Bryant 581B installation instructions Ð27Ð

Models: 581B

1 40
Download 40 pages 47.12 Kb
Page 27
Image 27
Ð27Ð

Table 15 Ð 581B060 Air Delivery Ð Horizontal Discharge Units

 

 

 

 

 

 

 

 

 

BELT DRIVE MOTOR

 

 

 

 

 

 

 

AIRFLOW

 

 

 

 

 

 

External Static Pressure (in. wg)

 

 

 

 

 

 

(Cfm)

 

0.1

 

0.2

 

0.4

0.6

 

0.8

 

 

1.0

 

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

1500

741

 

0.38

798

 

0.43

895

 

0.54

990

 

0.67

1073

 

0.80

1154

 

0.95

1600

783

 

0.45

838

 

0.51

933

 

0.63

1016

 

0.75

1102

 

0.90

1182

 

1.04

1700

825

 

0.53

878

 

0.60

969

 

0.72

1049

 

0.84

1134

 

1.00

1206

 

1.14

1800

885

 

0.63

942

 

0.73

1047

 

0.90

1139

 

1.05

1193

 

1.14

1276

 

1.30

1900

928

 

0.73

982

 

0.83

1084

 

1.02

1160

 

1.11

1223

 

1.24

1301

 

1.38

2000

971

 

0.84

1022

 

0.94

1121

 

1.12

1188

 

1.22

1254

 

1.36

1329

 

1.44

2100

1015

 

0.97

1063

 

1.10

1140

 

1.18

1196

 

1.27

1272

 

1.45

1354

 

1.58

2200

1060

 

1.10

1104

 

1.20

1159

 

1.23

1229

 

1.41

1306

 

1.53

1363

 

1.70

2300

1104

 

1.25

1130

 

1.27

1196

 

1.37

1264

 

1.56

1340

 

1.66

1397

 

1.86

2400

1138

 

1.30

1174

 

1.37

1245

 

1.57

1305

 

1.63

1373

 

1.84

1440

 

1.95

2500

1183

 

1.43

1201

 

1.50

1284

 

1.65

1338

 

1.75

1402

 

1.99

1469

 

2.04

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BELT DRIVE MOTOR

 

 

 

AIRFLOW

 

 

External Static Pressure (in. wg)

 

 

(Cfm)

1.2

 

 

1.4

 

1.6

 

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

1500

1218

 

1.12

1295

 

1.36

1360

 

1.40

1600

1251

 

1.20

1310

 

1.40

1385

 

1.49

1700

1281

 

1.31

1342

 

1.48

1398

 

1.53

1800

1341

 

1.40

1413

 

1.55

1474

 

1.58

1900

1374

 

1.53

1437

 

1.62

1490

 

1.67

2000

1396

 

1.66

1460

 

1.68

1509

 

1.77

2100

1413

 

1.75

1475

 

1.73

1529

 

1.92

2200

1434

 

1.81

1487

 

1.85

1554

 

2.07

2300

1459

 

1.88

1520

 

2.07

1576

 

2.24

2400

1502

 

2.06

1552

 

2.24

1604

 

2.42

2500

1524

 

2.24

1585

 

2.42

1638

 

2.60

 

 

 

 

 

 

 

 

 

 

LEGEND

Bhp Ð Brake Horsepower Input to Fan

NOTES:

1.Boldface indicates ®eld-supplied drive is required. (See Note 4.)

2.Manual backgroundManual background indicates ®eld-supplied motor and drive required.

3.indicates maximum usable bhp.

4.Motor drive range is 1020 to 1460 rpm. All other rpms require a ®eld- supplied drive.

5.Values include losses for ®lters, units casing, and wet coils.

6.Maximum continuous bhp is 1.8. Extensive motor and electrical test- ing on these units ensures that the full range of the motor can be utilized with con®dence. Using your fan motors up to the ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected.

7.Use of a ®eld-supplied motor may affect wire sizing. Contact your lo- cal representative to verify.

8.Interpolation is permissible. Do not extrapolate.

9.Minimum allowable cfm is 300 cfm/ton.

