REQ'D CLEARANCES FOR SERVICING. in. (mm)

Duct panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0

Unit top . . . . . . . . . . . . . . . . . . . . . . . . . . . 36 (914)

Side opposite ducts

. 36

(914)

Compressor access

. 36

(914)

(Except for NEC requirements)

 

 

REQ'D CLEARANCES TO COMBUSTIBLE MAT'L. in. (mm)

 

 

Maximum extension of overhangs . . . . . . . . . . . . . . . 48 (1219)

Unit top . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 (356)

Duct side of unit . . . . . . . . . . . . . . . . . . . . . . . . 2 (51)

Side opposite ducts

.

. 14 (356)

Bottom of unit

. . . . . 0

Flue panel

.

. 36 (914)

NEC REQ'D CLEARANCES. in. (mm)

 

 

Between units, control box side

 

. 42 (1067)

Unit and ungrounded surfaces, control box side

.

. 36 (914)

Unit and block or concrete walls and other grounded

 

 

surfaces, control box side

 

. 42 (1067)

UNIT

ELECTRICAL

UNIT WEIGHT

 

CORNER WEIGHT

 

 

 

(lb/kg)

 

588A

CHARACTERISTICS

 

 

 

 

 

lb

kg

A

B

 

C

D

 

 

 

048080

208/230-1-60, 208/230-3-60, 460-3-60

414

188

107/49

83/38

 

158/72

66/30

048100/120/140

208/230-1-60, 208/230-3-60, 460-3-60

426

193

110/50

86/39

 

159/72

71/32

060080

208/230-1-60, 208/230-3-60, 460-3-60

453

206

117/53

93/42

 

167/76

76/35

060100/120/140

208/230-1-60, 208/230-3-60, 460-3-60

465

211

120/55

96/44

 

167/76

82/37

 

 

 

 

 

 

 

 

 

UNIT

CENTER OF GRAVITY (in./mm)

588A

X

Y

Z

048080

28.76/731

23.46/596

15.35/390

048100/120/140

28.42/722

23.42/595

15.35/390

060080

28.36/720

23.27/591

15.35/390

060100/120/140

27.95/710

23.23/590

15.35/390

 

 

LEGEND

 

 

CG

Ð

Center of Gravity

MAT'L

Ð

Material

COND

Ð Condenser

NEC

Ð National Electrical Code

LV

Ð

Low Voltage

REQ'D

Ð

Required

NOTES:

1.Clearances must be maintained to prevent recirculation of air from outdoor- fan discharge.

2.Adequate clearance around air openings into combustion chamber must be provided.

Fig. 4 Ð 588A048,060 Without Base Rail, Unit Dimensions