTE: The
When the thermostat calls for heating, power is sent to W on the IGC (integrated gas unit controller) board. An LED
If the burners do not light, there is a
When ignition occurs the IGC board will continue to monitor the condition of the rollout and limit switches, the hall effect sensor, as well as the flame sensor. If the unit is controlled through a room thermostat set for fan auto., 45 seconds after ignition occurs, the
When additional heat is required, W2 closes and initiates power to the second stage of the main gas valve. When the thermostat is satisfied, W1 and W2 open and the gas valve closes, interrupting the flow of gas to the main burners. If the call for W1 lasted less than 1 minute, the heating cycle will not terminate until 1 minute after W1 became active. If the unit is controlled through a room thermostat set for fan auto., the
A LED indicator is provided on the IGC to monitor opera- tion. The IGC is located by removing the side panel and viewing the IGC through the view port located in the control box access panel. During normal operation, the LED is con- tinuously on. For information on troubleshooting refer to page 47.
C. Cooling, Units With EconoMi$er IV
When free cooling is not available, the compressors will be controlled by the zone thermostat. When free cooling is avail- able, the
Integrated EconoMi$er IV operation on
For EconoMi$er IV operation, there must be a thermostat call for the fan (G). This will move the damper to its mini- mum position during the occupied mode.
Above 50 F
If optional power exhaust is installed, as the
If
Damper movement from full closed to full open (or vice versa) will take between 11/2 and 21/2 minutes.
If free cooling can be used as determined from the appropri- ate changeover command (switch, dry bulb, enthalpy curve, differential dry bulb, or differential enthalpy), a call for cool- ing (Y1 closes at the thermostat) will cause the control to modulate the dampers open to maintain the supply air tem- perature set point at 50 to 55 F.
As the supply air temperature drops below the set point range of 50 to 55 F, the control will modulate the
D. Heating, Units With EconoMi$er IV
When the room temperature calls for heat, the heating con- trols are energized as described in the Heating, Units With- out Economizer section. The IFM is energized and the EconoMi$er IV damper modulates to the minimum position. When the thermostat is satisfied and W1 and W2 are deener- gized, the IFM continues to run, and the economizer damper modulates to the minimum position.
SERVICE
WARNING: Before performing service or mainte- nance operations on unit, turn off main power switch to unit. Electrical shock could cause personal injury.
I. CLEANING
Inspect unit interior at beginning of each heating and cool- ing season and as operating conditions require. Remove unit top panel and/or side panels for access to unit interior.
A. Coil Maintenance and Cleaning Recommendation
Routine cleaning of coil surfaces is essential to maintain proper operation of the unit. Elimination of contamination and removal of harmful residues will greatly increase the life of the coil and extend the life of the unit. The following main- tenance and cleaning procedures are recommended as part of the routine maintenance activities to extend the life of the coil.