Table 7—CO2Sensor Standard Settings

SETTING

EQUIPMENT

OUTPUT

VENTILATION

ANALOG

CO2

OPTIONAL

RELAY

RATE

OUTPUT

CONTROL RANGE

RELAY SETPOINT

HYSTERESIS

 

 

 

(cfm/Person)

(ppm)

(ppm)

(ppm)

 

 

 

 

1

 

Proportional

Any

0-10V

0-2000

1000

50

 

4-20 mA

 

 

 

 

 

 

 

2

Interface w/Standard

Proportional

Any

2-10V

0-2000

1000

50

Building Control System

7-20 mA

 

 

 

 

 

 

3

 

Exponential

Any

0-10V

0-2000

1100

50

 

4-20 mA

 

 

 

 

 

 

 

4

 

Proportional

15

0-10V

0-1100

1100

50

 

4-20 mA

 

 

 

 

 

 

 

5

 

Proportional

20

0-10V

0- 900

900

50

 

4-20 mA

 

Economizer

 

 

 

 

 

6

Exponential

15

0-10V

0-1100

1100

50

 

 

4-20 mA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7

 

Exponential

20

0-10V

0- 900

900

50

 

4-20 mA

 

 

 

 

 

 

 

8

Health & Safety

Proportional

0-10V

0-9999

5000

500

4-20 mA

 

 

 

 

 

 

 

9

Parking/Air Intakes/

Proportional

0-10V

0-2000

700

50

Loading Docks

4-20 mA

 

 

 

 

 

 