Liquid Propane
Units are shipped for use with natural gas, but may be ®eld- converted for use with liquid propane with accessory LP (liq- uid propane) kit.
All LP gas equipment must conform to NFPA safety standards.
LP gas pressure at the unit must not be less than 5 in. wg or greater than 13 in. wg under full load. Maintaining proper gas pressure depends on:
1.Vaporization rate. (Vaporization rate is determined by the temperature of the LP and the level of LP in the tank.)
2.Proper pressure regulation.
3.Pressure drop in lines between regulators and between the
Contact your LP gas supplier or regulator manufacturer for further details regarding tank sizing, recommended regula- tor settings, and pipe sizing.
Special pipe compound must be used when assembling pip- ing for liquid propane gas as white lead or commercial com- pounds will be easily dissolved. Use a
D. Field Duct Connections
NOTE: The design and installation of the duct system must be in accordance with the standards of the NFPA for the in- stallation of
Adhere to the following criteria when selecting, sizing, and installing the duct system:
1.Remove appropriate panels from unit to obtain either a horizontal or vertical application. If units are installed for horizontal applications, remove vertical duct covers, save screws, and install covers on vertical duct openings.
2.Select and size ductwork,
Fig. 12 Ð Location of Coil Area Not To Be Drilled
CAUTION: When the duct system fastening holes are being drilled into the side of the unit for duct ¯anges, be careful not to puncture the coil or coil tubes. See Fig. 12.
3.Use ¯exible transition between rigid ductwork and unit to prevent transmission of vibration. The transition may be screwed or bolted to duct ¯anges. Use suitable gas- kets to ensure weather- and airtight seal.
4.When horizontal return is used, install external, ®eld- supplied air ®lters in
5.For horizontal applications, be sure ductwork does not cover nameplate.
6.Size all ductwork for maximum required air¯ow (either heating or cooling) for unit being installed. Avoid abrupt duct size increases or decreases.
7.Adequately insulate and weatherproof all ductwork lo- cated outdoors. Insulate ducts passing through uncon- ditioned space, and use vapor barrier in accordance with latest issue of SMACNA (Sheet Metal and Air Condi- tioning Contractors National Association) and ACCA (Air Conditioning Contractors of America) minimum instal- lation standards for heating and
8.Flash, weatherproof, and vibration isolate all openings in building structure in accordance with local codes and good building practices.
E.Electrical Connections
WARNING: The unit cabinet must have an uninter- rupted, unbroken electrical ground to minimize the pos- sibility of personal injury if an electrical fault should occur. This ground may consist of electrical wire con- nected to the unit ground lug in the control compart- ment or conduit approved for electrical ground when installed in accordance with the NEC (National Elec- trical Code); ANSI/NFPA, latest edition, (in Canada, Canadian Electrical Code CSA [Canadian Standards As- sociation] C22.1); and local electrical codes. Do not use gas piping as an electrical ground. Failure to adhere to this warning could result in personal injury.
CAUTION: Failure to follow these precautions could result in damage to the unit being installed:
Field Power Supply (Fig.
1.Make all electrical connections in accordance with NEC ANSI/NFPA, latest edition, and local electrical codes gov- erning such wiring. In Canada, all electrical connec- tions must be in accordance with CSA standard C22.1 Canadian Electrical Code Part 1 and applicable local codes. Refer to unit wiring diagram.
2.Use only copper conductor for connections between ®eld- supplied electrical disconnect switch and unit. DO NOT USE ALUMINUM WIRE. Maximum wire size is no. 2 AWG (American Wire Gage).
Ð9Ð