Bryant R-22 Two-StageCompressor Resistances, Winding Resistance at 70_F±20_, Status Codes

Models: R-22

1 84
Download 84 pages 49.8 Kb
Page 65
Image 65

Table 20—Two-Stage Compressor Resistances

(Winding Resistance at 70_F±20_)

Winding

286BNA024

286BNA036

286BNA048

286BNA060

 

 

 

 

 

Start (S-C)

1.40

1.29

1.52

0.60

 

 

 

 

 

Run (R-C)

1.32

0.89

0.64

0.49

 

 

 

 

 

Status Codes

Table 21 shows the status codes flashed by the amber status light. Most system problems can be diagnosed by reading the status code as flashed by the amber status light on the control board.

The codes are flashed by a series of short and long flashes of the status light. The short flashes indicate the first digit in the status code, followed by long flashes indicating the second digit of the error code.

The short flash is 0.25 seconds ON and the long flash is 1.0 second ON. Time between flashes is 0.25 seconds. Time between short flash and first long flash is 1.0 second. Time between code repeating is 2.5 seconds with LED OFF.

EXAMPLE:

3 short flashes followed by 2 long flashes indicates a 32 code. Table 21 shows this to be low pressure switch open.

 

Table 21—TROUBLESHOOTING

 

 

 

 

 

 

AMBER

 

OPERATION

FAULT

LED

POSSIBLE CAUSE AND ACTION

FLASH

 

 

 

 

 

CODE

 

 

 

 

 

Standby – no call for unit operation

None

On solid,

Normal operation

no flash

 

 

 

 

 

 

 

Low Stage Cool/Heat Operation

None

1, pause

Normal operation

 

 

 

 

High Stage Cool/Heat Operation

None

2, pause

Normal operation

 

System Commu-

16

Communication with User Interface lost. Check wiring to UI, indoor and

 

nications Failure

outdoor units

 

 

 

 

 

 

 

Invalid Model Plug

25

Control does not detect a model plug or detects an invalid model plug. Unit

 

will not operate without correct model plug.

 

 

 

 

 

 

 

 

High Pressure

31*

High ---pressure switch trip. Check refrigerant charge, outdoor fan operation

 

Switch Open

and coils for airflow restrictions.

 

 

 

 

 

 

 

Low Pressure

32*

Low---pressure switch trip. Check refrigerant charge and indoor air flow.

 

Switch Open

 

 

 

 

 

 

 

 

Control Fault

45

Outdoor unit control board has failed. Control board needs to be replaced.

 

 

 

 

 

Brown Out (230v)

46

Line voltage < 187v for at least 4 seconds. Compressor and fan operation

 

not allowed until voltage>190v. Verify line voltage.

 

 

 

 

 

 

 

 

No 230v at Unit

 

There is no 230v at the contactor when indoor unit is powered and cooling/

 

Measured at L1

 

 

47

heating demand exists. Verify the disconnect is closed and 230v wiring is

 

and L2 on circuit

 

 

connected to the unit.

 

board

 

 

 

 

 

 

 

 

 

Outdoor Air Temp

53

Outdoor air sensor not reading or out of range. Ohm out sensor and check

 

Sensor Fault

wiring.

 

 

 

 

 

 

 

Outdoor Coil

55

Coil sensor not reading or out of range. Ohm out sensor and check wiring.

 

Sensor Fault

 

 

 

 

 

 

 

 

Thermistors out of

56

Improper relationship between coil sensor and outdoor air sensor. Ohm out

 

range

sensors and check wiring.

 

 

 

 

 

 

 

Low Stage

 

Compressor operation detected then disappears while low stage demand

 

71*

exists. Possible causes are internal compressor overload trip or start relay

 

Thermal Cutout

 

 

and capacitor held in circuit too long (if installed).

 

 

 

 

 

 

 

 

High Stage

 

Compressor operation detected then disappears while high stage demand

 

72*

exists. Possible causes are internal compressor overload trip or start relay

 

Thermal Cutout

 

 

and capacitor held in circuit too long (if installed).

 

 

 

 

 

 

 

 

Contactor Shorted

73*

Compressor voltage sensed when no demand for compressor operation

 

exists. Contactor may be stuck closed or there is a wiring error.

 

 

 

 

 

 

 

 

No 230V at

 

Compressor voltage not sensed when compressor should be starting. Con-

 

Compressor (289B

74

 

tactor may be stuck open or there is a wiring error.

 

Only)

 

 

 

 

 

 

 

 

 

Low Stage

81

Thermal cutout occurs in three consecutive low/high stage cycles. Low

 

Thermal Lockout

stage locked out for 4 hours or until 24v power recycled.

 

 

 

 

 

 

 

High Stage

82

Thermal cutout occurs in three consecutive high/low stage cycles. High

 

Thermal Lockout

stage locked out for 4 hours or until 24v power recycled.

 

 

 

 

 

 

 

Low---Pressure

83

Low pressure switch trip has occurred during 3 consecutive cycles. Unit

 

Lockout

operation locked out for 4 hours or until 24v power recycled.

 

 

 

 

 

 

 

High ---Pressure

84

High pressure switch trip has occurred during 3 consecutive cycles. Unit

 

Lockout

operation locked out for 4 hours or until 24v power recycled.

 

 

 

 

 

 

*Sequence: Compressor contactor is de---energized and outdoor fan is energized for up to 15 minutes. If demand still exists, control will energize compressor contactor after 15 minute delay. If fault is cleared, unit will resume operation. If fault still exists, fan shuts off, and error code continues to flash. Control will attempt re---start every 15 minutes. Cycling low voltage defeats the 15 minute delay.

65

Page 65