F. Heating Sequence of Operation

See Fig. 26-33 and unit wiring label.

On a call for heating, terminal ``W'' of the thermostat is en- ergized, starting the induced-draft motor. When the hall- effect sensor on the induced-draft motor senses that it has reached the required speed, the burner sequence begins. This function is performed by the integrated gas control (IGC). The evaporator-fan motor is energized 45 seconds after ¯ame is established. When the thermostat is satis®ed and ``W'' is deen- ergized, the burners stop ®ring and the evaporator-fan motor shuts off after a 45-second time-off delay.

A LED (light-emitting diode) indicator is provided on the con- trol board to monitor operation. The control board is located by removing the burner access panel. During normal opera- tion, the LED is continuously on. See Table 7 for error codes.

Table 7 Ð LED Indications

ERROR CODE

LED INDICATION

Normal Operation

On

Hardware Failure

Off

Fan On/Off Delay Modi®ed

1 Flash

Limit Switch Fault

2 Flashes

Flame Sense Fault

3 Flashes

Four Consecutive Limit Switch Faults

4 Flashes

Ignition Lockout Fault

5 Flashes

Induced-Draft Motor Fault

6 Flashes

Rollout Switch Fault

7 Flashes

Internal Control Fault

8 Flashes

 

 

NOTES:

1.There is a 3-second pause between error code displays.

2.If more than one error code exists, all applicable error codes will be displayed in numerical sequence.

3.This chart is on the wiring diagram located inside the burner access panel.

G. Limit Switches

Normally-closed limit switch (LS) completes the control cir- cuit through the thermostat R circuit. Should the leaving-air temperature rise above the maximum allowable tempera- ture, the limit switch opens and the R control circuit ``breaks.'' Any interruption in the R control circuit instantly closes the gas valve and stops gas ¯ow to the burners and pilot. The blower motor continues to run until LS resets.

When the air temperature at the limit switch drops to the low-temperature setting of the limit switch, the switch closes and completes the R control circuit. The electric-spark igni- tion system cycles and the unit returns to normal heating operation.

H. Auxiliary Limit Switch Ð Rollout

The function of the switch is to close the main gas valve in the event of ¯ame rollout. The switch is located above the main burners. When the temperature at the auxiliary switch reaches the maximum allowable temperature, the R control circuit trips, closing the gas valve and stopping gas ¯ow to the burners. The indoor (evaporator) fan motor (IFM) and in- duced draft motor continue to run until switch is reset.

III.START UP COOLING SECTION AND MAKE ADJUSTMENTS

CAUTION: Complete the required procedures given in the Pre-Start-Up section on page 22 before starting the unit.

Do not jumper any safety devices when operating the unit.

Do not operate the compressor when the outdoor tem- perature is below 40 F (unless accessory low-ambient kit is installed).

Do not rapid-cycle the compressor. Allow 5 minutes be- tween ``on'' cycles to prevent compressor damage.

Checking Cooling Control Operation

Start and check the unit for proper cooling control operation as follows:

1.Place room thermostat SYSTEM switch in OFF posi- tion. Observe that blower motor starts when FAN switch is placed in ON position and shuts down when FAN switch is placed in AUTO. position.

2.Place SYSTEM switch in COOL position and FAN switch in AUTO. position. Set cooling control below room tem- perature. Observe that compressor, condenser fan, and evaporator blower motors start. Observe that cooling cycle shuts down when control setting is satis®ed. The evaporator fan will continue to run for 30 seconds.

3.When using an auto.-changeover room thermostat, place both SYSTEM and FAN switches in AUTO. positions. Observe that unit operates in heating mode when tem- perature control is set to ``call for heating'' (above room temperature) and operates in cooling mode when tem- perature control is set to ``call for cooling'' (below room temperature).

IMPORTANT: Three-phase, scroll compressor units (588A048,060 and 589A036-060) are direction-oriented. These units must be checked to ensure proper compressor 3-phase power lead orientation. If not corrected within 5 minutes, the internal protector will shut off the compressor. The 3-phase power leads to the unit must be reversed to correct rotation. When turning backwards, scroll compressors emit elevated noise levels, and the difference between compressor suction and discharge pressures may be dramatically lower than normal.

(Text continued on page 35.)

Ð26Ð

Page 26
Image 26
Bryant 588A, 589A user manual III. Start UP Cooling Section and Make Adjustments

589A, 588A specifications

The Bryant 588A is a high-efficiency gas furnace celebrated for its advanced technology and superior performance in residential heating. Known for its reliability and durable construction, this model is ideal for homeowners looking for warmth and comfort during colder months.

One of the standout features of the Bryant 588A is its remarkable AFUE (Annual Fuel Utilization Efficiency) rating, which can reach up to 96.5%. This high efficiency means that a significant portion of the fuel consumed is converted into usable heat, leading to lower energy bills and a reduced carbon footprint. The furnace utilizes a two-stage heating system, which improves comfort levels by providing more consistent temperatures and reducing the frequency of temperature swings in the home.

Another notable characteristic is the incorporation of a multi-speed blower motor. This innovation enhances airflow and optimizes energy use by adjusting the fan speed according to the heating needs of the home. The variable speed operation also helps to minimize noise levels, creating a quieter environment compared to traditional single-speed furnaces.

The Bryant 588A features an advanced control system that allows for better system management and can be integrated with smart home technologies. This allows homeowners to monitor and adjust their heating settings remotely, offering convenience and efficiency. Additionally, the furnace is compatible with Bryant’s Evolution System, which provides advanced diagnostic features and improved energy performance.

Durability is a key characteristic of the Bryant 588A, as it is constructed with a heavy-duty cabinet designed to withstand the rigors of daily use and harsh weather conditions. The unit also includes a corrosion-resistant heat exchanger, ensuring longevity and reliability.

Furthermore, the Bryant 588A operates quietly, thanks to its insulated cabinet and advanced design. This feature is especially appreciated by homeowners seeking a peaceful living environment free from disruptive noises typically associated with heating systems.

In summary, the Bryant 588A gas furnace combines high efficiency, innovative technology, and durable construction. Its effective heating capabilities paired with user-friendly features make it a smart investment for anyone looking to enhance their home heating system while enjoying lower energy costs and increased comfort.