Heat Anticipator Setting
The room thermostat heat anticipator must be properly ad- justed to ensure proper heating performance. Set the heat anticipator, using an ammeter to determine the exact re- quired setting.
NOTE: For thermostat selection purposes, use .14 amp for the approximate required setting. Set heat anticipator stage 1 and 2 at .14 amp.
Failure to make a proper heat anticipator adjustment may result in improper operation, discomfort to the occupants of the conditioned space, and inefficient energy utilization; how- ever, the required setting may be changed slightly to provide a greater degree of comfort for a particular installation.
Fig. 16 Ð Typical Access Panel Locations
F. Accessory Installation
At this time any required accessories should be installed on the unit. Control wiring information is provided in the unit wiring book. Refer to accessory Installation Instructions pro- vided with accessory.
G. Optional Varislide™ Economizer
The optional economizer hood assembly is packaged and shipped in the ®lter section. Damper blades and control boards are installed at the factory and the economizer is shipped in the vertical discharge position.
NOTE: Horizontal discharge
Assembly
1.Determine if ventilation air is required in building. If so, determine the minimum amount to be supplied by each unit and record quantity of ventilation air needed for use in Step 7.
2.Remove ®lter access panel by raising panel and swing- ing panel outward. Panel is now disengaged from track and can be removed. No tools are required to remove ®lter access panel. Remove
3.Assemble
4.Slide economizer into unit and secure with screws. See Fig. 18.
NOTE: Be sure to engage rear economizer ¯ange under tabs in vertical
5.To convert to horizontal discharge application:
a.Rotate the economizer 90 degrees until the econo- mizer motor faces the condenser section (see Fig. 19.).
b.Rotate the barometric relief damper cover 90 degrees.
c.Install horizontal discharge
6.Insert economizer plug into economizer harness. Re- move tape from barometric relief damper. See Fig. 21.
7.If ventilation air is not required, proceed to Step 9. If ventilation air is required, determine the minimum po- sition setting for required air¯ow. See Fig. 22. Adjust minimum position setting by adjusting the screws on the position setting bracket. Slide bracket until the top screw is in the position determined by Fig. 22. Tighten screws.
Ð13Ð
Fig. 17 Ð Outdoor-Air Hood Details
ECONOMIZER | ECONOMIZER | ECONOMIZER | TOP |
CONTROL BOARD | PLUG | MOTOR | SCREW |
BAROMETRIC
RELIEF DAMPER
ECONOMIZER | POSITION SETTING |
MOUNTING SCREWS | BRACKET |