Most common motor failures are due to either an open, grounded, or short circuit. Directions below are specifically for single-phase units, however, they also apply to 3-phase compressors. When a single-phase compressor fails to start or run, 3 tests can help determine the problem. First, all possible external causes should be eliminated, such as overloads, improper voltage, pressure equal- ization, defective capacitor(s), relays, wiring, and so forth. Com- pressor has internal line-break overload, so be certain it is closed.

OPEN CIRCUIT

To determine if any winding has a break in the internal wires and current is unable to pass through:

1.Be sure all power is off.

2.Discharge all capacitors.

3.Remove wires from terminals C, S and R.

4.Check resistance from C-R, C-S and R-S using an ohmme- ter on 0-1000 ohm scale.

Because winding resistances are usually less than 10 ohms, each reading appears to be approximately 0 ohm. If resistance remains at 1000 ohms, an open or break exists, and compressor should be replaced.

CAUTION: Be sure internal line-break overload is not temporarily open.

GROUND CIRCUIT

To determine if a wire has broken or come in direct contact with shell, causing a direct short to ground:

1.Be sure all power is off.

2.Discharge all capacitors.

3.Remove wires from terminals C, S, and R.

4.On hermetic compressors, allow crankcase heaters to re- main on for several hours before checking motor to ensure windings are not saturated with refrigerant.

5.Use an ohmmeter on R X 10,000 ohm scale. A megohm- meter may be used in place of ohmmeter. Follow manufac- turer’s instructions.

6.Place 1 meter probe on ground or on compressor shell. Make a good metal-to-metal contact. Place other probe on terminals C, S, and R in sequence.

7.Note meter scale.

8.If reading of zero or low resistance is obtained, motor is grounded. Replace compressor.

A 1 ton or less capacity compressor is probably grounded if resistance is below 1 million ohms. On larger-sized, single-phase compressors, resistance to ground should not be less than 1000 ohms per volt of operating voltage.

Example:

230 volts X 1000 ohms/volt = 230,000 ohms minimum.

SHORT CIRCUIT

To determine if any wires within windings have broken through their insulation and made contact with other wires, thereby shorting all or part of the winding(s), be sure the following conditions are met:

1.Correct motor-winding resistances must be known before testing, either from previous readings or from manufactur- er’s specifications.

2.Temperature of windings must be as specified, usually about 70°F.

3.Resistance-measuring instrument must have an accuracy within ± 5 to 10 percent. This requires an accurate ohmme- ter, such as a Wheatstone bridge or null balance-type instrument.

—27—

4.Motor must be dry or free from direct contact with liquid refrigerant.

MAKE THIS CRITICAL TEST

(Not advisable unless above conditions are met.)

1.Be sure all power is off.

2.Discharge all capacitors.

3.Remove wires from terminals C, S, and R.

4.Place instrument probes together and determine probe and lead wire resistance.

5.Check resistance readings from C-R, C-S, and R-S.

6.Subtract instrument probe and lead resistance from each reading.

If any reading is within ± 20 percent of known resistance, motor is probably normal. Usually a considerable difference in reading is noted if a turn-to-turn short is present.

III. SYSTEM CLEANUP AFTER BURNOUT

CAUTION: Turn off all power to unit before proceed- ing. Wear safety glasses and gloves when handling refrigerants. Acids formed as a result of motor burnout can cause burns.

NOTE: To analyze level of suspected contamination from com- pressor burnout, use Total Test. See your distributor/branch.

Some compressor electrical failures can cause motor to overheat. When this occurs, by-products, which include sludge, carbon, and acids, can contaminate system. If burnout is severe enough, system must be cleaned before replacement compressor is installed. The 2 types of motor burnout are classified as mild or severe.

In mild burnout, there is little or no detectable odor. Compressor oil is clear or slightly discolored. An acid test of compressor oil will be negative. This type of failure is treated the same as mechanical failure. Liquid-line strainer should be removed and liquid-line filter drier installed.

In a severe burnout, there is a strong, pungent, rotten-egg odor. Compressor oil is very dark. Evidence of burning may be present in tubing connected to compressor. An acid test of compressor oil will be positive. Complete system must be reverse flushed with refrigerant. Check-Flo-Rater™ or TXV must be cleaned or re- placed. In a heat pump, accumulator and reversing valve are replaced. These components are also removed and bypassed during reverse-flushing procedure. Remove and discard liquid-line strainer. After system is reassembled, install liquid-line and suction-line filter driers. Run system for 2 hrs. Discard both driers and install new liquid-line drier only.

IV. COMPRESSOR REMOVAL AND REPLACEMENT

Once it is determined that compressor has failed and the reason established, compressor must be replaced.

CAUTION: Wear safety glasses and gloves when han- dling refrigerants and when using brazing torch.

1.Shut off all power to unit.

2.Remove and recover all refrigerant from system until pressure gages read zero psi. Use all service ports.

3.Disconnect electrical leads from compressor. Disconnect or remove crankcase heater and remove compressor-holddown bolts.

4.Cut compressor from system with tubing cutters. Do not use brazing torch for compressor removal. Oil vapor may ignite when compressor is disconnected.

Page 27
Image 27
Bryant R-22 service manual III. System Cleanup After Burnout, IV. Compressor Removal and Replacement

R-22 specifications

The Bryant R-22 stands out in the landscape of residential heating and cooling systems with its combination of efficiency, durability, and modern technology. Designed primarily for homeowners seeking comfortable climate control solutions, the R-22 model delivers consistent performance throughout varying seasonal extremes.

One of the main features of the Bryant R-22 is its high energy efficiency. Rated with a SEER (Seasonal Energy Efficiency Ratio) that meets or exceeds industry standards, this air conditioning unit is designed to reduce energy consumption while providing optimal cooling. This not only helps in lowering monthly utility bills but also promotes environmentally responsible usage.

Another notable characteristic is the unit's durability. Constructed with a robust cabinet and high-quality components, the R-22 is built to withstand the rigors of daily use, with protective features that enhance its longevity. The cabinet comes with a powder-coated finish that resists corrosion and harsh weather conditions, ensuring that the unit stays functional and aesthetically pleasing for years.

The Bryant R-22 also incorporates advanced technology to improve user experience. One such innovation is the SmartSet technology, which allows homeowners to program their unit to optimize comfort levels according to their specific needs. This programmable capability enhances energy savings and ensures that the home remains at the desired temperature when residents are present.

Moreover, the unit features a Quiet Operating System that significantly reduces noise levels, making it suitable for residential areas where noise might be a concern. The design minimizes vibrations and optimizes airflow, creating a comfortable environment without disruptive sounds.

For added convenience, the Bryant R-22 is compatible with various thermostat options, including Wi-Fi-enabled models. This allows users to control their home's climate from anywhere using a smartphone app, facilitating effortless adjustments and monitoring of energy usage.

Finally, the Bryant R-22 is backed by a solid warranty, providing peace of mind for homeowners. This commitment to quality and customer satisfaction is a testament to Bryant’s dedication to producing reliable and efficient HVAC solutions. Overall, the Bryant R-22 is an exemplary choice for those looking to enhance their home comfort with the latest in HVAC technology.