REQ'D CLEARANCES FOR SERVICING. in. (mm)

Duct panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0

Unit top . . . . . . . . . . . . . . . . . . . . . . . . . . . 36 (914)

Side opposite ducts

.

. 36

(914)

Compressor access

.

. 36

(914)

(Except for NEC requirements)

 

 

 

REQ'D CLEARANCES TO COMBUSTIBLE MAT'L. in. (mm)

 

 

 

Maximum extension of overhangs . . . . . . . . . . . . . . . 48 (1219)

Unit top . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 (356)

Duct side of unit . . . . . . . . . . . . . . . . . . . . . . . . 2 (51)

Side opposite ducts

. . . . . . . 14 (356)

Bottom of unit

. .

. .

. . . . . . 0

Flue panel

. .

. .

.

. . 36 (914)

NEC REQ'D CLEARANCES. in. (mm)

 

 

 

 

Between units, control box side

. . . . . . 42 (1067)

Unit and ungrounded surfaces, control box side . .

. .

. .

.

. . 36 (914)

Unit and block or concrete walls and other grounded

 

 

 

 

surfaces, control box side

. .

. .

.

. 42 (1067)

UNIT

ELECTRICAL

UNIT WEIGHT

 

CORNER WEIGHT

 

 

 

(lb/kg)

 

588A

CHARACTERISTICS

 

 

 

 

 

lb

kg

A

B

 

C

D

 

 

 

048080

208/230-1-60, 208/230-3-60, 460-3-60

438

199

113/51

89/40

 

164/75

72/33

048100/120/140

208/230-1-60, 208/230-3-60, 460-3-60

450

205

116/53

92/42

 

165/75

77/35

060080

208/230-1-60, 208/230-3-60, 460-3-60

477

217

123/56

99/45

 

173/79

82/37

060100/120/140

208/230-1-60, 208/230-3-60, 460-3-60

489

222

126/57

102/46

 

173/79

88/40

 

 

 

 

 

 

 

 

 

UNIT

CENTER OF GRAVITY (in./mm)

588A

X

Y

Z

048080

28.54/724.9

20.00/508

17.66/448.6

048100/120/140

28.22/716.8

20.05/509.3

17.66/448.6

060080

28.18/715.6

20.19/512.8

17.66/448.6

060100/120/140

27.79/705.9

20.23/513.8

17.66/448.6

 

 

 

 

 

 

LEGEND

 

 

CG

Ð

Center of Gravity

MAT'L

Ð

Material

COND

Ð Condenser

NEC

Ð National Electrical Code

LV

Ð

Low Voltage

REQ'D

Ð

Required

NOTES:

1.Clearances must be maintained to prevent recirculation of air from outdoor- fan discharge.

2.Adequate clearance around air openings into combustion chamber must be provided.

Fig. 5 Ð 588A048,060 With Optional Base Rail, Unit Dimensions

Ð5Ð

Page 5
Image 5
Bryant 589A, 588A user manual