Table 14 — Fan Performance — 581A210 Low Heat Horizontal Discharge Units*

AIRFLOW

 

 

 

 

 

EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

 

 

0.2

 

 

0.4

 

 

0.6

 

 

0.8

 

 

1.0

 

(Cfm)

 

 

 

 

 

 

 

 

 

 

 

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

3,500

635

1064

1.22

709

1278

1.47

776

1492

1.72

838

1708

1.96

896

1924

2.21

4,000

707

1402

1.61

773

1627

1.87

835

1853

2.13

892

2080

2.39

947

2307

2.65

4,500

780

1802

2.07

840

2037

2.34

897

2273

2.61

950

2510

2.89

1001

2465

2.84

5,000

853

2264

2.60

909

2510

2.89

961

2756

3.17

1011

2710

3.12

1059

3015

3.47

5,500

928

2794

3.21

979

3049

3.51

1028

3012

3.46

1075

3333

3.83

1120

3661

4.21

6,000

1003

3047

3.50

1051

3376

3.88

1096

3714

4.27

1140

4059

4.67

1182

4411

5.07

6,500

1079

3812

4.38

1123

4166

4.79

1166

4529

5.21

1207

4898

5.63

1247

5274

6.07

7,000

1155

4697

5.40

1196

5078

5.84

1236

5465

6.29

1275

5859

6.74

1313

6260

7.20

7,500

1231

5714

6.57

1270

6120

7.04

1308

6533

7.51

1345

6952

8.00

1381

7378

8.49

8,000

1308

6871

7.90

1344

7303

8.40

1380

7741

8.90

8,500

1385

8177

9.40

9,000

9,500

10,000

 

 

 

 

 

 

 

 

 

 

 

 

AIRFLOW

 

 

 

 

 

EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

 

 

1.2

 

 

1.4

 

 

1.6

 

 

1.8

 

 

2.0

 

(Cfm)

 

 

 

 

 

 

 

 

 

 

 

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

3,500

951

2143

2.46

1003

2120

2.44

1052

2387

2.75

1100

2662

3.06

1146

2944

3.39

4,000

998

2535

2.92

1048

2548

2.93

1095

2835

3.26

1141

3129

3.60

1184

3432

3.95

4,500

1050

2756

3.17

1097

3055

3.51

1142

3363

3.87

1185

3678

4.23

1227

4001

4.60

5,000

1105

3329

3.83

1150

3651

4.20

1192

3979

4.58

1234

4315

4.96

1274

4658

5.36

5,500

1163

3997

4.60

1205

4342

4.99

1246

4692

5.40

1286

5051

5.81

1324

5415

6.23

6,000

1224

4771

5.49

1263

5138

5.91

1302

5511

6.34

1340

5892

6.78

1377

6278

7.22

6,500

1286

5658

6.51

1324

6048

6.96

1361

6445

7.41

1397

6847

7.87

7,000

1350

6668

7.67

1386

7081

8.14

7,500

8,000

8,500

9,000

9,500

10,000

 

 

LEGEND

Bhp

Brake Horsepower Input to Fan

Watts

Input Watts to Motor

*Motor drive ranges:

Low Range: 896-1227 (208/230 and 460-v), 863-1141 (575-v)

High Range: 1113-1414 (208/230 and 460-v), 1042-1285 (575-v) All other rpms require field-supplied drive.

Refer to page 23 for general Fan Performance Data notes.

NOTE: Maximum continuous bhp is:

Low Range: 4.25 (208/230 and 460-v), 3.45 (575-v)

High Range: 5.75

Table 15 — Fan Performance — 581A210 Medium Heat Horizontal Discharge Units*

AIRFLOW

 

 

 

 

 

EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

 

 

0.2

 

 

0.4

 

 

0.6

 

 

0.8

 

 

1.0

 

(Cfm)

 

 

 

 

 

 

 

 

 

 

 

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

3,500

645

1105

1.27

720

1329

1.53

788

1549

1.78

851

1767

2.03

910

1982

2.28

4,000

718

1454

1.67

785

1692

1.95

848

1926

2.22

906

2158

2.48

962

2388

2.75

4,500

792

1866

2.15

853

2117

2.43

911

2364

2.72

965

2609

3.00

1017

2583

2.97

5,000

867

2343

2.69

923

2605

3.00

977

2865

3.30

1027

2845

3.27

1076

3163

3.64

5,500

943

2889

3.32

995

3162

3.64

1044

3158

3.63

1092

3497

4.02

1138

3843

4.42

6,000

1019

3177

3.65

1067

3532

4.06

1113

3892

4.48

1158

4259

4.90

1201

4631

5.33

6,500

1096

3973

4.57

1141

4354

5.01

1184

4742

5.45

1226

5136

5.91

1267

5535

6.37

7,000

1173

4894

5.63

1215

5304

6.10

1256

5719

6.58

1295

6140

7.06

1334

6567

7.55

7,500

1250

5952

6.85

1290

6389

7.35

1328

6832

7.86

1366

7281

8.37

8,000

1328

7153

8.23

1365

7620

8.76

8,500

9,000

9,500

10,000

 

 

 

 

 

 

 

 

 

 

 

 

AIRFLOW

 

 

 

 

 

EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

 

 

1.2

 

 

1.4

 

 

1.6

 

 

1.8

 

 

2.0

 

(Cfm)

 

 

 

 

 

 

 

 

 

 

 

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

3,500

965

2195

2.53

1018

2181

2.51

1068

2442

2.81

1116

2708

3.11

1162

2979

3.43

4,000

1014

2364

2.72

1064

2644

3.04

1112

2930

3.37

1158

3221

3.70

1202

3517

4.05

4,500

1067

2882

3.31

1114

3187

3.67

1160

3498

4.02

1204

3814

4.39

1246

4135

4.76

5,000

1123

3489

4.01

1168

3820

4.39

1211

4156

4.78

1253

4497

5.17

1294

4844

5.57

5,500

1182

4194

4.82

1224

4551

5.23

1266

4913

5.65

1306

5280

6.07

1345

5652

6.50

6,000

1243

5008

5.76

1283

5391

6.20

1323

5779

6.65

1361

6172

7.10

1398

6569

7.56

6,500

1306

5939

6.83

1345

6349

7.30

1382

6763

7.78

7,000

1371

6997

8.05

7,500

8,000

8,500

9,000

9,500

10,000

 

 

LEGEND

Bhp

Brake Horsepower Input to Fan

Watts

Input Watts to Motor

*Motor drive ranges:

Low Range: 896-1227 (208/230 and 460-v), 863-1141 (575-v)

High Range: 1113-1414 (208/230 and 460-v), 1042-1285 (575-v) All other rpms require field-supplied drive.

Refer to page 23 for general Fan Performance Data notes.

NOTE: Maximum continuous bhp is:

Low Range: 4.25 (208/230 and 460-v), 3.45 (575-v)

High Range: 5.75

24