CONTROLS AND COMPONENTS
Figure 1 shows the major components of the PPS system.
Pumpout Unit Ð The pumpout unit consists of a spring- mounted direct
CONTROLS Ð The pumpout unit has the following con- trols: an on/off switch, a
SAFETY CONTROL SETTINGS Ð The pumpout unit high- pressure switch (Fig. 1) is set to open at the settings listed in Table 5. The switch setting is checked by operating the pumpout condenser and slowly throttling the pumpout con- denser water.
Table 5 Ð High Condition Pressure Switch Settings
English
REFRIGERANT |
| |||
Cutout | CutIn | |||
| ||||
161 ± 5 psig |
| + 0 | ||
130 | − 5 psig | |||
|
| |||
220 ± 5 psig |
| + 0 | ||
185 | − 5 psig | |||
|
| |||
| SI |
|
| |
REFRIGERANT | ||||
Cutout | ||||
| ||||
1110 ± 34 kPa |
| + 0 | ||
896 | − 34 kPa | |||
|
| |||
1517 ± 34 kPa |
| + 0 | ||
1276 | − 34 kPa | |||
|
|
NOTES:
1.
2.
COMPRESSOR Ð The pumpout compressor assembly has a positive displacement of 1750 rpm (29 r/s) and 8.7 cfm (0.004 m3/s). It comes equipped with thermal protection on the motor and an
CONDENSER Ð The
OIL SEPARATOR Ð The pumpout unit includes an
SUCTION AND DISCHARGE VALVES Ð The pumpout unit comes with a
Storage Tank Ð The storage tank is rated for positive pressure refrigerants under ASME Section VIII pressure ves- sel codes with a minimum of 300 psig (2068 kPa) rating. The tank components include:
DRAIN VALVE Ð Located at its lowest point of drain with a minimum of 1 in. NPT.
DUAL RELIEF VALVES Ð Two relief valves and a
PRESSURE GAGE Ð A 30
LEVEL GAGE Ð Liquid level gage (magnetically coupled dial type) with electronic
During transfer of refrigerant into and out of the pump- out storage tank, carefully monitor the storage tank level gage. Do not ®ll the tank more than 90% of capacity to allow for refrigerant expansion. Over®lling may result in damage to the tank and personal injury. For maxi- mum refrigerant capacity, refer to Table 2.
OPERATION
Overview Ð Transferring refrigerant from one vessel to another is accomplished by using either gravity or pressure differential. A difference in elevation between 2 vessels re- sults in a gravity ¯ow of liquid; a difference in pressure forces the liquid from one vessel to the other. The latter method requires lowering the pressure in one vessel. If there is liq- uid in that vessel, its temperature must be lowered, and the pressure in the other vessel must be simultaneously increased.
Under most circumstances, creating the pressure differ- ential is not a difficult process. Some applications, such as ice storage, outdoor installations, or installations with high temperature differentials between the storage tank and the chiller may require additional consideration. In some in- stances, it may be necessary to add auxiliary heat to one of the vessels or to insulate the storage tank at job sites where high ambient temperature or sun load make it difficult to re- duce the temperature and pressure in the tank. Outdoor in- stallations must have a roof or cover over the storage tank to ensure that the pressure in the tank does not exceed the chiller relief pressure setting.
REFRIGERANT TRANSFER Ð When refrigerant is being evacuated from the chiller cooler or condenser vessels, any liquid refrigerant left in a vessel will ¯ash off, lowering the temperature in that vessel enough to freeze the ¯uid (usually water) ¯owing through the cooler or condenser tubes. This event, called tube
TRANSFERRING LIQUID REFRIGERANT FROM THE CHILLER COOLER TO THE CHILLER CONDENSER OR PUMPOUT STORAGE TANK Ð Chiller and pumpout unit valves are set to permit the pumpout compressor to dis- charge refrigerant vapor into the cooler vessel, lowering pres- sure in the condenser vessel/storage tank. The pressure dif- ferential forces liquid from the cooler vessel into the condenser vessel/storage tank. After all the liquid is transferred, the re- frigerant vapor remaining in the cooler vessel can be drawn off by reducing pressure in the chiller and discharging the vapor through the pumpout unit condenser into the con- denser vessel/storage tank.
TRANSFERRING LIQUID REFRIGERANT FROM THE CHILLER CONDENSER OR PUMPOUT STORAGE TANK TO THE CHILLER COOLER Ð Chiller and pumpout unit valves are set to increase pressure in the chiller condenser vessel/storage tank and to reduce pressure in the cooler ves- sel. Pressure in the cooler vessel is lowered to correspond to a saturated refrigerant liquid temperature 2 F (1.1 C) above the freezing temperature of the liquid circulating through the chiller cooler/condenser tubes (34 F [1.1 C] for water). The valves are set so that the pressure in the cooler vessel is lower than that of the condenser vessel/storage tank, forcing the liquid into the cooler vessel.
11