BASE UNIT DIMENSIONS — 583B024-036
REQ’D CLEARANCES FOR OPERATION AND SERVICING. in. (mm) Evaporator coil access side . . . . . . . . . . . . . . . . . . 36 (914)
Power entry side (except for NEC requirements) . | . . . . . . . . 36 | (914) |
Unit top | . . . . . . . . 48 (1219) | |
Side opposite ducts | . . . . . . . . 36 | (914) |
Duct panel | . . . . . . . 12 (304.8)* |
*Minimum distances: If unit is placed less than 12 in. (304.8 mm) from wall system, then the system performance may be compromised.
LEGEND
CG - Center of Gravity
COND - Condenser
EVAP - Evaporator
NEC - National Electrical Code
REQ'D - Required
Note: Dimensions are in in. (mm)
REQ’D CLEARANCES TO COMBUSTIBLE MAT’L. in. (mm)
Top of unit . . . . . . . . . . . . . . . . . . . . . . . . . 14 (355.6) Duct side of unit . . . . . . . . . . . . . . . . . . . . . . . 2 (50.8) Side opposite ducts . . . . . . . . . . . . . . . . . . . . . 14 (355.6) Bottom of unit . . . . . . . . . . . . . . . . . . . . . . . 0.50 (12.7) Flue panel . . . . . . . . . . . . . . . . . . . . . . . . . 36 (914.4)
NEC REQ’D CLEARANCES. in. (mm) |
|
|
|
| |
|
|
|
|
|
|
Between units, power entry side | . | . | . 42 | (1066.8) | |
Unit and ungrounded surfaces, power entry side | . | . | . . 36 (914) | ||
Unit and block or concrete walls and other grounded |
|
|
|
| |
surfaces, control box side | . | . | . 42 | (1066.8) |
| ELECTRICAL | UNIT WEIGHT | UNIT HEIGHT | CENTER OF GRAVITY | ||||
UNIT | IN. [MM] |
| IN. [MM] |
| ||||
CHARACTERISTICS |
|
|
|
| ||||
| lb. | kg. | “A” | X | Y | Z | ||
|
| |||||||
|
|
|
|
|
|
|
| |
583B024040/060 | 290 | 131.5 | 37.02 [940.3] | 22.0 [558.8] | 14.5 [368.3] | 16.0 [406.4] | ||
|
|
|
|
|
|
|
| |
583B030040/060 | 313 | 142.0 | 39.02 [991.1] | 22.0 [558.8] | 15.3 [387.4] | 17.6 [447.0] | ||
|
|
|
|
|
|
| ||
583B036060/090 |
|
|
|
|
|
| ||
321 | 145.6 | 35.02 [889.5] | 22.0 [558.8] | 15.3 [387.4] | 16.5 [419.1] | |||
|
|
|
|
|
|
|