CARE AND MAINTENANMCE

To ensure continuing high performance and to minimize the possibility of premature equipment failure, periodic mainte- nance must be performed on this equipment. This combina- tion heating/cooling unit should be inspected at least once each year by a quali®ed service person.

NOTE TO EQUIPMENT OWNER: Consult your local dealer about the availability of a maintenance contract.

WARNING: The ability to properly perform mainte- nance on this equipment requires certain expertise, me- chanical skills, tools, and equipment. If you do not pos- sess these, do not attempt to perform any maintenance on this equipment other than those procedures recom- mended in the User's Manual. FAILURE TO HEED THIS WARNING COULD RESULT IN SERIOUS PER- SONAL INJURY AND POSSIBLE DAMAGE TO THIS EQUIPMENT.

The minimum maintenance requirements for this equipment are as follows:

1.Inspect air ®lter(s) each month. Clean or replace when necessary.

2.Inspect cooling coil, drain pan, and condensate drain each cooling season for cleanliness. Clean when necessary.

3.Inspect fan motor and wheel for cleanliness and check lubrication each heating and cooling season. Clean and lubricate (if required) when necessary.

4.Check electrical connections for tightness and controls for proper operation each heating and cooling season. Service when necessary.

5.Check and inspect heating section before each heating season. Clean and adjust when necessary.

6.Check and clean vent screen if needed.

WARNING: Failure to follow these warnings could re- sult in serious personal injury:

1.Turn off gas supply, then turn off electrical power to the unit before performing any maintenance or service on the unit.

2.Use extreme caution when removing panels and parts. As with any mechanical equipment, per- sonal injury can result from sharp edges, etc.

3.Never place anything combustible either on, or in contact with, the unit.

4.Should overheating occur, or the gas supply fail to shut off, shut off the external main manual gas valve to the unit, then shut off the electrical supply.

I.AIR FILTER

CAUTION: Never operate the unit without a suitble air ®lter in the return-air duct system. Always replace the ®lter with the same dimensional size and type as originally installed. See Table 1 for recommended ®lter sizes.

Inspect air ®lter(s) at least once each month and replace (throwaway-type) or clean (cleanable-type) at least twice dur- ing each heating and cooling season and whenever the ®l- ter(s) becomes clogged with dust and lint.

When necessary, replace ®lters with the same dimensional size and type as originally provided.

SERVICE

CAUTION: When servicing unit, shut off all electri- cal power to unit to avoid shock hazard or injury from rotating parts.

I. CLEANING

Inspect unit interior at the beginning of each heating and cool- ing season and as operating conditions require.

A.Evaporator Coil

1.Turn unit power off. Remove evaporator coil access panel.

2.If economizer is installed, remove economizer by dis- connecting economizer plug and removing mounting screws. See Fig. 18 and 19. Refer to Accessory Econo- mizer Installation Instructions or Optional Economizer sections on pages 13 and 14 for further details.

3.Slide ®lters out of unit.

4.Clean coil using a commercial coil cleaner or dish- washer detergent in a pressurized spray canister. Wash both sides of coil and ¯ush with clean water. For best results, back¯ush toward return-air section to remove foreign material.

5.Flush condensate pan.

6.Reinstall economizer and ®lters.

7.Reconnect wiring.

8.Replace access panels.

B.Condenser Coil

Inspect coil monthly. Clean condenser coil annually, and as required by location and outdoor-air conditions.

One-Row Coil (size 036)

Wash coil with commercial coil cleaner. It is not necessary to remove top panel.

2-Row Coils (sizes 048-072)

NOTE: Save all screws removed in this section. The screws must be used when reinstalling the equipment.

1.Turn off unit power.

2.Remove top panel screws on condenser end of unit.

3.Remove condenser coil corner post. See Fig. 35. To hold top panel open, place coil corner post between top panel and center post. See Fig. 36.

4.Remove screws securing coil to center post.

5.Remove fastener holding coil sections together at re- turn end of condenser coil. Carefully separate the outer coil section 3 to 4 in. from the inner coil section. See Fig. 37.

6.Use a water hose or other suitable equipment to ¯ush down between the 2 coil sections to remove dirt and de- bris. Clean the outer surfaces with a stiff brush in the normal manner.

7.Secure inner and outer coil rows together with a ®eld- supplied fastener.

8.Reposition the outer coil section and remove the coil cor- ner post from between the top panel and center post.

9.Reinstall the coil corner post and replace all screws.

C. Condensate Drain

Check and clean each year at start of cooling season. In win- ter, keep drain dry or protect against freeze-up.

Ð28Ð

Page 28
Image 28
Bryant 581B installation instructions Care and Maintenanmce, AIR Filter, Service Cleaning

581B specifications

The Bryant 581B is an innovative and highly efficient gas furnace that stands out in the HVAC market for its remarkable performance, reliability, and advanced features. Designed to provide optimal heating comfort, the Bryant 581B is perfect for homeowners seeking both quality and energy efficiency.

One of the main features of the Bryant 581B is its impressive Annual Fuel Utilization Efficiency (AFUE) rating. With an AFUE rating of up to 80%, this gas furnace maximizes energy usage, ensuring that a significant portion of the fuel is converted into heat for your home. This efficiency not only translates into lower energy bills but also reduces the carbon footprint, making it an environmentally friendly choice.

The furnace is equipped with a multi-speed blower motor that enhances comfort by providing consistent airflow throughout the home. This technology adjusts to different heating demands, ensuring that every room reaches the desired temperature without the discomfort of hot or cold spots. The quiet operation of the blower motor also adds to the overall comfort, creating a peaceful home environment.

Another notable characteristic of the Bryant 581B is its durable construction. It features a robust heat exchanger built from high-quality materials, designed to withstand the rigors of daily use. The compact design of the furnace allows it to fit seamlessly into various spaces, making it an ideal choice for both new installations and replacement projects.

The Bryant 581B also comes with advanced safety features, including a self-diagnostic control board that monitors the system's performance. This feature allows for easy troubleshooting and maintenance, prolonging the life of the furnace. Additionally, the furnace is equipped with an induced draft blower that enhances venting efficiency and safety by ensuring that combustion gases are safely expelled from the home.

For homeowners looking for enhanced control, the Bryant 581B is compatible with a range of smart thermostats, providing the ability to monitor and adjust heating settings remotely. This integration with smart technology ensures that homeowners can maintain their desired comfort levels while maximizing efficiency.

In conclusion, the Bryant 581B gas furnace is a top-tier option that combines efficiency, durability, and modern technology. With its high AFUE rating, multi-speed blower, and advanced safety features, it promises to deliver unparalleled comfort and peace of mind for years to come. Whether for a new build or an upgrade, the Bryant 581B is an investment that pays off in both comfort and savings.