581B,C
Table 2 — Physical Data 581C (cont)
UNIT SIZE 581C |
| 024 | 036 | 048 | 060 |
FURNACE SECTION |
|
|
|
|
|
Rollout Switch Cutout Temp (F)† |
| 195 | 195 | 195 | 195 |
Burner Orifice Diameter (in. ...drill size)** |
|
|
|
|
|
Natural Gas | 071/072 | .113...33 | .113...33 | .113...33 | .113...33 |
| 114/115 | .113...33 | .113...33 | .113...33 | .113...33 |
| 149/150 | — | .129...30 | .129...30 | .129...30 |
| 060N | .102...38 | .102...38 | .102...38 | — |
| 090N | .102...38 | .102...38 | .102...38 | — |
| 120N | — | .116...32 | .116...32 | — |
Propane | 071/072 | .089...43 | .089...43 | .089...43 | .089...43 |
| 114115 | .089...43 | .089...43 | .089...43 | .089...43 |
| 149/150 | — | .102...38 | .102...38 | .104...39 |
| 060N | .082...45 | .082...45 | .082...45 | — |
| 090N | .082...45 | .082...45 | .082...45 | — |
Thermostat Heat Anticipator Setting (amps) | 120N | — | .094...42 | .094...42 | — |
|
|
|
|
| |
208/230/460 v |
|
|
|
|
|
First Stage |
| .14 | .14 | .14 | .14 |
Second Stage |
| .14 | .14 | .14 | .14 |
Gas Input (Btuh) |
|
|
|
|
|
First Stage/Second Stage | 072 | 50,000/ 72,000 | 50,000/ 72,000 | 50,000/ 72,000 | 50,000/ 72,000 |
| 115 | 82,000/115,000 | 82,000/115,000 | 82,000/115,000 | 82,000/115,000 |
| 150 | — | 120,000/150,000 | 120,000/150,000 | 120,000/150,000 |
| 071II | — | |||
| 114II | — | |||
| 149II | — | — | ||
| 060N*** | — | |||
| 090N*** | — | |||
| 120N*** | — | — | ||
Efficiency (Steady State) (%) | 072 | 82 | 82 | 82 | 82 |
| 115 | 80 | 81 | 81 | 81 |
| 150 | — | 80 | 80 | 80 |
| 071 | 82 | 82 | 82 | — |
| 114 | 80 | 81 | 81 | — |
| 149 | — | 80 | 80 | — |
| 060N | 80 | 80 | 80 | — |
| 090N | 80 | 80 | 80 | — |
| 120N | — | 80 | 80 | — |
Temperature Rise Range | 072 | ||||
| 115 | ||||
| 150 | — | |||
| 071 | — | |||
| 114 | — | |||
| 149 | — | — | ||
| 060N | — | |||
| 090N | — | |||
Manifold Pressure (in. wg) | 120N | — | — | ||
|
|
|
|
| |
Natural Gas |
| 3.5 | 3.5 | 3.5 | 3.5 |
Propane |
| 3.5 | 3.5 | 3.5 | 3.5 |
Maximum Static Pressure (in. wg) |
| 1.0 | 1.0 | 1.0 | 1.0 |
Field Gas Connection Size (in.) |
| 1/2 | 1/2 | 1/2 | 1/2 |
|
|
|
| |
Standard Compressor Internal Relief | 450 | ± | 50 |
|
Cutout | 428 |
|
| |
Reset (Auto.) | 320 |
|
| |
|
|
|
| |
(Liquid Line) (psig) |
|
|
|
|
Cutout | 7 | ± | 3 |
|
Reset (Auto.) | 22 | ± | 5 |
|
FREEZE PROTECTION THERMOSTAT |
|
|
|
|
Opens (F) | 30 | ± | 5 |
|
Closes (F) | 45 | ± | 5 |
|
Cleanable. Screen quantity and size varies with option selected. | ||||
| Throwaway | |||
Quantity...Size (in.) | 2...16 x 25 x 2 |
|
| 4...16 x 16 x 2 |
LEGEND | removed and the units will no longer be classified as Low NOx units. | |||
Bhp — Brake Horsepower | ll | |||
| dard models have |
**60,000 and 72,000 Btuh heat input units have 2 burners. 90,000 and 120,000 Btuh | ***California compliant | |
heat input units have 3 burners. 115,000 Btuh heat input units and 150,000 Btuh | ||
†††California SCAQMD compliant low NOx models have combustion products that are | ||
Heat input units have 3 burners. | ||
controlled to 40 nanograms per joule or less. | ||
††A propane kit is available as an accessory. Kit may be used at elevations as high as | ||
| ||
2000 ft. If a propane kit is used with Low NOx units, the Low NOx baffle must be |
|
12