BASE UNIT DIMENSIONS – 583B042-060
C99074
REQUIRED CLEARANCE FOR OPERATION AND SERVICING
| in. [mm] |
| |
EVAP. COIL ACCESS SIDE | 36.00 [914.0] |
| |
POWER ENTRY SIDE | 36.00 | [914.0] |
|
(EXCEPT FOR NEC REQUIREMENTS) |
|
|
|
UNIT TOP | 36.00 | [914.0] |
|
SIDE OPPOSITE DUCTS | 36.00 | [914.0] |
|
DUCT PANEL | 12.00 | [304.8] | * |
REQUIRED CLEARANCE TO COMBUSTIBLE MATL.
| in. [mm] | |
TOP OF UNIT | 14.00 | [355.6] |
DUCT SIDE OF UNIT | 2.00 | [50.8] |
SIDE OPPOSITE DUCTS | 14.00 | [355.6] |
BOTTOM OF UNIT | 0.50 | [12.7] |
ELECTRIC HEAT PANEL | 36.00 | [914.4] |
*MINIMUM DISTANCES: IF UNIT IS PLACED LESS THAN 12.00 in. [304.8 mm.]
FROM WALL THEN SYSTEM PERFORMANCE MAYBE COMPROMISED.
NEC. REQUIRED CLEARANCES.
MILLIMETERS [IN.]
BETWEEN UNITS, POWER ENTRY SIDE | 42.00 [1066.8] |
UNIT AND UNGROUNDED SURFACES, POWER ENTRY SIDE ... | 36.00 [914.0] |
UNIT AND BLOCK OR CONCRETE WALLS AND OTHER |
|
GROUNDED SURFACES, POWER ENTRY SIDE | 42.00 [1066.8] |
FLUE HOOD
| ELECTRICAL | UNIT WEIGHT | UNIT HEIGHT | CENTER OF GRAVITY | |||
UNIT | IN. [MM] |
| IN. [MM] |
| |||
CHARACTERISTICS |
|
|
|
| |||
| lb. | kg. | “A” | X | Y | Z | |
|
| ||||||
|
|
|
|
|
|
|
|
583B042060/090 |
|
|
|
|
|
| |
382 | 173.3 | 38.98 [990.2] | 23.0 [584.2] | 16.3 [412.8] | 16.6 [421.6] | ||
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
583B048090/115/130 |
|
|
|
|
|
| |
421 | 191.0 | 38.98 [990.2] | 21.5 [546.1] | 16.6 [422.1] | 18.0 [457.2] | ||
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
583B060090/115/130 |
|
|
|
|
|
| |
468 | 212.3 | 42.98 [1091.7] | 23.5 [596.9] | 16.3 [412.8] | 17.6 [447.0] | ||
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|