|
|
|
| PISTON BODY |
| PISTON | FEEDER |
|
|
| TUBES |
|
| |
(ORIENT AS SHOWN) |
|
| ||
|
|
| ||
BRASS | STRAINER |
|
| PISTON |
HEX NUT |
|
|
|
|
|
|
|
| PISTON RETAINER |
PISTON |
| TEFLON | BRASS | FLARE ADAPTER |
|
| |||
| SEAL |
| ||
RETAINER |
| HEX |
| |
|
|
| ||
|
|
| BODY | INTERNAL STRAINER |
A91138
PRODUCTION EXCEPT 1992
Fig. 45—Check-Flo-Rater™ Components
A94004
If the service valve is to be replaced, a metal barrier must be inserted between the valve and the unit to prevent damaging the unit exterior from the heat of the brazing operations.
CAUTION: Wear safety glasses and gloves when han- dling refrigerants.
Pumpdown Procedure
Service valves provide a convenient shutoff valve useful for certain
1.Attach pressure gage to suction
2.Front seat
3.Start unit in cooling mode. Run until suction pressure reaches 5 psig (35kPa). Do not allow compressor to pump to a vacuum.
4.Shut unit off. Front seat suction valve.
NOTE: All outdoor unit coils will hold only
V.
RELIANT PRODUCTS EXCEPT 1992 PRODUCTION
1.Shut off power to unit.
2.Pump unit down using pumpdown procedure described in this service manual.
3.Loosen nut and remove
4.Pull retainer out of body, being careful not to scratch
5.Slide piston out by inserting a small, soft wire with small kinks through metering hole. Do not damage metering hole, sealing surface around piston cones, or fluted portion of piston.
6.Clean piston
7.Install a new retainer
RELIANT AND CUBE PRODUCTS PRODUCED IN 1992
1.Shut off power to unit.
2.Reclaim
3.Loosen brass hex nut and remove line from brass hex body.
4.Slide piston out by inserting a small, soft wire with small kinks through metering hole. Do not damage metering hole, sealing surface around piston cones, or fluted portion of piston.
5.Clean piston
6.Always replace Teflon seal with new seal. Never try to reuse old seals.
7.Reassemble brass nut and brass hex body. Be sure orienta- tion is as shown in Fig. 45.
VI. REVERSING VALVE
In heat pumps, changeover between heating and cooling modes is accomplished with a valve that reverses flow of refrigerant in system. (See Fig. 46.) This
The sound made by a reversing valve as it begins or ends defrost is a ″ whooshing″ sound, as the valve reverses and pressures in system equalize. An experienced service technician detects this sound and uses it as a valuable troubleshooting tool.
Using a remote measuring device, check inlet and outlet line temperatures. DO NOT touch lines. If reversing valve is operating normally, inlet and outlet temperatures on appropriate lines should be close. Any difference would be due to heat loss or gain across valve body. Temperatures are best checked with a