Bryant R-22 service manual ServiceValves, Iv. Service Valves

Models: R-22

1 52
Download 52 pages 54.32 Kb
Page 38
Image 38
Fig. 44—Service Valves

 

SERVICE PORT

 

STEM

W/SCHRADER

FIELD

 

CORE

 

 

SIDE

 

 

STEM

 

 

SERVICE PORT

 

 

W/SCHRADER CORE

 

FIELD

 

 

SIDE

 

SEAT

 

 

 

 

SEAT

BAR STOCK FRONT SEATING VALVE

FORGED FRONT SEATING VALVE

A91447

A91448

Fig. 44—Service Valves

b. Remove all flux residue with brush and water while material is still hot.

2.Use sil-fosor phos-copperfor copper-to-copper only. No flux is required.

3.Silver solder is used on copper-to-brass, copper-to-steel, or copper-to-copper. Flux is required when using silver solder.

4.Fluxes should be used carefully. Avoid excessive applica- tion and do not allow fluxes to enter into the system.

5.Proper brazing temperature of copper is when it is heated to a dull red color.

This section on brazing is not intended to teach a technician how to braze. There are books and classes that teach and refine brazing techniques. The basic points above are listed only as a reminder.

IV. SERVICE VALVES

WARNING: Never attempt to make repairs to existing service valves. Unit operates under high pressure. Dam- aged seats and o-rings should not be replaced. Replace- ment of entire service valve is required. Tampering with damaged valves can cause personal injury or death. Service valve must be replaced by properly trained service technician.

Service valves provide a means for holding original factory charge in outdoor unit prior to hookup to indoor coil. They also contain gage ports for measuring system pressures and provide shutoff convenience for certain types of repairs. (See Fig. 44.)

Two types of service valves are used in outdoor residential equipment. The first type is a front-seating valve, which has a service port that contains a Schrader fitting. The service port is always pressurized after the valve is moved off the front-seat position.

The second type is a combination front-seating/back-seating valve, which has a metal-to-metal seat in both the open and closed positions. When it is fully back-seated, the service port is not

—38—

pressurized. To pressurize the service port, this valve must be moved off the back-seating position. This valve does not contain a Schrader fitting. Both types of service valves are designed for sweat connection to the field tubing.

The service valves in the outdoor unit come from the factory front-seated. This means that the refrigerant charge is isolated from the line-set connection ports. Some heat pumps are shipped with sweat-adapter tube. This tube must be installed on the liquid- service valve. After connecting the sweat adapter to the liquid- service valve of a heat pump, the valves are ready for brazing. The interconnecting tubing (line set) can be brazed to the service valves using either silver-bearing or non-silver-bearing brazing material. Consult local codes.

Before brazing the line set to the valves, the belled ends of the sweat connections on the service valves must be cleaned so that no brass plating remains on either the inside or outside of the bell joint. To prevent damage to the valve and/or cap Oring, use a wet cloth or other acceptable heat-sinking material on the valve before brazing. To prevent damage to the unit, use a metal barrier between brazing area and unit.

After the brazing operation and the refrigerant tubing and evapo- rator coil have been evacuated, the valve stem can be turned counterclockwise until it opens or back-seats, which releases refrigerant into tubing and evaporator coil. The system can now be operated.

Back-seating service valves must be back-seated (turned counter- clockwise until seated) before the service-port caps can be re- moved and hoses of gage manifold connected. In this position, refrigerant has access from and through outdoor and indoor unit. The service valve-stem cap is tightened to 20 ± 2 ft/lb torque and the service-port caps to 9 ± 2 ft/lb torque. The seating surface of the valve stem has a knife-set edge against which the caps are tightened to attain a metal-to-metal seal. If accessory pressure switches are used, the service valve must be cracked. Then, the knife-set stem cap becomes the primary seal.

The service valve cannot be field-repaired; therefore, only a complete valve or valve stem and service-port caps are available for replacement.

Page 38
Image 38
Bryant R-22 service manual ServiceValves, Iv. Service Valves