Technical data

Preface

Dimensions / Weight

 

 

 

Rack (W x D x H)

482.6 mm (Bezel) / 444.8 mm (Body) x 770.0 mm x

 

176.0 mm

 

 

Mounting depth rack

728 mm

 

 

Height unit rack

4 U

 

 

19" rackmount

Yes

 

 

Mounting cable depth

100 mm (1000 mm rack recommended)

rack

 

 

 

Weight

min. 32 kg; max. 46 kg (actual weight may vary

 

depending on configuration)

 

 

Rack integration kit

rack integration kit as option

 

Rack integration kit is standard for the

 

Ijapanese market.

Ventilation clearance

At least 200 mm on the front and rear.

Ambient conditions

Environment class 3K2

EN 60721 / IEC 721 Part 3-3

Environment class 2K2

EN 60721 / IEC 721 Part 3-2

 

 

Temperature:

 

Operation (3K2)

10 °C .... 35 °C

Transport (2K2)

-25 °C .... 60 °C

 

 

Humidity

10% ... 85% (non condensing)

 

 

Condensation during operation must be avoided!

Noise level

Sound power level LWAd (ISO 9296)

< 6.2

B (standby)

 

< 6.6

B (operation)

 

 

Sound pressure level at bystander position LpAm

< 46 dB(A) (standby)

(ISO 9296) (at < 23 °C)

< 51 dB(A) (operation)

 

 

 