![Fig. 42—Heat Pump Refrigerant-Flow Diagrams](/images/new-backgrounds/33356/3335673x1.webp)
| COOLING CYCLE |
| |
| REVERSING VALVE | ||
|
| (ENERGIZED) | |
| OUTDOOR FAN |
| |
INDOOR | INDOOR COIL |
| |
FAN |
|
| |
| ACCUMULATOR |
| |
| SUCTION SERVICE |
| |
| PORT AT SERVICE |
| |
| VALVE (CLG CYCLE) | COMP | |
|
| ||
|
| STRAINER | |
STRAINER |
| OUTDOOR | |
| COIL | ||
|
| ||
(METERING) | SUCTION | LIQUID LINE | |
SERVICE | PRESSURE SWITCH | ||
|
| PORT | |
HEAT PUMP | (BYPASSING) | |
| ||
ACCESSORY | LIQUID LINE SERVICE PORT | |
FILTER DRIER | ||
AT SERVICE VALVE (CLG CYCLE) | ||
(DUAL FLOW) | ||
|
A88400
Fig. 42—Heat Pump Refrigerant-Flow Diagrams
CAUTION: Due to the high pressure of nitrogen, it should never be used without a pressure regulator on the tank.
Leaks in a system pressurized with refrigerant can be spotted with a leak detector that detects extremely small refrigerant leaks. This discussion assumes that system is pressurized with either all refrigerant or a mixture of nitrogen and refrigerant.
If system has been operating for some time, make first check for a leak visually. Since refrigerant carries a small quantity of oil, traces of oil at any joint or connection are an indication that refrigerant is leaking at that point.
A simple and inexpensive method of testing for leaks is to use soap bubbles. Any solution of water and soap may be used. Soap solution is applied to all joints and connections in system. A small pinhole leak is located by tracing bubbles in soap solution around leak.
Use electronic leak detector to check for leaks. This unquestion- ably is the most efficient and easiest method for checking leaks. There are various types of electronic leak detectors. Generally speaking, they are all portable, and most are lightweight, consist- ing of a box with several switches and a probe or sniffer. Detector is turned on and probe is passed around all fittings and connections in system. Leak is detected by either a movement of a pointer on detector dial, by a buzzing sound, or a light.
In all instances, when a leak is found, system charge must be bled down and leak repaired before final charging and operation. After leak testing or leak is repaired, evacuate system, and recharge with correct refrigerant charge.
A88401
Fig. 43—Leak Detector
III. BRAZING
When brazing is required in the refrigeration system, certain basics should be followed:
1.Clean joints make the best joints. To clean:
a.Remove all oxidation from surfaces to a shiny finish before brazing.
TABLE 19—24V PIN CONNECTION TROUBLESHOOTING
MODE OF OPERATION | TERMINAL | LOCATION ON | VOLTAGE | VOLTAGE | POSSIBLE SOURCE | |
DESIGNATION | CONTROL BOARD | PATH | REQUIRED | OF PROBLEM | ||
All | Input | 24 | Check transformer (secondary) | |||
Input | 24 | Check thermostat | ||||
Y1, Y2, | Input | 24 | Check thermostat | |||
Input | 24 | Check thermostat | ||||
| Input | 24 | Check thermostat | |||
|
|
|
|
| ||
Output | 24 | Outdoor temperature below | ||||
| speed; change temperature | |||||
|
|
|
|
| ||
| Input | 24 | Check thermostat | |||
Defrost |
|
|
|
|
| |
Y2, W2, | Output | 24 | Outdoor temperature below 50°F; | |||
| Coil temperature less than 30°F | |||||
|
|
|
|
| ||
Second Stage of | Y1, | Input | 24 | Check thermostat | ||
Auxiliary Heat | W3, | Output | 24 | Check | ||
|
|
|
|
|
| |
Cooling Second- | Y1, Y2, | Input | 24 | Ambient thermistor failure; | ||
stage Latching | Check | |||||
|
|
|
|