|
|
| 1 |
|
| C - TRANSFORMER COMMON |
| ||
|
|
|
|
|
| ||||
|
|
|
|
| |||||
|
|
| 2 |
|
| R - TRANSFORMER LINE |
| ||
|
|
|
|
|
| ||||
|
|
|
|
| |||||
|
|
| 3 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
| 4 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
| 5 |
|
| W2 - FIRST STAGE AUXILIARY HEAT |
| ||
|
|
|
|
|
| ||||
|
|
|
|
| |||||
|
|
| 6 |
|
| O - REVERSING VALVE |
| ||
|
|
|
|
|
| ||||
|
|
|
|
| |||||
|
|
| 7 |
|
| Y2 - SECOND STAGE COOLING/HEAT PUMP | |||
|
|
|
|
| |||||
|
|
|
| ||||||
|
|
| 8 |
|
| Y1 - FIRST STAGE COOLING/HEAT PUMP |
| ||
|
|
|
|
|
| ||||
|
|
|
|
| |||||
|
|
| 9 |
|
| W3 - SECOND STAGE AUXILIARY HEAT |
| ||
|
|
|
|
|
| ||||
|
|
|
|
| |||||
|
|
| 10 |
|
| L - MALFUNCTION LIGHT |
| ||
|
|
|
|
| |||||
|
|
| 11 |
|
| 4 - TON | IF NO JUMPER IS |
| |
|
|
|
|
|
| ||||
|
|
|
|
| |||||
|
|
| 12 |
|
|
| |||
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
| INSTALLED, DEFAULT |
| |
|
|
| 13 |
|
|
|
|
| |
|
|
|
|
|
|
|
| ||
|
|
|
|
| 5 - TON | IS 3 - TON |
| ||
|
|
|
|
| |||||
|
|
| 14 |
|
|
|
| ||
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
| ||
|
|
| 15 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
| ||
|
|
| 16 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
| ||
|
|
| 17 |
|
| JUMPER FOR |
|
| |
|
|
|
|
|
|
| |||
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
| ||
|
|
| 18 |
|
| HEAT PUMP ONLY | A93576 | ||
|
|
|
|
| |||||
|
|
|
| ||||||
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
| |
|
|
|
| Fig. |
| ||||
T3 | T8 |
| T7 | T2 |
| T1 |
EXTERNAL MAIN
MAIN WINDING
4 POLE START
| 2 POLE START |
HIGH SPEED | LOW SPEED |
(L1) T1 + T7 | (L1) T1 |
(L2) T2 + T3 | (L2) T7 + T8 |
A92015
Fig. 38—Energizing Windings
TABLE
WINDING | 3 TON | 4 TON | 5 TON |
0.80 | 0.70 | 0.60 | |
3.20 | 2.20 | 1.80 | |
1.30 | 1.00 | 1.00 | |
3.10 | 2.20 | 2.00 | |
|
|
|
|
pressures exceeds 500 psi. The compressor is also protected by 3 PTC devices attached to the motor windings. The PTC’s resistance is sensed by the
MECHANICALLY INTERLOCKED CONTACTORS
The
The
TEMPERATURE THERMISTORS
Thermistors are electronic devices which sense temperature. As the temperature increases, the resistance decreases. Two ther- mistors are used to sense temperature: one senses outdoor ambient, and the other senses coil temperature (heat pump only). Refer to Fig. 39 for resistance values versus temperature.
If the outdoor ambient thermistor should fail, a malfunction signal appears on the indoor thermostat and
THERMISTOR CURVE
| 90 | |
(KOHMS) | 80 | |
70 | ||
| ||
| 60 | |
RESISTANCE | 50 | |
20 | ||
| 40 | |
| 30 |
10
0
0 | 20 | 40 | 60 | 80 | 100 | 120 |
TEMPERATURE (DEG. F)
A91431
Fig. 39—Resistance Values Versus Temperature
If the outdoor coil thermistor should fail, a malfunction signal appears on the indoor thermostat and
V. LED FUNCTION/MALFUNCTION LIGHTS
The
NOTE: Only malfunction signal appears at thermostat. Both function and malfunction signals appear at control board. (See Fig. 33 for LED location.) Table 15 provides the function/malfunction code, location, and definition.
VI. TROUBLESHOOTING
NOTE: Troubleshooting charts for air conditioning and heat pump units are provided in the back of this manual — see Fig. 52, 53, and 54.
COMPRESSOR WINDING CHECK
The