Bryant 581B B. Low Charge Cooling, C. To Use Cooling Charging Charts, EXAMPLE: Fig

Models: 581B

1 40
Download 40 pages 47.12 Kb
Page 30
Image 30
B. Low Charge Cooling

B. Low Charge Cooling

Using Cooling Charging Charts, Fig. 39-42, vary refrigerant until the conditions of the appropriate chart are met. Note the charging charts are different from type normally used. Charts are based on charging the units to the correct super- heat for the various operating conditions. Accurate pressure gage and temperature-sensing device are required. Connect the pressure gage to the service port on the suction line. Mount the temperature-sensing device on the suction line and insu- late it so that outdoor ambient temperature does not affect the reading. Indoor-air cfm must be within the normal oper- ating range of the unit.

C. To Use Cooling Charging Charts

Take the outdoor ambient temperature and read the suction pressure gage. Refer to appropriate chart to determine what suction temperature should be. If suction temperature is high, add refrigerant. If suction temperature is low, carefully re- claim some of the charge. Recheck the suction pressure as charge is adjusted.

EXAMPLE: (Fig. 41)

Outdoor Temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . 85 F Suction Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74 psig Suction Temperature should be . . . . . . . . . . . . . . . . . . . 48 F (Suction Temperature may vary ± 5 F.)

D. Refrigerant Leaks

Proceed as follows to repair a refrigerant leak and to charge the unit:

1.Locate leak and ensure that refrigerant system pres- sure has been relieved.

2.Repair leak following accepted practices.

NOTE: Replace ®lter drier in the liquid line whenever the system has been opened for repair.

3.Add a small charge of R-22 refrigerant vapor to system and leak-test unit.

4.Evacuate refrigerant system if additional leaks are not found.

5.Charge unit with R-22 refrigerant, using a volumetric- charging cylinder or accurate scale. Refer to unit rating plate for required charge. Be sure to add extra refriger- ant to compensate for internal volume of ®lter drier.

VI. MAIN BURNERS

At the beginning of each heating season, inspect for deterio- ration or blockage due to corrosion or other causes. Observe the main burner ¯ames and adjust if necessary.

VII. FLUE GAS PASSAGEWAYS

To inspect the ¯ue collector box and upper areas of the heat exchanger:

1.Remove the combustion blower wheel and motor assem- bly according to directions in Combustion-Air Blower sec- tion below.

2.Remove the 3 screws holding the blower housing to the ¯ue cover.

3.Remove the ¯ue cover to inspect the heat exchanger.

4.Clean all surfaces as required using a wire brush.

VIII. COMBUSTION-AIR BLOWER

Clean periodically to ensure proper air¯ow and heating effi- ciency. Inspect blower wheel every fall and periodically dur- ing heating season. For the ®rst heating season, inspect blower wheel bimonthly to determine proper cleaning frequency.

Fig. 39 Ð Cooling Charging Chart, 581B036

Fig. 40 Ð Cooling Charging Chart, 581B048

To inspect blower wheel, remove draft hood and screen. Shine a ¯ashlight into opening to inspect wheel. If cleaning is re- quired, remove motor and wheel as follows:

1.Slide burner access panel out.

2.Remove the 2 screws which hold the heat shield in place, and remove heat shield.

3.Remove the 7 screws that attach induced-draft motor mounting plate to blower housing (Fig. 43).

Ð30Ð

Page 30
Image 30