Bryant 581B Iv. Field Connections, A. External Trap Condensate Drain, B. Install Flue Hood

Models: 581B

1 40
Download 40 pages 47.12 Kb
Page 7
Image 7
IV. FIELD CONNECTIONS

IV. FIELD CONNECTIONS

A. External Trap Condensate Drain

The unit's 3¤4-in. condensate drain connections are located at the bottom and side of the unit. Unit discharge connec- tions do not determine the use of drain connections; either drain connection can be used with vertical or horizontal applications.

When using the standard side drain connection, make sure the plug in the alternate bottom connection is tight before installing the unit.

To use the bottom drain connection for a roof curb installa- tion, relocate the factory-installed plug from the bottom con- nection to the side connection. See Fig. 7. The piping for the condensate drain and external trap can be completed after the unit is in place.

All units must have an external trap for condensate drain- age. Install a trap at least 4-in. deep and protect against freeze- up. See Fig. 8. If drain line is installed downstream from the external trap, pitch the line away from the unit at 1 in. per 10 ft of run. Do not use a pipe size smaller than the unit connection.

B. Install Flue Hood

Flue hood is shipped screwed to the burner compartment ac- cess panel. Remove from shipping location and using screws provided, install ¯ue hood in location shown in Fig. 2 and 9.

NOTE: Drain plug is shown in factory-installed position.

Fig. 7 Ð Condensate Drain Pan

NOTE: Trap should be deep enough to offset maximum unit static dif- ference. A 4-in. trap is recommended.

Fig. 8 Ð External Trap Condensate Drain

Fig. 9 Ð Flue Hood Details

For units being installed in California Air Quality Manage- ment Districts which require NOx emissions of 40 nanograms/ joule or less, kit CRLOWNOX001A00 must be installed.

C. Gas Piping (Fig. 10)

Unit is equipped for use with type of gas shown on nameplate.

The gas supply pipe enters the unit through the access hole provided. The gas connection to the unit is made to the 1¤2-in. female NPT gas inlet on the manual shutoff or gas valve.

Install a separate gas supply line that runs directly from the meter to the heating section. Refer to Table 2 and the NFGC for gas pipe sizing. Do not use cast iron pipe. Check the local utility for recommendations concerning existing lines. Choose a supply pipe that is large enough to keep the pressure loss as low as practical. Never use pipe smaller than the 1¤2-in. fe- male NPT gas inlet on the unit gas valve.

For natural gas applications, the gas pressure at unit gas con- nection must not be less than 4 in. wg or greater than 13 in. wg while the unit is operating. On 581B048,060,072 high heat units, the gas pressure at unit gas connection must not be less than 5 in. wg or greater than 13 in. wg while the unit is operating. For propane applications, the gas pressure must not be less than 5 in. wg or greater than 13 in. wg at the unit connection.

LEGEND

NFGC Ð National Fuel Gas Code

*Field Supplied.

NOTE: Follow all local codes.

STEEL PIPE NOMINAL

SPACING OF SUPPORTS

DIAMETER (in.)

X DIMENSION (ft)

1¤2

6

3¤4 or 1

8

11¤4 or Larger

10

Fig. 10 Ð Gas Piping Guide

(With Accessory Utility Connections Package)

Ð7Ð

Page 7
Image 7
Bryant 581B Iv. Field Connections, A. External Trap Condensate Drain, B. Install Flue Hood, Ð Condensate Drain Pan