OPEN-DRIVE COMPRESSORS

These compressors are designed to operate with Refriger- ants 12, 22, 134a, 502, or 507/404A. See Table 1.

Operating Requirements — Satisfactory operation of a reciprocating compressor depends on 3 fundamental requirements:

1.Prevention of excess discharge temperature.

2.Adequate compressor lubrication.

3.A clean and dry system.

Discharge Temperature — The temperature at the discharge valves within the cylinders is a controlling factor. Some cooling of the discharge gas occurs before reaching the discharge stop valve, thus when water-cooled heads are used, this cooling is greater than it is without water cooling. To pre- vent excessive temperature at the compressor discharge valves, the following temperatures, when measured immediately following the discharge stop valve, must never be exceeded:

For nonwater-cooled heads . . . . . . . . . . . . . . . . . . 275 F max For water-cooled heads . . . . . . . . . . . . . . . . . . . . . 250 F max

The approximate discharge gas temperature can be found by using the following equation:

 

 

 

 

 

N – 1

 

 

 

T2 = T1 (

P2

) N

 

 

P1

Where:

 

 

 

 

 

T2

=

Discharge temperature, F absolute

T1

=

Suction temperature, F absolute (including

 

 

superheat)

P2

=

Discharge pressure, psia

P1

=

Suction pressure, psia

N= Compression exponent of the gas (see Table 2)

Table 2 — Compression Exponent “N”

COMPRESSION

 

 

WITHOUT

 

WITH

 

RATIO

 

WATER-COOLED

WATER-COOLED

=

Discharge

 

 

 

HEADS*

 

HEADS

 

 

 

 

 

 

 

R-22

Suction psia

 

R-12

 

R-22

R-502

 

 

 

 

 

 

 

 

2

 

1.216

 

1.325

 

1.234

1.240

 

3

 

1.191

 

1.258

 

1.216

1.218

 

4

 

1.177

 

1.240

 

1.206

1.205

 

5

 

1.172

 

1.234

 

1.197

1.199

 

6

 

1.166

 

1.232

 

1.190

1.196

 

8

 

1.160

 

1.228

 

1.178

1.192

 

10

 

1.155

 

1.225

 

1.169

1.187

 

12

 

1.150

 

1.224

 

1.161

1.182

*For R-134a and R-507/404A refer to the Carlyle Compressor Selection program (http://www.carlylecompressor.com/TechnicalInfo/Carwin.htm) to determine discharge temperature. The selection program can also be used for R-22 and R-502 in place of the discharge temperature formulas.

The value of compression exponent “N” depends upon the properties of gas compressed, degree of cooling in compressor jacket, leakages, etc.

To simplify discharge temperature calculations, the preced- ing formula may be stated in the following form:

T2

= [(460 + T1) x C] – 460

Where:

T2

=

Discharge temperature, F actual

T1

=

Suction gas temperature, F actual (including

 

 

superheat)

N – 1

( P2 ) N

C =

P1

Values for “C” at various compression ratios are listed in Table 3.

Table 3 — “C” Factors

COMPRESSION

 

WITHOUT

 

WITH

 

RATIO

WATER-COOLED

WATER-COOLED

= Discharge psia

 

 

HEADS*

 

HEADS

 

Suction psia

 

R-12

 

R-22

R-502

R-22

 

 

 

2

 

1.14

 

1.17

 

1.13

1.15

3

 

1.19

 

1.25

 

1.22

1.22

4

 

1.23

 

1.31

 

1.27

1.27

5

 

1.26

 

1.36

 

1.30

1.31

6

 

1.29

 

1.40

 

1.33

1.34

8

 

1.33

 

1.47

 

1.37

1.40

10

 

1.36

 

1.53

 

1.40

1.44

12

 

1.38

 

1.57

 

1.41

1.47

*For R-134a and R-507/404A refer to the Carlyle Compressor Selection program (http://www.carlylecompressor.com/TechnicalInfo/Carwin.htm) to determine discharge temperature. The selection program can also be used for R-22 and R-502 in place of the discharge temperature formulas.

Example:

 

 

Refrigerant 12

 

 

Compression Ratio

P2

= 8

P

 

 

 

1

 

Factor C = 1.33

Suction Temperature, T1 = 0° F saturated, superheated to 65 F

Solution:

T2 = [(460 + 65) x 1.33] – 460

=698 – 460

=238 F

Although exponents are shown for high compression ratios, these are for information only. Rating tables define allowable selection and operation limits.

High Compression Ratio — Avoid compressor oper- ation at compressor ratios exceeding those covered in the rating tables. For operating conditions outside the limits shown in these tables, use 2-stage compression. Care must be taken to prevent the compressor from pulling down to levels outside the rating tables.

Suction Gas Superheat — Excessive suction gas super- heat will result in abnormally high discharge temperatures, which must be avoided. When using Refrigerants 12, 134a, 502, and 507/404A it is recommended that the actual suction gas temperature not exceed the values in Table 4.

Table 4 — Actual Suction Gas Temperature

Limits (F) Refrigerants 12, 134a, 502, and

507/404A*

SATURATED SUCTION

–60

–50

–40

–30

–20

–10

0 AND

GAS TEMP

ABOVE

Actual

R-12

35

45

55

65

65

R-134a

65

Suction

Gas Temp

R-502

25

35

45

55

65

65

65

 

R-507/404A

 

 

 

 

 

 

 

 

*With Refrigerant 22, the suction gas superheat should never exceed 25 F for continuous operation.

Keeping Liquid Refrigerant Out of Compres- sor — Liquid refrigerant, or excessive amounts of entrained liquid particles in suction gas must be kept out of the compres- sor by proper system design and compressor control. Under operating conditions, presence of unevaporated liquid refriger- ant in the compressor tends to break down oil film on cylinder walls, resulting in increased wear and loss of machine capacity.

During compressor operation, proper adjustment of the expansion valve will prevent excessive amounts of liquid from entering the compressor.

2

Page 2
Image 2
Carrier 09RH specifications Compression Exponent N, Factors, Compression Without Ratio WATER-COOLED, Heads