ARI* CAPACITIES

COOLING CAPACITIES AND EFFICIENCIES

UNIT 583B

NOMINAL TONS

STANDARD CFM

NET COOLING

SEER†

SOUND RATINGS**

CAPACITIES (Btuh)

(dB)

 

 

 

 

 

 

 

 

 

 

024040

2

800

24,000

12.0

72

024060

 

 

 

 

 

030040

2-1/2

1000

29,000

12.0

72

036060

 

 

 

 

 

036060

3

1200

35,000

12.0

72

036090

 

 

 

 

 

042060

3-1/2

1400

41,000

12.0

73

042090

 

 

 

 

 

048090

 

 

 

 

 

048115

4

1600

48,000

12.0

78

048130

 

 

 

 

 

060090

 

 

 

 

 

060115

5

1750

59,000

12.0

76

060130

 

 

 

 

 

583B with ICM FIOP

Unit

“A”‡

“A”‡

SEER

583B

Capacity

EER

 

024

24,000

10.7

12.7

 

 

 

 

030

29,000

10.7

12.7

 

 

 

 

036

35,000

10.6

12.5

 

 

 

 

042

41,000

10.7

12.5

 

 

 

 

048

48,000

10.5

12.3

 

 

 

 

060

59,000

10.4

12.3

‡“A” Capacity– 80°F db/67°Fwb indoor & 95°Fdb outdoor.

 

 

LEGEND

dB

Decibels

db

Dry Bulb

SEER

— Seasonal Energy Efficiency Ratio

wb

Wet Bulb

*Air Conditioning & Refrigeration Institute.

Rated in accordance with U.S. Government DOE (Department of Energy) test procedures and/or ARI Standard 210/240-89.

**Tested in accordance with ARI Standard 270-95 (not listed in ARI).

NOTES:

1.Ratings are net values, reflecting the effects of circulating fan heat. Ratings are based on:

Cooling Standard: 80°F db, 67°F wb indoor entering-air tempera- ture and 95°F db outdoor entering-air temperature.

2.Before purchasing this appliance, read important energy cost and efficiency information available from your retailer.

TABLE OF CONTENTS

Page

Features/Benefits. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1,2

Model Number Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . 2

ARI Capacities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3,4

Physical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5,6

Options and Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7,8

Base Unit Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9,10

Accessory Dimensions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

Selection Procedure. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

Performance Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13-18

Typical Piping and Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

Application Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21

Typical Wiring Schematics. . . . . . . . . . . . . . . . . . . . . . . . . 22-25

Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26

Guide Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27,28

— 3—

Page 3
Image 3
Bryant manual Ari* Capacities, Cooling Capacities And Efficiencies, 583B with ICM FIOP, Table Of Contents