Bryant 581B Ii.Heating Section Start-Upand Adjustments, A. Checking Heating Control Operation

Models: 581B

1 40
Download 40 pages 47.12 Kb
Page 18
Image 18
II.HEATING SECTION START-UP AND ADJUSTMENTS

II.HEATING SECTION START-UP AND ADJUSTMENTS

A. Checking Heating Control OperationCAUTION: Complete the required procedures given in the Pre-Start-Up section on this page before starting unit.

Do not jumper any safety devices when operating the unit.

Ensure that burner ori®ces are properly aligned. Unstable operation may occur when the burner ori®ces in the mani- fold are misaligned.

Follow the lighting instructions on the heating section opera- tion label (located inside the burner access door) to start the heating section.

When lighting the unit for the ®rst time, perform the follow- ing additional steps: If the gas supply pipe was not purged before connecting the unit, it will be full of air. It is recom- mended that the ground joint union be loosened and the supply line be allowed to purge until the odor of gas is de- tected. Never purge gas lines into a combustion chamber. Im- mediately upon detection of gas odor, retighten the union. Allow 5 minutes to elapse, then light unit in accordance with Check- ing Heating Control Operation section below.

A. Checking Heating Control Operation

Start and check the unit for proper heating control operation as follows: (Also see unit lighting instructions located inside the burner access panel.)

1.Turn on unit electrical supply and manual gas valve.

2.Set system switch selector at HEAT position and fan switch at AUTO. or ON position. Set heating temperature lever above room temperature.

3.The induced-draft motor will start immediately. The evapo- rator fan will have a 45-second delay before starting.

4.After a call for heating, the main burners should light within 5 seconds. If the burner does not light, then there is a 22-second delay before another 5-second try. If the burner still does not light, the time delay is repeated. If the burner does not light within 15 minutes, there is a lockout. To reset the control, break the 24-v power to W1.

5.The evaporator-fan motor will turn on 45 seconds after burner ignition.

6.The evaporator-fan motor will turn off 45 seconds after thermostat temperature is satis®ed.

7.Adjust air¯ow to obtain a temperature rise within the range speci®ed on the unit nameplate.

NOTE: The default value for the evaporator-fan motor ON/ OFF delay is 45 seconds. The Integrated Gas Unit Controller (IGC) modi®es this value when abnormal limit switch cycles occur. Based upon unit operating conditions, the ON delay can be reduced to 0 seconds and the OFF delay can be ex- tended to 180 seconds. When one ¯ash of the light-emitting diode (LED) is observed, the evaporator-fan ON/OFF delay has been modi®ed.

If the limit switch trips at the start of the heating cycle dur- ing the evaporator ON delay, the time period of the ON delay for the next cycle will be 5 seconds less than the time at which the switch tripped.

EXAMPLE: If the limit switch trips at 30 seconds, the evaporator-fan ON delay for the next cycle will occur at 25 seconds.

To prevent short-cycling, a 5-second reduction will only occur if a minimum of 10 minutes has elapsed since the last call for heating.

The evaporator-fan OFF delay can also be modi®ed. Once the call for heating has ended, there is a 10 minute period during which the modi®cation can occur. If the limit switch trips during this period, the evaporator-fan OFF delay will increase by 15 seconds. A maximum of 9 trips can occur, ex- tending the evaporator-fan OFF delay to 180 seconds.

To restore the original default value, reset the power to the unit.

To shut off unit set system switch selector at OFF position. Resetting heating selector lever below room temperature will temporarily shut unit off until space temperature falls below thermostat setting.

B. Safety Relief

A soft solder joint at the suction service Schrader port pro- vides pressure relief under abnormal temperature and pres- sure conditions.

C. Ventilation (Continuous Fan)

Set fan and system switch selectors at ON and OFF posi- tions, respectively. Evaporator fan operates continuously to provide constant air circulation. When the evaporator-fan selector switch is turned to the OFF position, there is a 30-second delay before the fan turns off.

D. Gas Input

Check gas input and manifold pressure after unit start-up. (See Table 5.) If adjustment is required proceed as follows.

B. Safety ReliefCAUTION: These units are designed to consume the rated gas inputs using the ®xed ori®ces at speci- ®ed manifold pressures as shown in Table 5. DO NOT REDRILL THE ORIFICES UNDER ANY CIRCUMSTANCES.

The rated gas inputs shown in Table 5 are for altitudes from sea level up to 2000 ft above sea level. These inputs are based on natural gas with a heating value of 1050 Btu/ft3 at

0.65speci®c gravity, or LP gas with a heating value of

2500 Btu/ft3 at 1.5 speci®c gravity. For elevations above 2000 ft, reduce input 4% for each 1000 ft above sea level. When the gas supply being used has a different heating value or speci®c gravity, refer to national and local codes, or contact your distributor or branch to determine the required ori®ce size. Refer to Table 6 for the correct ori®ce to use at high al- titudes. Kits are available from your distributor.

E. Adjusting Gas Input

The gas input to the unit is determined by measuring the gas ¯ow at the meter or by measuring the manifold pressure. Measuring the gas ¯ow at the meter is recommended for natu- ral gas units. The manifold pressure must be measured to determine the input of propane gas units.

Measuring Gas Flow at Meter Method Ð Natural Gas Units

Minor adjustment can be made by changing the manifold pres- sure. The manifold pressure must be maintained between 3.2 and 3.8 in. wg on high-®re, two-stage units. If larger adjust- ments are required, change main burner ori®ces following the recommendations of national and local codes.

NOTE: All other appliances that use the same meter must be turned off when gas ¯ow is measured at the meter.

Proceed as follows:

1.Turn off gas supply to unit.

2.Remove pipe plug on outlet of gas valve or manifold, then connect manometer at this point. Turn on gas to unit.

Ð18Ð

Page 18
Image 18
Bryant 581B Ii.Heating Section Start-Upand Adjustments, A. Checking Heating Control Operation, B. Safety Relief