The outdoor Integral Control Motor (ECM), is a
The PWM signal is created by turning a DC signal on and off once within a given period of time. The signal on time relative to the signal total period defines the percent of the PWM. For example, if the period is 5 sec and the control power is turned on for 1 sec then off, the signal will remain off for 4 sec before turning on again to start the next cycle. The PWM is called a 20 percent duty cycle signal. If the on time is increased to 4 sec of the 5 sec period, the PWM is called an 80 percent duty cycle. The ECM reads the PWM signal and increases the motor speed linearly from minimum speed to maximum speed with the percent duty cycle value of the supplied PWM signal.
Outdoor Fan Motor Operation
There are two different types of motors used in the Evolution
On 289B models, an ECM fan motor is used to achieve higher efficiency ratings of the system. The outdoor unit control energizes outdoor fan anytime compressor is operating, except for defrost or
On 286B/187B models, the outdoor fan motor is a PSC type. A fan relay on the control board turns the fan off and on by opening and closing a high voltage circuit to the motor. It does not change speeds between low and high stage operation.
On 289B/180B models, the outdoor fan is an ECM type. The motor control is continuously powered with high voltage. The motor speed is determined by electrical pulses provided by the PWM outputs on the control board. The ECM motor RPM adjusts to outdoor conditions as described in Table 19. The PWM output can be measured with a volt meter set to DC volts.
In low ambient cooling (below 55°F/12.7°C), the control board cycles the fan off and on.
Table 19—Outdoor Fan Motor PWM
Outdoor Temp (DC volts, Tolerance +/- 2%)
|
| Low Stage |
| High Stage | Low & High | |
Model |
|
|
| Stage | ||
(OAT≤104_F / 40_C) |
| (OAT≤104_F / 40_C) |
| |||
|
| (OAT>104_F / 40_C) | ||||
|
|
|
|
| ||
|
|
|
|
|
|
|
289BNA036 |
| 9.06 |
| 10.23 |
| 11.90 |
|
|
|
|
|
|
|
289BNA048 |
| 9.91 |
| 11.04 |
| 11.90 |
|
|
|
|
|
|
|
289BNA060 |
| 10.83 |
| 11.70 |
| 11.90 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
180BNA024 |
| 9.57 |
| 10.88 |
| 11.90 |
180BNA036 |
| 9.06 |
| 10.23 |
| 11.90 |
180BNA048 |
| 9.91 |
| 11.04 |
| 11.90 |
180BNA060 |
| 10.83 |
| 11.70 |
| 11.90 |
NOTE: For 289B models in | ambient cooling, the PWM output for | |||||
both high |
operation below 55_F (12.8_C).
ECM Fan Motor Troubleshooting
If the outdoor fan motor fails to start and run:
SCheck the
SIf the 230vac is present, use Table 19 to check for proper control voltage output to the fan motor from the control board. The control board sends DC voltage signals to the motor through the terminals labeled PWM1 and PWM2 Set a voltmeter on a DC voltage scale and check across these terminals.
SFirst check voltage with the motor disconnected. If no control voltage is present, check
SIf voltage is present, reconnect the motor and check again. Shut down the unit to reconnect the motor and restart the unit to complete this troubleshooting procedure. If control voltage is no longer present or motor fails to respond, check motor connections.
SIf connections are good, replace the motor.
Time Delays
The unit time delays include:
SFive minute time delay to start cooling or heating operation when there is a call from the thermostat or user interface. To bypass this feature, momentarily short and release Forced Defrost pins.
SFive minute compressor
STwo minute time delay to return to standby operation from last valid communication (with Evolution only).
SOne minute time delay of outdoor fan at termination of cooling mode when outdoor ambient is greater than or equal to 100_F.
SFifteen second delay at termination of defrost before the auxiliary heat (W1) is
STwenty second delay at termination of defrost before the outdoor fan is energized.
SThirty second compressor delay when quiet shift enabled.
SOn 226A, 266A, 286B models there is a 1 minute time delay between staging from low to high and from high to low capacity. On 289B models there is no delay; the compressor will change from low to high and from high to low capacity “on the fly” to meet the demand.
Pressure Switches
The Puronr
The Puronr
60