REQ'D CLEARANCES FOR SERVICING. in. (mm)
Duct panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0
Unit top . . . . . . . . . . . . . . . . . . . . . . . . . . . 36 (914)
Side opposite ducts | . | . 36 | (914) |
Compressor access | . | . 36 | (914) |
(Except for NEC requirements) |
|
|
|
REQ'D CLEARANCES TO COMBUSTIBLE MAT'L. in. (mm) |
|
|
|
Maximum extension of overhangs . . . . . . . . . . . . . . . 48 (1219)
Unit top . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 (356)
Duct side of unit . . . . . . . . . . . . . . . . . . . . . . . . 2 (51)
Side opposite ducts | . . . . . . . 14 (356) | |||
Bottom of unit | . . | . . | . . . . . . 0 | |
Flue panel | . . | . . | . | . . 36 (914) |
NEC REQ'D CLEARANCES. in. (mm) |
|
|
|
|
Between units, control box side | . . . . . . 42 (1067) | |||
Unit and ungrounded surfaces, control box side . . | . . | . . | . | . . 36 (914) |
Unit and block or concrete walls and other grounded |
|
|
|
|
surfaces, control box side | . . | . . | . | . 42 (1067) |
UNIT | ELECTRICAL | UNIT WEIGHT |
| CORNER WEIGHT |
| |||
|
| (lb/kg) |
| |||||
588A | CHARACTERISTICS |
|
|
|
|
| ||
lb | kg | A | B |
| C | D | ||
|
|
| ||||||
048080 | 438 | 199 | 113/51 | 89/40 |
| 164/75 | 72/33 | |
048100/120/140 | 450 | 205 | 116/53 | 92/42 |
| 165/75 | 77/35 | |
060080 | 477 | 217 | 123/56 | 99/45 |
| 173/79 | 82/37 | |
060100/120/140 | 489 | 222 | 126/57 | 102/46 |
| 173/79 | 88/40 | |
|
|
|
|
|
|
|
|
|
UNIT | CENTER OF GRAVITY (in./mm) | ||
588A | X | Y | Z |
048080 | 28.54/724.9 | 20.00/508 | 17.66/448.6 |
048100/120/140 | 28.22/716.8 | 20.05/509.3 | 17.66/448.6 |
060080 | 28.18/715.6 | 20.19/512.8 | 17.66/448.6 |
060100/120/140 | 27.79/705.9 | 20.23/513.8 | 17.66/448.6 |
|
|
|
|
|
| LEGEND |
|
| |
CG | Ð | Center of Gravity | MAT'L | Ð | Material |
COND | Ð Condenser | NEC | Ð National Electrical Code | ||
LV | Ð | Low Voltage | REQ'D | Ð | Required |
NOTES:
1.Clearances must be maintained to prevent recirculation of air from outdoor- fan discharge.
2.Adequate clearance around air openings into combustion chamber must be provided.
Fig. 5 Ð 588A048,060 With Optional Base Rail, Unit Dimensions