H.Operating Instructions.

1.Follow Operating Instructions to place boiler in operation. See Figure 36.

2.Electronic Ignition Modules with LED indicators. Table 10 cross-references the ignition module terminal designations to the ignition terminal

numbers in the wiring ladder diagrams. The yellow LED indicates the status of the flame, see Table 11. The green LED indicates the status of the system, see Table 12. See Figure 37 for LED locations. See Figure 38 for Troubleshooting Guide.

TABLE 10: IGNITION MODULE TERMINAL

CROSS-REFERENCE

 

Ignition Module

Wiring Ladder Diagram

 

Terminal Designation

Terminal Number

 

MV

1

 

 

 

 

MV/PV

2

 

PV

3

 

GND

4

 

 

 

 

24V (GND)

5

 

 

 

 

24V

6

 

 

 

Figure 37: LED Locations

SPARK

9

TABLE 11: yellow led flame codes

Yellow LED

Indicates

Recommended Service Action

Flash Codea

 

 

 

Heartbeat

Normal Flame Signal

N/A

 

 

 

 

Weak Flame Signal -

 

 

System will operate reliably but flame signal is

 

2

less than desired.

Perform routine maintenance to

Note: This indication may flash temporarily

assure optimum flame signal.

 

 

during or shortly after lightoff on some appli-

 

 

cations.

 

 

Marginal Flame Signal (less than 1.1 µA) -

 

 

System may not operate reliably over time.

Check gas supply, pilot burner, flame

 

Service call recommended.

1

sense wiring, contamination of flame

Note: This indication may flash temporarily

 

rod, burner ground connection.

 

during or shortly after lightoff on some appli-

 

 

 

cations.

 

 

No Flame or Flame Signal -

 

OFF

below minimum threshold for system

N/A

 

operation.

 

aFlash Code Descriptions

-Heartbeat: Constant ½ second bright, ½ second dim cycles.

-The flash code number signifies that the LED flashes X times at 2Hz, remains off for two seconds, and then repeats sequence.

66

Page 66