Bryant 583B manual GUIDE SPECIFICATIONS continued

Models: 583B

1 28
Download 28 pages 39.19 Kb
Page 28
Image 28
GUIDE SPECIFICATIONS continued

GUIDE SPECIFICATIONS continued

K.Electrical Requirements:

All unit power wiring shall enter the unit cabinet at a single location.

L.Motors:

1.Compressor motors shall be of the refrigerant-cooled type with line-break thermal and current overload pro- tection.

2.All fan motors shall have permanently lubricated bear- ings, and inherent, automatic reset, thermal overload protection.

3.Condenser fan motor shall be totally enclosed.

M.Grille:

1.Louvered Grille:

Louvered grille shall be factory-installed to provide hail guard and vandalism protection.

N.Duct Conversion:

Shall be available with the use of included duct covers. O. Special Features:

1.ICM Indoor Blower FIOP:

Integral control motor shall be a factory installed option for optimizing comfort levels in all operating modes and increasing system efficiency.

2.Coil Options:

Shall include factory-installed optional copper/ copper and vinyl-coated refrigerant coils.

3.Economizer:

a.Economizer controls capable of providing free cool- ing using outside air.

b.Equipped with low leakage dampers not to exceed 3% leakage, at 1.0 in. wg pressure differential.

c.Spring return motor shuts off outdoor damper on power failure.

4.Flat Roof Curb:

Curbs shall have seal strip and a wood nailer for flash- ing and shall be installed per manufacturer’s instruc- tions.

5.Manual Outdoor Air Damper:

Package shall consist of damper, birdscreen, and rain- hood which can be preset to admit outdoor air for year- round ventilation.

6.Thermostat:

To provide for one-stage heating and cooling in addition manual or automatic changeover and indoor fan control.

7.Natural-to-Propane Conversion Kit:

Shall be complete with all required hardware to convert to liquid propane (LP) operation.

8.Low Ambient Package:

Shall consist of a solid-state control and condenser coil temperature sensor for controlling condenser-fan mo- tor operation, which shall allow unit to operate down to 0° F outdoor ambient temperature.

9.Filter Rack Kit:

Shall provide filter mounting for downflow applications.

10.Square-To-Round Duct Transitions:

Shall have the ability to convert the supply and return openings from rectangular to round.

11.Compressor Protection (Time Guard® II Kit) Solid-state control shall protect compressor by prevent- ing “short cycling.”

12.Crankcase Heater:

Shall provide anti-floodback protection for low-load cooling applications.

13.High Altitude Kit:

Shall consist of natural gas orifices to compensate for gas heat operation at 2001 to 6000 ft above sea level.

14.Low NOx (Natural Gas only) option:

Shall provide NOx reduction to values below 40 nano- grams/joule to meet California emission requirements.

15.Compressor Hard Start Kit:

Shall provide additional starting torque for single-phase compressors. (Single phase only).

16.Rigging kit includes lifting brackets which are inserted into the basepan handholds to rig unit for rooftop appli- cations.

SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE

UNIT MUST BE INSTALLED IN ACCORDANCE

WITH INSTALLATION INSTRUCTIONS

Cancels: PDS 583B.24.2

Form PDS 583B.24.3

© 2001 Bryant Heating & Cooling Systems, 7310 W. Morris St., Indpls., IN 46231

PRINTED IN U.S.A.

Catalog No. 5258-305 5-01

— 28—

Page 28
Image 28
Bryant 583B manual GUIDE SPECIFICATIONS continued