Hardware installation | Connecting the server to the mains |
AC source related power supply configuration and system load limits
The system configuration and load is limited by the number of AC mains power sources available as indicated in the following table.
Number | AC redundant systems | AC | |||
of power | (requires 2 AC sources) | (connected to 1 AC source) | |||
supply |
|
|
|
| |
Max. DC | Installation | Max. DC | Installation | ||
modules | |||||
loading to | requirements | loading for AC | requirements | ||
installed | |||||
support AC |
|
| |||
|
|
| |||
| redundancy |
| systems |
| |
|
|
|
|
| |
2 | 830W | 2 PSUs | 1580W | 2 PSUs | |
|
| connected to |
| connected to | |
|
| mains (1+1) |
| mains (1+1) | |
|
|
|
|
| |
3 | N/A | N/A | 2320W | 3 PSUs | |
|
|
|
| connected to | |
|
|
|
| mains (2+1) | |
|
|
|
|
| |
4 | 1580W | 2 PSUs | 2320W | 4 PSUs | |
|
| connected to |
| connected to | |
|
| mains |
| mains (3+1) | |
|
| 2 PSUs |
|
| |
|
| connected to |
|
| |
|
| an isolated AC |
|
| |
|
| source |
|
| |
|
| e.g. UPS (2+2) |
|
| |
|
|
|
|
|
Table 4: System power supply configuration and system load limits
Installation in PRIMECENTER/Datacenter rack
Please follow the installation requirements for connection to the mains described in the rack manuals.
RX600 S5 | Operating Manual | 57 |