Bryant 583B manual PERFORMANCE DATA cont STANDARD INDOOR PSC MOTOR, COOLING CAPACITIES cont

Models: 583B

1 28
Download 28 pages 39.19 Kb
Page 15
Image 15
— 15—
tldb = t edb

PERFORMANCE DATA (cont)

STANDARD INDOOR PSC MOTOR

COOLING CAPACITIES (cont)

583B048 COOLING PERFORMANCE TABLE

 

Temp (F)

 

 

 

 

 

 

 

 

 

Evaporator Air — CFM/BF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Outdoor Air

 

1200 / 0.06

 

 

 

 

 

1600 / 0.08

 

 

 

 

 

2000 / 0.11

 

 

 

 

Entering

 

 

 

 

 

 

 

 

 

Evaporator Air — Ewb (F)

 

 

 

 

 

 

 

 

 

Condenser

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

62

 

 

67

 

 

72

 

62

 

 

 

67

 

72

 

62

 

 

67

 

 

72

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TC

47.9

 

 

52.3

 

 

56.8

 

49.6

 

 

 

53.7

 

58.1

 

50.5

 

 

54.0

 

 

57.7

75

 

SHC

41.5

 

 

34.8

 

 

28.2

 

47.4

 

 

 

38.7

 

29.9

 

50.5

 

 

41.6

 

 

30.7

 

 

kW

3.38

 

 

3.43

 

 

3.48

 

3.68

 

 

 

3.78

 

3.82

 

4.01

 

 

4.23

 

 

4.27

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TC

45.7

 

 

50.2

 

 

54.7

 

47.5

 

 

 

51.6

 

56.1

 

48.9

 

 

51.6

 

 

56.0

85

 

SHC

40.4

 

 

34.1

 

 

27.4

 

46.5

 

 

 

37.9

 

29.3

 

48.9

 

 

40.9

 

 

30.3

 

 

kW

3.77

 

 

3.80

 

 

3.86

 

4.03

 

 

 

4.16

 

4.21

 

4.36

 

 

4.63

 

 

4.68

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TC

43.3

 

 

47.9

 

 

52.3

 

45.3

 

 

 

49.2

 

53.7

 

47.0

 

 

48.9

 

 

53.5

95

 

SHC

39.1

 

 

33.1

 

 

26.5

 

45.3

 

 

 

37.1

 

28.5

 

47.0

 

 

39.9

 

 

29.5

 

 

kW

4.15

 

 

4.23

 

 

4.28

 

4.41

 

 

 

4.57

 

4.63

 

4.78

 

 

5.07

 

 

5.11

 

 

TC

39.2

 

 

43.7

 

 

47.9

 

41.5

 

 

 

44.6

 

48.9

 

42.9

 

 

44.3

 

 

48.9

105

 

SHC

36.4

 

 

30.8

 

 

24.6

 

41.5

 

 

 

34.6

 

26.4

 

42.9

 

 

37.5

 

 

27.6

 

 

kW

4.67

 

 

4.79

 

 

4.82

 

4.93

 

 

 

5.14

 

5.19

 

5.34

 

 

5.60

 

 

5.66

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TC

35.3

 

 

39.6

 

 

43.7

 

38.2

 

 

 

40.3

 

44.3

 

39.3

 

 

40.1

 

 

44.0

115

 

SHC

34.4

 

 

29.0

 

 

23.0

 

38.2

 

 

 

32.8

 

24.7

 

39.3

 

 

35.7

 

 

26.0

 

 

kW

5.32

 

 

5.50

 

 

5.54

 

5.65

 

 

 

5.85

 

5.89

 

6.06

 

 

6.27

 

 

6.36

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TC

32.0

 

 

35.2

 

 

38.7

 

34.4

 

 

 

35.5

 

39.3

 

35.0

 

 

35.2

 

 

38.8

125

 

SHC

32.0

 

 

27.0

 

 

21.0

 

34.4

 

 

 

30.8

 

22.8

 

35.0

 

 

33.4

 

 

24.0

 

 

kW

6.16

 

 

6.31

 

 

6.34

 

6.47

 

 

 

6.63

 

6.69

 

6.89

 

 

7.04

 

 

7.16

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

583B060 COOLING PERFORMANCE TABLE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Temp (F)

 

 

 

 

 

 

 

 

 

Evaporator Air — CFM/BF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Outdoor Air

 

1500 / 0.05

 

 

 

1750 / 0.06

 

 

 

 

 

2000 / 0.07

 

 

 

2500 / 0.08

 

 

Entering

 

 

 

 

 

 

 

 

 

