581B,C

Table 2 — Physical Data 581C (cont)

UNIT SIZE 581C

 

024

036

048

060

FURNACE SECTION

 

 

 

 

 

Rollout Switch Cutout Temp (F)†

 

195

195

195

195

Burner Orifice Diameter (in. ...drill size)**

 

 

 

 

 

Natural Gas —Std

071/072

.113...33

.113...33

.113...33

.113...33

 

114/115

.113...33

.113...33

.113...33

.113...33

 

149/150

.129...30

.129...30

.129...30

 

060N

.102...38

.102...38

.102...38

 

090N

.102...38

.102...38

.102...38

 

120N

.116...32

.116...32

Propane —Alt††

071/072

.089...43

.089...43

.089...43

.089...43

 

114115

.089...43

.089...43

.089...43

.089...43

 

149/150

.102...38

.102...38

.104...39

 

060N

.082...45

.082...45

.082...45

 

090N

.082...45

.082...45

.082...45

Thermostat Heat Anticipator Setting (amps)

120N

.094...42

.094...42

 

 

 

 

 

208/230/460 v

 

 

 

 

 

First Stage

 

.14

.14

.14

.14

Second Stage

 

.14

.14

.14

.14

Gas Input (Btuh)

 

 

 

 

 

First Stage/Second Stage (3---phase units)

072

50,000/ 72,000

50,000/ 72,000

50,000/ 72,000

50,000/ 72,000

 

115

82,000/115,000

82,000/115,000

82,000/115,000

82,000/115,000

 

150

120,000/150,000

120,000/150,000

120,000/150,000

 

071II

—/72,000

—/72,000

—/72,000

 

114II

—/115,000

—/115,000

—/115,000

 

149II

—/150,000

—/150,000

 

060N***

—/ 60,000

—/60,000

—/60,000

 

090N***

—/ 90,000

—/90,000

—/90,000

 

120N***

—/120,000

—/120,000

Efficiency (Steady State) (%)

072

82

82

82

82

 

115

80

81

81

81

 

150

80

80

80

 

071

82

82

82

 

114

80

81

81

 

149

80

80

 

060N

80

80

80

 

090N

80

80

80

 

120N

80

80

Temperature Rise Range

072

15---45

15---45

15---45

15---45

 

115

55---85

35---65

35---65

35---65

 

150

50---80

50---80

50---80

 

071

15---45

15---45

15---45

 

114

55---85

35---65

35---65

 

149

50---80

50---80

 

060N

20---50

20---50

20---50

 

090N

30---60

30---60

30---60

Manifold Pressure (in. wg)

120N

40---70

40---70

 

 

 

 

 

Natural Gas —Std

 

3.5

3.5

3.5

3.5

Propane —Alt††

 

3.5

3.5

3.5

3.5

Maximum Static Pressure (in. wg)

 

1.0

1.0

1.0

1.0

Field Gas Connection Size (in.)

 

1/2

1/2

1/2

1/2

HIGH-PRESSURE SWITCH (psig)

 

 

 

 

Standard Compressor Internal Relief

450

±

50

 

Cutout

428

 

 

Reset (Auto.)

320

 

 

LOSS-OF-CHARGE SWITCH/LOW-PRESSURE

 

 

 

 

(Liquid Line) (psig)

 

 

 

 

Cutout

7

±

3

 

Reset (Auto.)

22

±

5

 

FREEZE PROTECTION THERMOSTAT

 

 

 

 

Opens (F)

30

±

5

 

Closes (F)

45

±

5

 

OUTDOOR-AIR INLET SCREENS

Cleanable. Screen quantity and size varies with option selected.

RETURN-AIR FILTERS

Throwaway

Quantity...Size (in.)

2...16 x 25 x 2

 

 

4...16 x 16 x 2

LEGEND

removed and the units will no longer be classified as Low NOx units.

Bhp — Brake Horsepower

ll Three-phase standard models have heating inputs as shown. Single-phase stan-

 

dard models have one-stage heating with heating input values.

**60,000 and 72,000 Btuh heat input units have 2 burners. 90,000 and 120,000 Btuh

***California compliant three-phase models.

heat input units have 3 burners. 115,000 Btuh heat input units and 150,000 Btuh

†††California SCAQMD compliant low NOx models have combustion products that are

Heat input units have 3 burners.

controlled to 40 nanograms per joule or less.

††A propane kit is available as an accessory. Kit may be used at elevations as high as

 

2000 ft. If a propane kit is used with Low NOx units, the Low NOx baffle must be

 

12

Page 12