Bryant 581B installation instructions Ð Base Unit Dimensions

Models: 581B

1 40
Download 40 pages 47.12 Kb
Page 2
Image 2
Fig. 2 Ð Base Unit Dimensions

 

STANDARD

VARISLIDE™

CORNER

CORNER

CORNER

CORNER

UNIT

UNIT

ECONOMIZER

WEIGHT

WEIGHT

WEIGHT

WEIGHT

581B

WEIGHT

WEIGHT

``A''

``B''

``C''

``D''

 

Lb

Kg

Lb

Kg

Lb

Kg

Lb

Kg

Lb

Kg

Lb

Kg

036

530

240

34

15.4

127

57.6

122

55.3

138

62.6

143

64.9

048

540

245

34

15.4

129

58.5

124

56.2

141

64.0

146

66.2

060

560

254

34

15.4

134

60.8

129

58.5

146

66.2

151

68.5

072

615

279

34

15.4

147

66.7

142

64.4

160

72.6

166

75.3

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTES:

1. Dimensions in [ ] are in millimeters.

2. Manual background Center of Gravity.

3.Manual background Direction of air¯ow.

4.On vertical discharge units, ductwork to be attached to accessory roof curb only. For horizontal discharge units ®eld-supplied flanges should be attached to horizontal discharge openings, and all duct- work should be attached to the ¯anges.

5.Minimum clearance (local codes or jurisdiction may prevail):

a.Between unit, ¯ue side and combustible surfaces, 48 inches.

b.Bottom of unit to combustible surfaces (when not using curb) 1 inch. Bottom of base rail to combustible surfaces (when not using curb) 0 inches.

c.Condenser coil, for proper air¯ow, 36 in. one side, 12 in. the other. The side getting the greater clearance is optional.

d.Overhead, 60 in. to assure proper condenser fan operation.

e.Between units, control box side, 42 in. per NEC (National Electrical Code).

f.Between unit and ungrounded surfaces, control box side, 36 in. per NEC.

g.Between unit and block or concrete walls and other grounded surfaces, control box side, 42 in. per NEC.

h.Horizontal supply and return end, 0 inches.

6.With the exception of the clearance for the condenser coil and combustion side as stated in Note 5a, b, and c, a removable fence or barricade requires no clearance.

7.Units may be installed on combustible ¯oors made from wood or Class A, B, or C roof covering material if set on base rail.

8.The vertical center of gravity is 1 -6 [457] up from the bottom of the base rail.

 

CONNECTION SIZES

A

13¤8

Dia. [35]

Field Power Supply Hole

B

2 Dia. [51] Power Supply Knock-Out

C

13¤4

Dia. [44]

Charging Port Hole

D

7¤8

 

Dia. [22] Field Control Wiring Hole

E

3¤4

-14

NPT Condensate Drain

F

1¤2

-14

NPT Gas Connection

G

21¤2

Dia. [64]

Power Supply Knock-Out

BOTTOM POWER CHART,

THESE HOLES REQUIRED FOR USE WITH ACCESSORY PACKAGES Ð CRBTMPWR001A00 (1¤2 , 3¤4 )

THREADED

WIRE

REQUIRED SIZES

CONDUIT

USE

(MAXIMUM)

SIZE

 

 

 

1¤2

24 V

7¤8

[22.2]

3¤4

Power

11¤8

[28.4]

Fig. 2 Ð Base Unit Dimensions

Ð2Ð

Page 2
Image 2
Bryant 581B installation instructions Ð Base Unit Dimensions