Evaporator Air — Ewb (F)

 

 

 

 

 

 

 

 

 

Condenser

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

62

 

67

 

72

 

62

 

67

 

72

 

62

 

 

67

 

72

62

 

67

 

 

72

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TC

57.6

 

64.3

 

69.9

59.8

 

66.1

 

71.7

 

61.7

 

67.6

 

73.1

65.0

 

69.6

 

75.1

75

 

SHC

50.6

 

43.0

 

34.4

55.5

 

46.2

 

36.3

 

59.8

 

49.3

 

38.1

65.0

 

54.8

 

41.3

 

 

kW

4.63

 

4.69

 

4.75

4.67

 

4.71

 

4.78

 

4.68

 

4.73

 

4.80

4.70

 

4.75

 

4.84

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TC

54.4

 

60.9

 

67.0

56.4

 

63.0

 

68.6

 

58.0

 

64.5

 

69.9

62.3

 

66.4

 

71.6

85

 

SHC

49.0

 

41.6

 

33.4

53.6

 

45.0

 

35.2

 

58.0

 

48.2

 

37.0

62.3

 

54.0

 

40.2

 

 

kW

5.06

 

5.17

 

5.21

5.10

 

5.17

 

5.23

 

5.14

 

5.18

 

5.26

5.17

 

5.21

 

5.29

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TC

51.2

 

57.5

 

63.7

53.1

 

59.4

 

65.3

 

55.1

 

60.7

 

66.5

59.3

 

62.7

 

68.1

95

 

SHC

47.5

 

40.0

 

32.2

51.9

 

43.5

 

34.0

 

55.1

 

46.8

 

35.8

59.3

 

52.8

 

39.1

 

 

kW

5.54

 

5.68

 

5.72

5.58

 

5.68

 

5.74

 

5.64

 

5.69

 

5.76

5.68

 

5.71

 

5.79

 

 

TC

45.8

 

51.9

 

57.7

47.8

 

53.4

 

59.1

 

50.2

 

54.6

 

60.1

53.8

 

56.2

 

61.4

105

 

SHC

44.0

 

37.0

 

29.5

47.8

 

40.3

 

31.4

 

50.2

 

43.4

 

33.1

53.8

 

49.3

 

36.2

 

 

kW

6.17

 

6.35

 

6.39

6.23

 

6.36

 

6.41

 

6.30

 

6.37

 

6.42

6.36

 

6.38

 

6.44

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TC

41.9

 

47.6

 

53.2

44.5

 

49.0

 

54.4

 

46.8

 

50.1

 

55.2

50.0

 

51.6

 

56.5

115

 

SHC

41.9

 

35.1

 

27.8

44.5

 

38.3

 

29.6

 

46.8

 

41.5

 

31.3

50.0

 

47.1

 

34.5

 

 

kW

6.75

 

6.94

 

6.98

6.83

 

6.95

 

6.99

 

6.82

 

6.95

 

7.01

6.94

 

6.95

 

7.03

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TC

38.6

 

43.2

 

48.3

41.1

 

44.5

 

49.4

 

43.1

 

45.4

 

50.0

46.0

 

46.7

 

51.0

125

 

SHC

38.6

 

33.2

 

25.8

41.1

 

36.3

 

27.6

 

43.1

 

39.3

 

29.1

46.0

 

44.5

 

32.1

 

 

kW

7.36

 

7.64

 

7.67

7.58

 

7.64

 

7.68

 

7.63

 

7.64

 

7.69

7.64

 

7.65

 

7.71

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LEGEND

BF

Bypass Factor

Ewb

Entering Wet-Bulb

kW

Total Unit Power Input

SHC

Sensible Heat Capacity (1000 Btuh)

TC

Cooling Capacity (1000 Btuh)

PSC

Permanent Split Capacitor

NOTES:

1.Ratings are net; they account for the effects of the evaporator-fan motor power and heat.

2.Direct interpolation is permissible. Do not extrapolate.

3.The following formulas may be used:

sensible capacity (Btuh) 1.10 x cfm

tlwb = Wet-bulb temperature corresponding to enthalpy of air leaving evaporator coil (hlwb)

hlwb = hewb

total capacity (Btuh)

4.5 x cfm

 

Where: hewb =

Enthalpy of air entering evaporator coil

4.The SHC is based on 80°F edb temperature of air entering evaporator coil. Below 80°F edb, subtract (Corr Factor x CFM) from SHC above 80°F edb, add (Corr Factor x CFM) to SHC Correction Factor = 1.10 x (1 + BF) x (edb + 80)

— 15—

Page 15
Image 15