| T2 C |
| C |
| O |
O | DFT |
R | T1 |
W |
|
2
Y |
|
|
|
|
|
|
C | Y |
|
|
|
|
|
SPEEDUP | P1 |
|
|
|
|
|
J1 | P3 | 90 INTERVALTIMER | 60 30 | 30 60 | 120 | |
| DFT |
| OFF | QUIET SHIFT | ON | |
| Speedup |
|
|
| Quiet | |
| Pins |
|
|
| Shift |
OF2
Defrost interval
DIP switches
Fig.
OF1
A99442
either heating or cooling. This enables owner to obtain timely
The service alarm is an accessory device. Service alarm locks out compressor under certain adverse operating conditions. System is manually reset by shutting it off at thermostat subbase, then turning it back on. If adverse condition is corrected, system restarts.
One example of an adverse condition would be a system located in a desert climate where high operating temperatures may cause system to shut down on the
Connect service alarm to
Connect all field
Refer to Fig. 25 or 26 for wiring connections for service alarm or service alarm with
NOTE: The wire from the X terminal on the service alarm to L on the outdoor terminal board, indoor terminal board, and thermostat subbase is
Service alarm requires 2 inputs.
1.It must sense a 24v input from thermostat. As thermostat calls for heating or cooling, it supplies 24v to
2.A current transformer (or induction loop) similar to a
NOTE: On a
WARNING: If service alarm needs replacing, shut off all power to unit before attempting removal. Electrical shock can cause personal injury or death.
Troubleshooting
To check for correct operation, shut off circuit breaker or discon- nect switch to outdoor unit while it is running. Signal light on thermostat should light. If this does not occur, check for wiring errors or replace the service alarm.
XII. OUTDOOR THERMOSTAT(S)
The outdoor thermostat(s) is installed in the control box. The sensing bulb(s) remain in the control box. Outdoor thermostat brings on stages of electric heat as outdoor temperature and