Bryant 589A, 588A user manual

Models: 589A 588A

1 52
Download 52 pages 50.86 Kb
Page 3
Image 3
Manual background

REQ'D CLEARANCES FOR SERVICING. in. (mm)

Duct panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0

Unit top . . . . . . . . . . . . . . . . . . . . . . . . . . . 36 (914)

Side opposite ducts

.

. 36

(914)

Compressor access

.

. 36

(914)

(Except for NEC requirements)

 

 

 

REQ'D CLEARANCES TO COMBUSTIBLE MAT'L. in. (mm)

 

 

 

Maximum extension of overhangs . . . . . . . . . . . . . . . 48 (1219)

Unit top . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 (356)

Duct side of unit . . . . . . . . . . . . . . . . . . . . . . . . 2 (51)

Side opposite ducts

. . . . . . . 14 (356)

Bottom of unit

. .

. .

. . . . . . 0

Flue panel

. .

. .

.

. . 36 (914)

NEC REQ'D CLEARANCES. in. (mm)

 

 

 

 

Between units, control box side

. . . . . . 42 (1067)

Unit and ungrounded surfaces, control box side . .

. .

. .

.

. . 36 (914)

Unit and block or concrete walls and other grounded

 

 

 

 

surfaces, control box side

. .

. .

.

. 42 (1067)

UNIT

ELECTRICAL

UNIT WEIGHT

 

CORNER WEIGHT

 

UNIT HEIGHT

 

 

(lb/kg)

 

(in./mm)

588A

CHARACTERISTICS

 

 

 

 

 

lb

kg

A

B

 

C

D

E

 

 

 

018040

208/230-1-60

296

135

87/40

68/31

 

82/37

59/27

27.4/697

024040

208/230-1-60

327

149

103/47

49/22

 

129/59

46/21

27.4/697

024060

208/230-1-60

339

155

106/48

52/24

 

132/60

49/22

27.4/697

030040

208/230-1-60, 208/230-3-60

344

157

106/48

53/24

 

132/60

53/24

27.4/697

030060/080

208/230-1-60, 208/230-3-60

356

162

102/46

71/32

 

123/56

60/27

27.4/697

036060/080

208/230-1-60, 208/230-3-60, 460-3-60

360

164

92/42

82/37

 

117/53

69/31

27.4/697

036100/120

208/230-1-60, 208/230-3-60, 460-3-60

372

169

95/43

85/39

 

120/55

72/33

27.4/697

042060/080

208/230-1-60, 208/230-3-60, 460-3-60

399

181

101/46

92/42

 

125/57

81/37

31.4/798

042100/120

208/230-1-60, 208/230-3-60, 460-3-60

411

187

104/47

95/43

 

128/58

84/38

31.4/798

 

 

 

 

 

 

 

 

 

 

UNIT

F

G

CENTER OF GRAVITY in./mm

588A

in./mm

in./mm

X

 

Y

Z

018040

 

 

25.04/636

22.72/577

 

024040

 

 

26.90/683.3

20.17/512.3

 

024060

 

 

26.82/681.2

20.22/513.6

 

030040

197¤8/504.8

221¤4/565.4

26.57/674.9

20.1

/509.3

13.16/334.3

030060/080

 

 

26.93/684

21.1

/535.4

 

036060/080

 

 

27.31/693.7

21.0

/532.6

 

036100/120

 

 

27.23/691.6

21.0

/533.1

 

042060/080

237¤8/606.4

261¤4/666.8

26.87/682.5

21.0

/533.1

14.96/380

042100/120

26.81/681

21.0

/533.7

 

 

 

 

 

 

 

 

 

 

 

 

LEGEND

 

 

CG

Ð

Center of Gravity

MAT'L

Ð

Material

COND

Ð Condenser

NEC

Ð National Electrical Code

LV

Ð

Low Voltage

REQ'D

Ð

Required

NOTES:

1.Clearances must be maintained to prevent recirculation of air from outdoor- fan discharge.

2.Adequate clearance around air openings into combustion chamber must be provided.

Fig. 3 Ð 588A018-042 With Optional Base Rail, Unit Dimensions

Ð3Ð

Page 3
Image 3