Bryant 589A A Ð Superheat Charging Table, 588A018, B Ð Superheat Charging Table, 588A024

Models: 589A 588A

1 52
Download 52 pages 50.86 Kb
Page 36
Image 36

For Integrated Control Motors (ICM)

To con®gure the 589A unit, move the 5 Easy Select board wires to the terminals which control the air¯ow. Refer to the Easy Select interface board (Fig. 22) located next to the terminals and to Fig. 30 and 32.

Perform the following steps for basic system con®guration.

AUX HEAT RANGE (VIO) Ð The air¯ow for unit 589A is preset at the factory. The air¯ow selection must not be set at a setting lower than the default. Refer to Table 15 for air¯ow and gas heat input for terminals 1-4.

AC/HP SIZE (BLU) Ð The preset factory default selection for AC/HP SIZE (air conditioner/heat pump) is set to 400 cfm/ ton. The selection pins are con®gured for 350 cfm/ton and 400 cfm/ton.

TYPE (ORN) Ð The TYPE is a preset factory default selec- tion. The preset factory default setting is AC for the 589A units. Default setting should not be altered.

AC/HP CFM ADJUST (BLK) Ð The preset factory default selection is MED. Selections HI and LO will adjust the air- ¯ow supplied for all operational modes (see following table).

The selection options allow installer to adjust air¯ow to meet such individual needs as noise and static compensation, etc.

MODE

FAN ONLY

COOLING

HEATING

LO - Adjust

−15%

−10%

−10%

HI - Adjust

15%

10%

10%

AC/HP TIME DELAY (GRY) Ð Four motor operation delay options are provided to customize system operation. See table below:

OPTION

TERMINAL

DESCRIPTION

 

 

Used when it is desirable

30-Sec On/60-Sec

 

to allow system coils time

1

to heat up or cool down

Off Delay Pro®le

 

prior to air¯ow. Enhances

 

 

 

 

system efficiency.

 

 

Preset factory default setting for

 

 

589A. Used for servicing or

No Delay Option

2

when other components are

used to perform a delay func-

 

 

 

 

tion (e.g., integrated gas

 

 

control).

30-Sec Off Delay

3

Enhances system efficiency.

45-Sec Off Delay

4

Enhances system efficiency.

 

 

 

 

 

Table 8A Ð Superheat Charging Table, 588A018

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TEMP (F)

 

 

 

 

 

INDOOR AIR Ð CFM

 

 

 

 

 

OUTDOOR

 

 

 

 

 

 

 

600

 

 

 

 

 

 

ENTERING

 

 

 

 

 

Indoor Air Ð Ewb (F)

 

 

 

 

 

 

AIR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

54

56

58

60

62

 

64

 

66

 

68

70

72

74

76

 

 

 

 

 

 

65

 

SPH

17.3

18.5

19.6

20.8

24.2

 

27.7

 

28.5

 

29.3

29.3

29.3

29.3

29.3

70

 

SPH

13.8

14.9

16.1

17.3

20.7

 

24.1

 

25.7

 

27.3

27.3

27.3

27.3

27.3

75

 

SPH

10.2

11.4

12.5

13.7

17.1

 

20.6

 

22.9

 

25.2

25.2

25.2

25.2

25.2

80

 

SPH

8.2

8.8

9.5

10.2

13.6

 

17.0

 

20.1

 

23.1

23.9

24.1

25.4

26.1

85

 

SPH

6.1

6.2

6.5

6.6

10.0

 

13.5

 

17.3

 

21.1

22.6

24.1

25.6

27.1

90

 

SPH

*

*

*

5.0

8.1

 

11.4

 

15.2

 

19.0

20.5

22.0

23.5

25.0

95

 

SPH

*

*

*

*

6.2

 

9.4

 

13.2

 

17.0

18.5

20.0

21.5

23.0

100

 

SPH

*

*

*

*

*

 

7.3

 

11.1

 

14.9

17.2

19.5

21.7

24.0

105

 

SPH

*

*

*

*

*

 

5.3

 

9.1

 

12.9

15.9

18.9

21.9

24.9

110

 

SPH

*

*

*

*

*

 

*

 

6.7

 

10.8

13.8

16.8

19.8

22.8

115

 

SPH

*

*

*

*

*

 

*

 

*

 

8.8

11.8

14.8

17.8

20.8

LEGEND

*Do not attempt to charge system under these conditions Ð refrigerant

Ewb Ð Entering Wet Bulb

slugging may occur.

SPH Ð Superheat at Compressor (F)

 

 

 

 

 

 

Table 8B Ð Superheat Charging Table, 588A024

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TEMP (F)

 

 

 

 

 

INDOOR AIR Ð CFM

 

 

 

 

 

OUTDOOR

 

 

 

 

 

 

 

800

 

 

 

 

 

 

ENTERING

 

 

 

 

 

Indoor Air Ð Ewb (F)

 

 

 

 

 

 

AIR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

54

56

58

60

62

 

64

 

66

 

68

70

72

74

76

 

 

 

 

 

 

65

 

SPH

18.2

19.0

19.9

20.7

22.5

 

24.2

 

25.1

 

25.9

26.6

27.2

27.9

28.6

70

 

SPH

17.1

17.6

18.1

18.6

20.4

 

22.1

 

23.0

 

23.9

24.9

26.0

27.1

28.1

75

 

SPH

16.0

16.2

16.4

16.6

18.3

 

20.1

 

21.0

 

21.8

23.3

24.8

26.2

27.7

80

 

SPH

14.8

14.7

14.6

14.5

16.3

 

18.0

 

19.7

 

21.3

22.4

23.5

24.6

25.8

85

 

SPH

13.7

13.3

12.9

12.5

14.3

 

16.0

 

18.4

 

20.7

21.5

22.3

23.1

23.8

90

 

SPH

11.1

10.9

10.7

10.4

12.2

 

13.9

 

16.3

 

18.7

19.9

21.0

22.2

23.4

95

 

SPH

8.5

8.4

8.4

8.4

10.1

 

11.9

 

14.3

 

16.6

18.2

19.8

21.4

23.0

100

 

SPH

7.3

7.5

7.7

7.9

8.9

 

9.9

 

12.2

 

14.6

16.6

18.6

20.6

22.6

105

 

SPH

6.2

6.6

6.9

7.3

7.6

 

7.8

 

10.2

 

12.5

14.9

17.3

19.7

22.1

110

 

SPH

*

*

*

5.3

5.5

 

5.8

 

8.1

 

10.5

13.3

16.1

18.9

21.7

115

 

SPH

*

*

*

*

*

 

*

 

6.1

 

8.4

11.6

14.9

18.1

21.3

LEGEND

*Do not attempt to charge system under these conditions Ð refrigerant

Ewb Ð Entering Wet Bulb

slugging may occur.

SPH Ð Superheat at Compressor (F)

 

Ð36Ð

Page 36
Image 36
Bryant 589A user manual A Ð Superheat Charging Table, 588A018, B Ð Superheat Charging Table, 588A024