Table 16 Ð 581B072 Air Delivery Ð Horizontal Discharge Units

 

 

 

 

 

 

 

 

 

BELT DRIVE MOTOR

 

 

 

 

 

 

AIRFLOW

 

 

 

 

 

 

External Static Pressure (in. wg)

 

 

 

 

 

 

(Cfm)

 

0.1

 

0.2

 

0.4

 

0.6

 

0.8

 

1.0

 

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

1800

885

 

0.63

942

 

0.73

1047

 

0.90

1139

 

1.05

1193

 

1.14

1276

 

1.30

1900

928

 

0.73

982

 

0.83

1084

 

1.02

1160

 

1.11

1223

 

1.24

1301

 

1.38

2000

971

 

0.84

1022

 

0.94

1121

 

1.12

1188

 

1.22

1254

 

1.36

1329

 

1.44

2100

1015

 

0.97

1063

 

1.10

1140

 

1.18

1196

 

1.27

1272

 

1.45

1354

 

1.58

2200

1060

 

1.10

1104

 

1.20

1159

 

1.23

1229

 

1.41

1306

 

1.53

1363

 

1.70

2300

1104

 

1.25

1130

 

1.27

1196

 

1.37

1264

 

1.56

1340

 

1.66

1397

 

1.86

2400

1138

 

1.30

1174

 

1.37

1245

 

1.57

1305

 

1.63

1373

 

1.84

1440

 

1.95

2500

1183

 

1.43

1201

 

1.50

1284

 

1.65

1338

 

1.75

1402

 

1.99

1469

 

2.04

2600

1210

 

1.58

1246

 

1.67

1312

 

1.76

1366

 

1.96

1435

 

2.10

1494

 

2.19

2700

1254

 

1.76

1285

 

1.80

1354

 

1.95

1403

 

2.14

1474

 

2.21

1536

 

2.46

2800

1274

 

1.82

1304

 

1.85

1374

 

2.12

1459

 

2.25

1514

 

2.42

1570

 

2.66

2900

1318

 

1.95

1345

 

2.05

1412

 

2.32

1496

 

2.54

1529

 

2.61

1603

 

2.87

3000

1362

 

2.20

1378

 

2.30

1451

 

2.40

1534

 

2.66

1560

 

2.81

1611

 

3.01

 

 

 

 

BELT DRIVE MOTOR

 

 

 

AIRFLOW

 

 

External Static Pressure (in. wg)

 

 

(Cfm)

1.2

 

 

1.4

 

1.6

 

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

1800

1341

 

1.40

1413

 

1.55

1474

 

1.58

1900

1374

 

1.53

1437

 

1.62

1490

 

1.67

2000

1396

 

1.66

1460

 

1.68

1509

 

1.77

2100

1413

 

1.75

1475

 

1.73

1529

 

1.92

2200

1434

 

1.81

1487

 

1.85

1554

 

2.07

2300

1459

 

1.88

1520

 

2.07

1576

 

2.24

2400

1502

 

2.06

1552

 

2.24

1604

 

2.42

2500

1524

 

2.24

1585

 

2.42

1638

 

2.60

2600

1552

 

2.40

1616

 

2.63

1671

 

2.80

2700

1584

 

2.61

1646

 

2.83

1706

 

2.97

2800

1624

 

2.85

1677

 

2.99

Ð

 

Ð

2900

1671

 

3.03

Ð

 

Ð

Ð

 

Ð

3000

Ð

 

Ð

Ð

 

Ð

Ð

 

Ð

 

 

 

 

 

 

 

 

 

 

LEGEND

Bhp Ð Brake Horsepower Input to Fan

NOTES:

1.Boldface indicates ®eld-supplied drive is required. (See Note 4.)

2.Manual backgroundManual background indicates ®eld-supplied motor and drive required.

3.indicates maximum usable bhp.

4.Motor drive range is 1120 to 1585 rpm. All other rpms require a ®eld- supplied drive.

5.Values include losses for ®lters, units casing, and wet coils.

6.Maximum continuous bhp is 2.4. Extensive motor and electrical test- ing on these units ensures that the full range of the motor can be utilized with con®dence. Using your fan motors up to the ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected.

7.Use of a ®eld-supplied motor may affect wire sizing. Contact your lo- cal representative to verify.

8.Interpolation is permissible. Do not extrapolate.

9.Minimum allowable cfm is 300 cfm/ton.

Ð27Ð

Page 27
Image 27
Bryant 581B installation instructions Ð27Ð