Burnham 1100-H4 manual Vent System Components Included with Boiler, Vent/Air Intake Length

Models: 1100-H4

1 96
Download 96 pages 6.14 Kb
Page 9
Image 9

Table 2: Vent System Components Included with Boiler

Vent System Components

Part Number

 

 

Gasketed Vent Terminal 3” Horizontal

8110701

(SCG-3 thru SCG-7)

 

Gasketed Vent Terminal 4” Horizontal

8110702

(SCG-8 & SCG 9)

 

Disc Air Intake - 3”

6116045

(SCG-3 & SCG-4)

 

Disc Air Intake - 4”

6116044

(SCG-5 & SCG-6)

 

Air Intake - 5”

6116063

(SCG-7 thru SCG-9)

 

Table 3: Burnham Vent System and Air Intake System Components

Vent System Component

Part Number

Equivalent

Feet of Pipe

 

 

3” Dia. Pipe x 1 Ft

8116296U

1

4” Dia. Pipe x 1 Ft

100176-01

 

3” Dia. Pipe x 3 Ft

8116298U

3

 

 

4” Dia. Pipe x 3 Ft

100177-01

 

 

 

 

3” Dia. Pipe x 5 Ft

8116300U

5

 

 

4” Dia. Pipe x 5 Ft

100178-01

 

 

 

 

3” Dia. Pipe x Adjustable

8116319U

Equal to

 

 

Installed Length

4” Dia. Pipe x Adjustable

100179-01

(1.06 TO 1.64)

3” Dia. 90° Elbow

8116294U

5

4” Dia. 90° Elbow

100180-01

 

3” Dia. 45° Elbow

8116292U

5

4” Dia. 45° Elbow

100181-01

 

 

 

 

3” Dia. Horizontal Drain Tee

8116302U

2

 

 

4” Dia. Horizontal Drain Tee

100182-01

 

 

 

 

3” Dia. Vertical Drain Tee

8116304U

 

 

4” Dia. Vertical Drain Tee

100183-01

 

 

 

 

3” Single Wall Thimble

8116116

---

4” Single Wall Thimble

100184-01

 

3” Double Wall Thimble

8116115

---

4” Double Wall Thimble

100185-01

 

Intake System Components

Equivalent

(Parts by Others)

Feet of Pipe *

 

 

3”, 4”, or 5” ID Pipe x 1 Ft

1

3”, 4”, or 5” ID Pipe x 2 Ft

2

3”, 4”, or 5” ID Pipe x 4 Ft

4

 

 

3”, 4”, or 5” ID Pipe x 5 Ft

5

 

 

3”, or 4” 90° Elbow

5

 

 

3”, or 4” 45° Elbow

5

 

 

5” 90° Elbow

6

 

 

5” 45° Elbow

6

*Equivalent Feet of Pipe Based on Standard 4” Smoke Pipe Design

Table 4: Vent/Air Intake Length

 

3” Air Intake Pipe

4” Air Intake Pipe

5” Air Intake Pipe

3” Vent Pipe

4” Vent Pipe

Model

(Equiv. Ft.)

(Equiv. Ft.)

(Equiv. Ft.)

(Equiv. Ft.)

(Equiv. Ft.)

 

Min.

Max.

Min.

Max.

Min.

Max.

Min.

Max.

Min.

Max.

SCG-3 & SCG-4

8

50

---

---

---

---

8

50

---

---

SCG-5 & SCG-6

---

---

8

50

---

---

8

50

---

---

SCG-7

---

---

---

---

8

50

8

50

---

---

SCG-8 & SCG-9

---

---

---

---

8

40

---

---

8

40

Page 9